Knowledge (XXG)

ANSI device numbers

Source πŸ“

917:
denote a "ground", hence a "51G" is a time overcurrent ground relay. The "G" suffix can also mean "generator", hence an "87G" is a Generator Differential Protective Relay while an "87T" is a Transformer Differential Protective Relay. "F" can denote "field" on a generator or "fuse", as in the protective fuse for a pickup transformer. Suffix numbers are used to distinguish multiple "same" devices in the same equipment such as 51–1, 51–2.
923:
For device 16, the suffix letters further define the device: the first suffix letter is 'S' for serial or 'E' for Ethernet. The subsequent letters are: 'C' security processing function (e.g. VPN, encryption), 'F' firewall or message filter, 'M' network managed function, 'R' rotor, 'S' switch and 'T'
916:
A suffix letter or number may be used with the device number; for example, suffix N is used if the device is connected to a Neutral wire (example: 59N in a relay is used for protection against Neutral Displacement); and suffixes X, Y, Z are used for auxiliary devices. Similarly, the "G" suffix can
978:
It may surprise some to learn that this standardβ€”or more accurately its AIEE predecessorβ€”is one of the oldest IEEE standards in use. It was first published as AIEE No. 26 in 1928 and was used to document the control systems in the then popular automatic railway
70:-based relays can perform many protective functions in one device. When one device performs several protective functions, it is typically denoted "11" by the standard as a "Multifunction Device", but ANSI Device Numbers are still used in documentation like 993:
Applied Protective Relaying 1979 by Westinghouse Electric Corporation, 2nd Printing, "Appendix II, Electrical Power System Device Numbers and Functions" as adopted by IEEE standard and incorporated in American Standard
1018: 961: 177:
24 – Volts per Hertz Relay (in some old analog applications, a 59 and an 81 device would be chained together as a 59/81 to implement the equivalent of V/Hz protection)
82: 920:
Device numbers may be combined if the device provides multiple functions, such as the Instantaneous / Time-delay Overcurrent relay denoted as 50/51.
44: 58:
Many of these devices protect electrical systems and individual system components from damage when an unwanted event occurs such as an
1023: 81:
ANSI/IEEE C37.2-2008 is one of a continuing series of revisions of the standard, which originated in 1928 as
24: 20: 1003:
IEEE Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations'
942: 75: 71: 53:
Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations
63: 59: 40: 36: 468:
66 - Notching or Jogging Device/Maximum Starting Rate/Starts per Hour/Time Between Starts
67: 1012: 582:
87N - Neutral Differential Protection / Restricted Earth Fault (REF) see also 87RGF
62:. Historically, a single protective function was performed by one or more distinct 285:
46 - Reverse-Phase or Phase Balance Current Relay or Stator Current Unbalance
384:
52b - AC Circuit Breaker Position (contact closed when circuit breaker open)
777:
C - Capacitor, Condenser, Compensator, Carrier Current, Case or Compressor
381:
52a - AC Circuit Breaker Position (contact open when circuit breaker open)
540:
81R - common industry use for Rate Of Change Of Frequency Relay (ROCOF)
924:
telephone component. Thus a managed Ethernet switch would be 16ESM.
78:
to indicate which specific functions are performed by that device.
