1090:
Connected equipment will not work without a neutral, but the RCD cannot protect people from contact with the energized wire. For this reason circuit breakers must be installed in a way that ensures that the neutral wire cannot be switched off unless the live wire is also switched off at the same time. Where there is a requirement for switching off the neutral wire, two-pole breakers (or four-pole for 3-phase) must be used. To provide some protection with an interrupted neutral, some RCDs and RCBOs are equipped with an auxiliary connection wire that must be connected to the earth busbar of the distribution board. This either enables the device to detect the missing neutral of the supply, causing the device to trip, or provides an alternative supply path for the tripping circuitry, enabling it to continue to function normally in the absence of the supply neutral.
359:
372:
1650:
requirement for supplementary bonding in those locations. Two RCDs may be used to cover the installation, with upstairs and downstairs lighting and power circuits spread across both RCDs. When one RCD trips, power is maintained to at least one lighting and power circuit. Other arrangements, such as the use of RCBOs, may be employed to meet the regulations. The new requirements for RCDs do not affect most existing installations unless they are rewired, the distribution board is changed, a new circuit is installed, or alterations are made such as additional socket outlets or new cables buried in walls.
1026:
1498:
516:
local building and safety departments. The code is An ungrounded GFI receptacle will trip using the built-in "test" button, but will not trip using a GFI test plug, because the plug tests by passing a small current from line to the non-existent ground. It is worth noting that despite this, only one GFCI receptacle at the beginning of each circuit is necessary to protect downstream receptacles. There does not appear to be a risk of using multiple GFI receptacles on the same circuit, though it is considered redundant.
396:
1188:, suffered from accidental trips mainly caused by poor or inconsistent insulation on the wiring. False trips were frequent when insulation problems were compounded by long circuit lengths. So much current leaked along the length of the conductors' insulation that the breaker might trip with the slightest increase of current imbalance. The migration to outlet-receptacle–based protection in North American installations reduced the accidental trips and provided obvious verification that wet areas were under
1059:) must be provided. Circuit breakers that combine the functions of an RCD with overcurrent protection respond to both types of fault. These are known as RCBOs and are available in 2-, 3- and 4-pole configurations. RCBOs will typically have separate circuits for detecting current imbalance and for overload current but use a common interrupting mechanism. Some RCBOs have separate levers for residual-current and over-current protection or use a separate indicator for ground faults.
575:
42:
893:'T' (time-delayed) RCDs have a short time delay. They are typically used at the origin of an installation for fire protection to discriminate with 'G' devices at the loads, and in circuits containing surge suppressors. They must not trip at one-half of rated current. They provide at least 130 milliseconds delay of tripping at rated current, 60 milliseconds at twice rated, and 50 milliseconds at five times rated. The maximum break time is 500
2589:
3168:
1685:
1206:
1094:
a single-pole RCD will not isolate or disconnect all relevant wires in certain uncommon situations, for example where the return conductor is not being held, as expected, at ground potential, or where current leakage occurs between the return and earth conductors. In these cases, a double-pole RCD will offer protection, since the return conductor would also be disconnected.
1152:, USA, who had estimated electrical shock hazards in humans. This system, with its associated circuit breaker, included overcurrent and short-circuit protection. In addition, the original prototype was able to trip at a lower sensitivity in the presence of an interrupted neutral, thus protecting against an important cause of electrical fire.
602:. Some early RCDs were entirely electromechanical and relied on finely balanced sprung over-centre mechanisms driven directly from the current transformer. As these are hard to manufacture to the required accuracy and prone to drift in sensitivity both from pivot wear and lubricant dry-out, the electronically-amplified type with a more robust
643:
358:
829:
provides a conducting path and connectors for the return (neutral) conductor but this path remains uninterrupted when a fault occurs (sometimes known as "solid neutral"), or that both conductors are disconnected for some faults (such as RCD detected leakage) but only one conductor is disconnected for other faults (such as overload).
1673:) and a second group of circuits is supplied via the RCD. This arrangement had the recognised problems that cumulative earth leakage currents from the normal operation of many items of equipment could cause spurious tripping of the RCD, and that tripping of the RCD would disconnect power from all the protected circuits.
663:
the RCD part, and the outgoing circuit cables must be led through a specially dimensioned terminal tunnel with the current transformer part around it. This can lead to incorrect failed trip results when testing with meter probes from the screw heads of the terminals, rather than from the final circuit wiring.