360:
51LR - AC Inverse Time Overcurrent (Locked Rotor) Protection Relay
117: 32: 31:
can be used to identify equipment and devices in a system such as
849:
S - Synchronizing, Secondary, Strainer, Sump, or Suction (Valve)
48: 116:
7F - Alternative number for Rate Of Change Of Frequency Relay (
962:"Knowing the Language: The History and Practice of IEEE C37.2" 653:
For specific applications where other numbers are not suitable
647:
For specific applications where other numbers are not suitable
641:
For specific applications where other numbers are not suitable
66:
devices, so each device would receive its own number. Today,
294:
49 - Machine or Transformer Thermal Relay / Thermal Overload
522:
78 - Phase Angle Measuring or Out-of-Step Protective Relay
249:
35 - Brush-Operating or Slip-ring Short Circuiting Device
282:
45 - Atmospheric Condition Monitor (fumes, smoke, fire)
555:
85 - Pilot Communications, Carrier or Pilot-Wire Relay
303:
50BF - Breaker Failure or LBB (Local Breaker Back-up)
101:
3 - Checking or Interlocking Relay, complete Sequence
342:
50/51 - Instantaneous / Time-delay Overcurrent relay
843:
PUTT - Putt: Permissive Underreaching Transfer Trip
840:POTT - Pott: Permissive Overreaching Transfer Trip 549:83 - Automatic Selective Control or Transfer Relay 288:47 - Phase-Sequence or Phase Balance Voltage Relay 336:50Q - Negative Sequence Instantaneous Overcurrent 330:50SG - Sensitive Ground Instantaneous Overcurrent 183:26 – Apparatus Thermal Device, Temperature Switch 159:20 - Electrically-Operated Valve (Solenoid Valve) 315:50IG - Isolated Ground Instantaneous Overcurrent 1019:American National Standards Institute standards 489:67Q - Negative Sequence Directional Overcurrent 486:67SG - Sensitive Ground Directional Overcurrent 291:48 - Incomplete Sequence Relay / Blocked Rotor 180:25 – Synchronizing or Synchronism-check Device 16:System of identifying electrical power devices 324:50NBF - Neutral Instantaneous Breaker Failure 264:39 - Mechanical Condition Monitor (Vibration) 156:19 - Starting-to-Running Transition Contactor 8: 717:RTU – Remote Terminal Unit/Data Concentrator 591:87RGF - Restricted Ground Fault see also 87N 261:38 - Bearing Protective Device / Bearing Rtd 807:F - Feeder, Field, Filament, Filter, or Fan 459:64S - Sub-harmonic Stator Ground Protection 453:64REF – Restricted Earth Fault Differential 573:87L - Segregated Line Current Differential 492:68 - Blocking Relay / Power Swing Blocking 252:36 - Polarity or Polarizing Voltage Device 234:32N - Wattmetric Zero-Sequence Directional 195:27TN - Third Harmonic Neutral Undervoltage 107:5 - Stopping Device, Emergency Stop Switch 83:American Institute of Electrical Engineers 801:DUTT - Direct Underreaching Transfer Trip 570:87GT - Generator/Transformer Differential 438:62 - Time-Delay Stopping or Opening Relay 399:57 - Short-Circuiting or Grounding Device 372:51V - Voltage Restrained Time Overcurrent 354:51C - Voltage Controlled Time Overcurrent 885:TT - Transformer (Tertiary-Voltage Side) 795:DCUB - Directional Comparison Unblocking 624:92 - Voltage And Power Directional Relay 375:51Q - Negative Sequence Time Overcurrent 333:50SP - Split Phase Instantaneous Current 153:18 - Accelerating or Decelerating Device 98:2 - Time-delay Starting or Closing Relay 933: 864:TDDO - Time Delayed Relay Coil Drop-Out 612:88 - Auxiliary Motor or Motor Generator 576:87LG - Ground Line Current Differential 321:50N - Neutral Instantaneous Overcurrent 276:43 - Manual Transfer or Selector Device 174:23 – Temperature control device, Heater 