1660:
If spurious tripping would cause a greater problem than the risk of the electrical accident the RCD is supposed to prevent (examples might be a supply to a critical factory process, or to life support equipment), RCDs may be omitted, providing affected circuits are clearly labelled and the balance of
1616:
Taiwan requires circuits of receptacles in washrooms, balconies, and receptacles in kitchen no more than 1.8 metres from the sink the use of earth leakage circuit breakers. This requirement also apply to circuit of water heater in washrooms and circuits that involves devices in water, lights on metal
1518:
GFCIs are commonly available as an integral part of a socket or a circuit breaker installed in the distribution panelboard. GFCI sockets invariably have rectangular faces and accept so-called Decora face plates, and can be mixed with regular outlets or switches in a multi-gang box with standard cover
1514:
has required devices in certain locations to be protected by GFCIs since the 1960s. Beginning with underwater swimming pool lights (1968) successive editions of the code have expanded the areas where GFCIs are required to include: construction sites (1974), bathrooms and outdoor areas (1975), garages
1093:
Related to this, a single-pole RCD/RCBO interrupts the energized conductor only, while a double-pole device interrupts both the energized and return conductors. Usually this is a standard and safe practice, since the return conductor is held at ground potential anyway. However, because of its design,
695:
resulting from damage in branch circuit wiring as well as extensions to branches such as appliances and cord sets. By detecting arc faults and responding by interrupting power, AFCIs help reduce the likelihood of the home's electrical system being an ignition source of a fire. Dual function AFCI/GFCI
629:
This difference causes a current in the sense coil (6), which is picked up by the sense circuitry (7). The sense circuitry then removes power from the solenoid (5), and the contacts (4) are forced apart by a spring, cutting off the electricity supply to the appliance. A power failure will also remove
515:
In North
America, GFI receptacles can be used in cases where there is no grounding conductor, but they must be labeled as "no equipment ground". This is referenced in the National Electric Code section 406 (D) 2, however codes change and someone should always consult a licensed professional and their
1066:
Whole installations on a single RCD, common in older installations in the UK, are prone to "nuisance" trips that can cause secondary safety problems with loss of lighting and defrosting of food. Frequently the trips are caused by deteriorating insulation on heater elements, such as water heaters and
1063:
neutral contacts in a light fitting; a device cannot differentiate between current flow through an intended load from flow through a person, though the RCD may still trip if the person is in contact with the ground (earth), as some current may still pass through the persons finger and body to earth.
950:
Type B RCDs, in addition to Type A, also respond to steady DC, and higher frequency current, or for combinations of alternating and direct current as may be found from single-phase or multi-phase rectifying circuits, like all the switching power supplies used at home, or for example washing machines
658:
As well as requiring both live and neutral inputs and outputs (or, full three-phase), many GFCI/RCBO devices require a functional earth (FE) connection. This serves to provide both EMC immunity and to reliably operate the device if the input-side neutral connection is lost but live and earth remain.
468:
only break the circuit when the total current is excessive (which may be thousands of times the leakage current an RCD responds to). A small leakage current, such as through a person, can be a very serious fault, but would probably not increase the total current enough for a fuse or overload circuit
1527:
sockets protected by a GFCI (integral with the socket or with the corresponding circuit breaker) in lieu of rewiring the entire circuit with a grounding conductor. In such cases the sockets must be labeled "no equipment ground" and "GFCI protected"; GFCI manufacturers typically provide tags for the
1488:
From
January 2003, all new circuits originating at the switchboard supplying lighting or socket outlets (power points) in domestic buildings must have RCD protection. Residential facilities (such as boarding houses, hospitals, hotels and motels) will also require RCD protection for all new circuits
1258:
Regulations differ widely from country to country. A single RCD installed for an entire electrical installation provides protection against shock hazards to all circuits, however, any fault may cut all power to the premises. A solution is to create groups of circuits, each with an RCD, or to use an
1130:
The cold cathode system was installed in a number of gold mines and worked reliably. However, Rubin began working on a completely novel system with greatly improved sensitivity, and by early 1956, he had produced a prototype second-harmonic magnetic amplifier-type core balance system (South
African
1089:
In the case of RCDs that need a power supply, a dangerous condition can arise if the neutral wire is broken or switched off on the supply side of the RCD, while the corresponding live wire remains uninterrupted. The tripping circuit needs power to work and does not trip when the power supply fails.
892:
There are two groups of devices. 'G' (general use) 'instantaneous' RCDs have no intentional time delay. They must never trip at one-half of the nominal current rating, but must trip within 200 milliseconds for rated current, and within 40 milliseconds at five times rated current. 'S' (selective) or
812:
RCDs with three or more poles can be used on three-phase AC supplies (three current paths) or to disconnect the neutral conductor as well, with four-pole RCDs used to interrupt three-phase and neutral supplies. Specially designed RCDs can also be used with both AC and DC power distribution systems.
650:
Residual-current and over-current protection may be combined in one device for installation into the service panel; this device is known as a GFCI (Ground-Fault
Circuit Interrupter) breaker in the US and Canada, and as a RCBO (residual-current circuit breaker with over-current protection) in Europe
507:
with incorporated RCD are sometimes installed on appliances that might be considered to pose a particular safety hazard, for example long extension leads, which might be used outdoors, or garden equipment or hair dryers, which may be used near a bath or sink. Occasionally an in-line RCD may be used
1649:
requires that all socket outlets in most installations have RCD protection, though there are exemptions. Non armoured cables buried in walls must also be RCD protected (again with some specific exemptions). Provision of RCD protection for circuits present in bathrooms and shower rooms reduces the
1599:
South Africa mandated the use of Earth
Leakage Protection devices in residential environments (e.g. houses, flats, hotels, etc.) from October 1974, with regulations being refined in 1975 and 1976. Devices need to be installed in new premises and when repairs are carried out. Protection is required
768:
The difference between the modes of operation of the essentially two different types of RCD functionality is that the operation for power distribution purposes requires the internal latch to remain set within the RCD after any form of power disconnection caused by either the user turning the power
662:
For reasons of space, many devices, especially in DIN rail format, use flying leads rather than screw terminals, especially for the neutral input and FE connections. Additionally, because of the small form factor, the output cables of some models (Eaton/MEM) are used to form the primary winding of
343:
RCDs are testable and resettable devices—a test button safely creates a small leakage condition, and another button resets the conductors after a fault condition has been cleared. Some RCDs disconnect both the energized and return conductors upon a fault (double pole), while a single pole RCD only
1179:
In 1961, Dalziel, working with Rucker
Manufacturing Co., developed a transistorized device for earth leakage protection which became known as a Ground Fault Circuit Interrupter (GFCI), sometimes colloquially shortened to Ground Fault Interrupter (GFI). This name for high-sensitivity earth leakage
1062:
An RCD helps to protect against electric shock when current flows through a person from a phase (live / line / hot) to earth. It cannot protect against electric shock when current flows through a person from phase to neutral or from phase to phase, for example where a finger touches both live and
1033:
RCDs can be tested with a built-in test button to confirm functionality on a regular basis. RCDs may not operate correctly if wired improperly, so they are generally tested by the installer. By introducing a controlled fault current from live to earth, the operating time and wiring can be tested.
764:
In the fourth situation, it would be deemed to be highly undesirable, and probably very unsafe, for a connected appliance to automatically resume operation after a power disconnection, without having the operator in attendance – as such, manual reactivation of the RCD is necessary.
609:
In the internal mechanism of an RCD, the incoming supply and the neutral conductors are connected to the terminals at (1), and the outgoing load conductors are connected to the terminals at (2). The earth conductor (not shown) is connected through from supply to load uninterrupted. When the reset
1664:
The previous edition of the regulations required use of RCDs for socket outlets that were liable to be used by outdoor appliances. Normal practice in domestic installations was to use a single RCD to cover all the circuits requiring RCD protection (typically sockets and showers) but to have some
828:
1+N and 1P+N – non-standard terms used in the context of RCBOs, at times used differently by different manufacturers. Typically these terms may signify that the return (neutral) conductor is an isolating pole only, without a protective element (an unprotected but switched neutral), that the RCBO
488:
in the installation; the trip will operate just as well if the return path is through plumbing or contact with the ground or anything else. Automatic disconnection and a measure of shock protection is therefore still provided even if the earth wiring of the installation is damaged or incomplete.