144:15 - Speed or Frequency Matching Device 43:. The device numbers are enumerated in 558:86 - Lock-Out Relay, Master Trip Relay 528:79 - AC Reclosing Relay / Auto Reclose 519:77 - Telemetering Device, Speed Sensor 312:50G - Ground Instantaneous Overcurrent 123:8 - Control Power Disconnecting Device 989: 987: 870:TDPU - Time Delayed Relay Coil Pickup 792:DCB - Directional Comparison Blocking 714:RTD - Resistance Temperature Detector 477:67N - Neutral Directional Overcurrent 471:67 - AC Directional Overcurrent Relay 426:60 - Voltage or Current Balance Relay 327:50P - Phase Instantaneous Overcurrent 267:40 - Field Relay / Loss of Excitation 255:37 - Undercurrent or Underpower Relay 204:27 AUX - Undervoltage Auxiliary Input 7: 941:Kunsman, Steven (December 1, 2011). 876:TH - Transformer (High-Voltage Side) 474:67G - Ground Directional Overcurrent 300:50 - Instantaneous Overcurrent Relay 879:TL - Transformer (Low-Voltage Side) 726:LRSS – Local/Remote selector switch 687:HIZ – High Impedance Fault Detector 681:DME – Disturbance Monitor Equipment 483:67P - Phase Directional Overcurrent 423:59Q - Negative Sequence Overvoltage 306:50DD - Current Disturbance Detector 297:49RTD - RTD Biased Thermal Overload 89:List of device numbers and acronyms 675:DDR – Dynamic Disturbance Recorder 561:87 - Differential Protective Relay 387:53 - Exciter or DC Generator Relay 348:50/87 - Instantaneous Differential 198:27TN/59N - 100% Stator Earth Fault 14: 960:Tengdin, John (1 February 2009). 720:SER – Sequence of Events Recorder 390:54 - Turning Gear Engaging Device 279:44 - Unit Sequence Starting Relay 150:17 - Shunting or Discharge Switch 867:TDO - Time-Delay Opening Contact 861:TDC - Time-Delay Closing Contact 825:MOC - Mechanism Operated Contact 711:RIO – Remote Input/Output Device 630:94 - Tripping or Trip-Free Relay 513:75 - Position Changing Mechanism 501:71 - Liquid Switch, Level Switch 414:59NU - Neutral Voltage Unbalance 402:58 - Rectification Failure Relay 339:50/27 - Inadvertent Energization 210:27/50 - Inadvertent Energization 873:THD - Total Harmonic Distortion 846:R - Reactor, Rectifier, or Room 606:87U - Unrestrained Differential 429:60N - Neutral Current Unbalance 222:31 - Separate Excitation Device 147:16 - Data Communications Device 943:"The Protective Relay Evolves" 702:PDC – Phasor Data Concentrator 621:91 - Voltage Directional Relay 603:87T - Transformer Differential 495:69 - Permissive Control Device 480:67Ns – Earth Fault Directional 363:51N - Neutral Time Overcurrent 351:51 - AC Time Overcurrent Relay 207:27/27X - Bus/Line Undervoltage 171:22 – Equalizer Circuit Breaker 1: 705:PMU – Phasor Measurement Unit 690:HMI – Human Machine Interface 627:93 - Field-Changing Contactor 594:87R - Restrained Differential 531:80 - Liquid or Gas Flow Relay 447:64F - Field Ground Protection 441:63 - Pressure Switch Detector 435:61 - Density Switch or Sensor 432:60P - Phase Current Unbalance 357:51G - Ground Time Overcurrent 138:13 - Synchronous-Speed Device 855:T - Transformer or Thyratron 678:DFR – Digital Fault Recorder 669:CLK - Clock or Timing Source 567:87G - Generator Differential 507:73 - Load-Resistor Contactor 444:64 - Ground Protective Relay 408:59B - Bank Phase Overvoltage 396:56 - Field Application Relay 369:51R - Locked / Stalled Rotor 366:51P - Phase Time Overcurrent 273:42 - Running Circuit Breaker 231:32H - High Directional Power 225:32 - Directional Power Relay 201:27X - Auxiliary Undervoltage 110:6 - Starting Circuit Breaker 756:B - Bus, Battery, or Blower 708:PQM – Power Quality Monitor 