1371:
mA protection was mandatory only in rooms where there is water, high power or sensitive equipment (bathrooms, kitchens, IT...). The type of RCD required (A, AC, F) depends upon the type of the equipment that will be connected and the maximum power of the socket outlet. Minimal distances between
625:
Any fault to earth (for example caused by a person touching a live component in the attached appliance) causes some of the current to take a different return path, which means that there is an imbalance (difference) in the current in the two conductors (single-phase case), or, more generally, a
1284:
Austria regulated residual current devices in the Ă–VE E8001-1/A1:2013-11-01 norm (most recent revision). It has been required in private housing since 1980. The maximum activation time must not exceed 0.4 seconds. It needs to be installed on all circuits with power plugs with a maximum leakage
783:
ms. For the fourth situation, there is generally a greater choice of ratings available – generally all lower than the other forms, but lower values often result in more nuisance tripping. Sometimes users apply protection in addition to one of the other forms, when they wish to
633:
The test button (8) allows the correct operation of the device to be verified by passing a small current through the orange test wire (9). This simulates a fault by creating an imbalance in the sense coil. If the RCD does not trip when this button is pressed, then the device must be replaced.
1459:
models, or differential circuit breaker for the mode of operation) for all domestic installations to protect all the lines. The law was recently updated to mandate at least two separate RCDs for separate domestic circuits. Short-circuit and overload protection has been compulsory since 1968.
441:
RCDs are designed to disconnect the circuit if there is a leakage current. In their first implementation in the 1950s, power companies used them to prevent electricity theft where consumers grounded returning circuits rather than connecting them to neutral to inhibit electrical meters from
1102:
The world's first high-sensitivity earth leakage protection system (i.e. a system capable of protecting people from the hazards of direct contact between a live conductor and earth), was a second-harmonic magnetic amplifier core-balance system, known as the magamp, developed in
621:
which surrounds (but is not electrically connected to) the live and neutral conductors. In normal operation, all the current down the live conductor returns up the neutral conductor. The currents in the two conductors are therefore equal and opposite and cancel each other out.
1551:
mA are sometimes deployed in environments (such as computing centers) where a lower threshold would carry an unacceptable risk of accidental trips. These high-current RCDs serve for equipment and fire protection instead of protection against the risks of electrical shocks.
784:
override those with a lower rating. It may be wise to have a selection of type four RCDs available, because connections made under damp conditions or using lengthy power cables are more prone to trip-out when any of the lower ratings of RCD are used; ratings as low as 10
1312:
mA residual current device is required that protects all circuits in "wet rooms" (e.g. bathroom, kitchen) as well as circuits that power certain "wet" appliances (washing machine, tumble dryer, dishwasher). Electrical underfloor heating is required to be protected by a
1175:
in this application, but concluded that the early transistors then available were too unreliable. However, with the advent of improved transistors, the company that he worked for and other companies later produced transistorized versions of earth leakage protection.
1325:
Since NBR 5410 (1997) residual current devices and grounding are required for new construction or repair in wet areas, outdoor areas, interior outlets used for external appliances, or in areas where water is more probable like bathrooms and kitchens.
339:
or serious harm if it persists for more than a small fraction of a second. RCDs are designed to disconnect the conducting wires ("trip") quickly enough to potentially prevent serious injury to humans, and to prevent damage to electrical devices.
796:
The number of poles represents the number of conductors that are interrupted when a fault condition occurs. RCDs used on single-phase AC supplies (two current paths), such as domestic power, are usually one- or two-pole designs, also known as
1192:–required protection. European installations continue to use primarily RCDs installed at the distribution board, which provides protection in case of damage to fixed wiring. In Europe socket-based RCDs are primarily used for retrofitting.
1665:
circuits (typically lighting) not RCD protected. This was to avoid a potentially dangerous loss of lighting should the RCD trip. Protection arrangements for other circuits varied. To implement this arrangement it was common to install a
371:
395:
1271:
A minimum of two RCDs is required per domestic installation. All socket outlets and lighting circuits are to be distributed over circuit RCDs. A maximum of three subcircuits only, may be connected to a single RCD. In
Australia, the
1423:
b) For a place where the floor is likely to be wet or where the wall or enclosure is of low electrical resistance, protection against earth leakage current must be provided by a residual current device of sensitivity not exceeding
1515:(1978), areas near hot tubs or spas (1981), hotel bathrooms (1984), kitchen counter sockets (1987), crawl spaces and unfinished basements (1990), near wet bar sinks (1993), near laundry sinks (2005) and in laundry rooms (2014).