420:59X - Auxiliary Overvoltage 309:50EF - End Fault Protection 246:34 - Master Sequence Device 192:27S - DC Undervoltage Relay 1040: 966:Electric Light & Power 747:A - Alarm, Auxiliary Power 723:TCM – Trip Circuit Monitor 609:87V - Voltage Differential 600:87S - Percent Differential 585:87O - Overall Differential 270:41 - Field Circuit Breaker 852:SOTF - Switch On To Fault 798:DD - Disturbance Detector 699:MET – Substation Metering 633:95 – Trip Circuit Healthy 597:87S - Stator Differential 516:76 - DC Overcurrent Relay 462:64TN - 100% Stator Ground 411:59N - Neutral Overvoltage 132:11 - Multifunction Device 129:10 - Unit Sequence Switch 947:Power Grid International 750:AC - Alternating Current 684:ENV – Environmental Data 666:AFD - Arc Flash Detector 579:87M - Motor Differential 552:84 - Operating Mechanism 456:64S – Stator Earth Fault 318:50LR - Acceleration Time 216:29 - Isolating Contactor 189:27P - Phase Undervoltage 113:7 - Rate of Change Relay 810:G - Ground or Generator 588:87PC - Phase Comparison 546:82 - DC Reclosing Relay 504:72 - DC Circuit Breaker 450:64R – Rotor Earth Fault 417:59P - Phase Overvoltage 393:55 - Power Factor Relay 378:52 – AC Circuit Breaker 237:32P - Directional Power 228:32L - Low Forward Power 186:27 – Undervoltage Relay 968:. PennWell Corporation 828:N - Neutral or Network 744:_2 - Negative-Sequence 741:_1 - Positive-Sequence 672:CLP - Cold Load Pickup 618:90 - Regulating Device 564:87B - Bus Differential 405:59 - Overvoltage Relay 219:30 - Annunciator Relay 141:14 - Underspeed Device 21:electric power systems 1024:Electrical components 1005:, IEEE Std C37.2-2008 912:Suffixes and prefixes 837:PC - Phase Comparison 822:M - Motor or Metering 816:H - Heater or Housing 786:D - Discharge (Valve) 543:81U - Under Frequency 165:21G - Ground Distance 135:12 - Overspeed Device 104:4 - Master Protective 25:industrial automation 759:BF - Breaker Failure 735:Suffixes Description 660:Acronyms Description 537:81O - Over Frequency 534:81 - Frequency Relay 243:33 - Position Switch 168:21P - Phase Distance 126:9 - Reversing Device 72:single-line diagrams 789:DC - Direct Current 729:VTFF - Vt Fuse Fail 525:78V - Loss of Mains 240:32R - Reverse Power 213:28 - Flame Detector 162:21 - Distance Relay 29:ANSI Device Numbers 783:CH - Check (Valve) 765:BL - Block (Valve) 696:LGC – Scheme Logic 345:50/74 - CT Trouble 95:1 - Master Element 900:U - Under or Unit 834:P - Phase or Pump 819:L - Line or Logic 813:GC - Ground Check 85:Standard No. 26. 64:electromechanical 1031: 995: 991: 982: 981: 975: 973: 957: 951: 950: 938: 636:96 – Transmitter 615:89 - Line Switch 510:74 - Alarm Relay 258:37P - Underpower 60:electrical fault 37:circuit breakers 1039: 1038: 1034: 1033: 1032: 1030: 1029: 1028: 1009: 1008: 999: 998: 992: 985: 971: 969: 959: 958: 954: 940: 939: 935: 930: 914: 909: 858:TD - Time Delay 693:HST – Historian 91: 51:Standard C37.2 17: 12: 11: 5: 1037: 1035: 1027: 1026: 1021: 1011: 1010: 1007: 1006: 997: 996: 983: 952: 932: 931: 929: 926: 913: 910: 908: 907: 904: 901: 898: 895: 892: 889: 886: 883: 882:TM - Telemeter 880: 877: 874: 871: 868: 865: 862: 859: 856: 853: 850: 847: 844: 841: 838: 835: 832: 829: 826: 823: 820: 817: 814: 811: 808: 805: 802: 799: 796: 793: 790: 787: 784: 781: 778: 775: 772: 769: 766: 763: 760: 757: 754: 751: 748: 745: 742: 731: 730: 727: 724: 721: 718: 715: 712: 709: 706: 703: 700: 697: 694: 691: 688: 685: 682: 679: 676: 673: 670: 667: 656: 655: 649: 643: 637: 634: 631: 628: 625: 622: 619: 616: 613: 610: 607: 604: 601: 598: 595: 592: 589: 586: 583: 580: 577: 574: 571: 568: 565: 562: 559: 556: 553: 550: 547: 544: 541: 538: 535: 532: 529: 526: 523: 520: 517: 514: 511: 508: 505: 502: 499: 496: 493: 490: 487: 484: 481: 478: 475: 472: 469: 466: 463: 460: 457: 454: 451: 448: 445: 442: 439: 436: 433: 430: 427: 424: 421: 418: 415: 412: 409: 406: 403: 400: 397: 394: 391: 388: 385: 382: 379: 376: 373: 370: 367: 364: 361: 358: 355: 352: 349: 346: 343: 340: 337: 334: 331: 328: 325: 322: 319: 316: 313: 310: 307: 304: 301: 298: 295: 292: 289: 286: 283: 280: 277: 274: 271: 268: 265: 262: 259: 256: 253: 250: 247: 244: 241: 238: 235: 232: 229: 226: 223: 220: 217: 214: 211: 208: 205: 202: 199: 196: 193: 190: 187: 184: 181: 178: 175: 172: 169: 166: 163: 160: 157: 154: 151: 148: 145: 142: 139: 136: 133: 130: 127: 124: 121: 114: 111: 108: 105: 102: 99: 96: 92: 90: 87: 68:microprocessor 15: 13: 10: 9: 6: 4: 3: 2: 1036: 1025: 1022: 1020: 1017: 1016: 1014: 1004: 1001: 1000: 990: 988: 984: 980: 967: 963: 956: 953: 948: 944: 937: 934: 927: 925: 921: 918: 911: 906:Z - Impedance 905: 903:X - Auxiliary 902: 899: 896: 893: 890: 888:Q - Lube Oil 887: 884: 881: 878: 875: 872: 869: 866: 863: 860: 857: 854: 851: 848: 845: 842: 839: 836: 833: 830: 827: 824: 821: 818: 815: 812: 809: 806: 803: 800: 797: 794: 791: 788: 785: 782: 779: 776: 773: 770: 767: 764: 761: 758: 755: 752: 749: 746: 743: 740: 739: 738: 737: 736: 728: 725: 722: 719: 716: 713: 710: 707: 704: 701: 698: 695: 692: 689: 686: 683: 680: 677: 674: 671: 668: 665: 664: 663: 662: 661: 654: 650: 648: 644: 642: 638: 635: 632: 629: 626: 623: 620: 617: 614: 611: 608: 605: 602: 599: 596: 593: 590: 587: 584: 581: 578: 575: 572: 569: 566: 563: 560: 557: 554: 551: 548: 545: 542: 539: 536: 533: 530: 527: 524: 521: 518: 515: 512: 509: 506: 503: 500: 498:70 - Rheostat 497: 494: 491: 488: 485: 482: 479: 476: 473: 470: 467: 465:65 - Governor 464: 461: 458: 455: 452: 449: 446: 443: 440: 437: 434: 431: 428: 425: 422: 419: 416: 413: 410: 407: 404: 401: 398: 395: 392: 389: 386: 383: 380: 377: 374: 371: 368: 365: 362: 359: 356: 353: 350: 347: 344: 341: 338: 335: 332: 329: 326: 323: 320: 317: 314: 311: 308: 305: 302: 299: 296: 293: 290: 287: 284: 281: 278: 275: 272: 269: 266: 263: 260: 257: 254: 251: 248: 245: 242: 239: 236: 233: 230: 227: 224: 221: 218: 215: 212: 209: 206: 203: 200: 197: 194: 191: 188: 185: 182: 179: 176: 173: 170: 167: 164: 161: 158: 155: 152: 149: 146: 143: 140: 137: 134: 131: 128: 125: 122: 119: 115: 112: 109: 106: 103: 100: 97: 94: 93: 88: 86: 84: 79: 77: 73: 69: 65: 61: 56: 54: 50: 46: 42: 38: 34: 30: 26: 22: 1002: 979:substations. 977: 970:. Retrieved 965: 955: 946: 936: 922: 919: 915: 780:CA - Cathode 771:BT - Bus Tie 734: 733: 732: 659: 658: 657: 652: 646: 640: 80: 57: 52: 28: 18: 994:C37.2-1970. 804:E - Exciter 774:BU - Backup 768:BP - Bypass 41:instruments 1013:Categories 972:18 October 928:References 891:W - Water 762:BK - Brake 753:AN - Anode 76:schematics 894:F - Fuel 897:G - Gas 831:O - Over 33:relays 651:99 – 645:98 – 639:97 – 118:ROCOF 39:, or 974:2017 49:IEEE 45:ANSI 23:and 74:or 19:In 1015:: 986:^ 976:. 964:. 945:. 55:. 35:, 27:, 949:. 120:) 47:/

Index

electric power systems
industrial automation
relays
circuit breakers
instruments
ANSI
IEEE
electrical fault
electromechanical
microprocessor
single-line diagrams
schematics
American Institute of Electrical Engineers
ROCOF
"The Protective Relay Evolves"
"Knowing the Language: The History and Practice of IEEE C37.2"


Categories
American National Standards Institute standards
Electrical components

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.

↑