1163:
mA magamp earth leakage protection units were installed in the homes of the mining village during 1957 and 1958. F.W.J. Electrical
Industries, which later changed its name to FW Electrical Industries, continued to manufacture
1501:
A Leviton GFCI "Decora" socket in a North
American kitchen. Local electrical code requires tamper-resistant socket in homes, and requires a GFCI for socket within 1 metre of a sink. The T-slot indicates this device is rated
1267:
In
Australia, residual current devices have been mandatory on power circuits since 1991 and on light circuits since 2000. In Queensland specifically, residual power devices have been compulsory for all new homes since 1992.
484:. If these do not sum to zero, there is a leakage of current to somewhere else (to earth/ground or to another circuit), and the device will open its contacts. Operation does not require a fault current to return through the
678:
mA (or greater) trip current time-delayed RCD is installed, covering the whole installation, and then more sensitive RCDs should be installed downstream of it for sockets and other circuits that are considered high-risk.
1046:
A residual-current circuit breaker cannot remove all risk of electric shock or fire. In particular, an RCD alone will not detect overload conditions, phase-to-neutral short circuits or phase-to-phase short circuits (see
364:
A two-pole, or double-pole, residual-current device. The test button and connect/disconnect switch are colored blue. A fault will trigger the switch to its off (down) position, which in this device would disconnect both
453:. They are an essential part of the automatic disconnection of supply (ADS), i.e. to switch off when a fault develops, rather than rely on human intervention, one of the essential tenets of modern electrical practice.
1489:
originating at the switchboard supplying socket outlets. These RCDs will normally be located at the switchboard. They will provide protection for all electrical wiring and appliances plugged into the new circuits.
1067:
cooker elements or rings. Although regarded as a nuisance, the fault is with the deteriorated element and not the RCD: replacement of the offending element will resolve the problem, but replacing the RCD will not.
805:. A single-pole RCD interrupts only the energized conductor, while a double-pole RCD interrupts both the energized and return conductors. (In a single-pole RCD, the return conductor is usually anticipated to be at
1431:
c) For an installation where hand-held equipment, apparatus or appliance is likely to be used, protection against earth leakage current must be provided by a residual current device of sensitivity not exceeding
1183:
In the early 1970s most North American GFCI devices were of the circuit breaker type. GFCIs built into the outlet receptacle became commonplace beginning in the 1980s. The circuit breaker type, installed into a
1338:
mA RCDs on all circuits that are rated for less than 20 A (circuits at greater rating are mostly used for distribution). RCDs became mandatory in 1975 for new buildings, and then for all buildings in 2008.
1468:
In the latest guidelines for electrical wiring in residential buildings (2008) handbook, the overall residential wiring need to be protected by a residual current device of sensitivity not exceeding 100
1143:
mA. Very rapid tripping times were achieved through a novel design, and this combined with the high sensitivity was well within the safe current–time envelope for ventricular fibrillation determined by
2175:
1401:
1009:
The surge current refers to the peak current an RCD is designed to withstand using a test impulse of specified characteristics. The IEC 61008 and IEC 61009 standards require that RCDs withstand a 200
305:. This type of circuit interrupter cannot protect a person who touches both circuit conductors at the same time, since it then cannot distinguish normal current from that passing through a person.
590:
The diagram depicts the internal mechanism of a residual-current device (RCD). The device is designed to be wired in-line in an appliance power cord. It is rated to carry a maximal current of 13
512:, or wiring that does not contain a grounding conductor. The in-line RCD can also have a lower tripping threshold than the building to further improve safety for a specific electrical device.
1439:
d) For an installation other than the installation in (a), (b) and (c), protection against earth leakage current must be provided by a residual current device of sensitivity not exceeding 100
928:
mA 'G' type for each final circuit. In this way, a failure of a device to detect the fault will eventually be cleared by a higher-level device, at the cost of interrupting more circuits.
433:). Section 210.8 of this installation Code is the primary reference for the installation requirements of the GFCI but other requirements can be found in Chapters 5, 6, and 7 of the NEC.
1600:
for power outlets and lighting, with the exception of emergency lighting that should not be interrupted. The standard device used in South Africa is indeed a hybrid of ELPD and RCCB.
508:
to serve a similar function to one in a plug. By putting the RCD in the extension lead, protection is provided at whatever outlet is used even if the building has old wiring, such as
1669:
incorporating an RCD in what is known as a split load configuration, where one group of circuit breakers is supplied direct from the main switch (or time delay RCD in the case of a
1510:
In North America socket-outlets located in places where an easy path to ground exists—such as wet areas and rooms with uncovered concrete floors—must be protected by a GFCI. The US
1001:
and notes that these designations have been introduced because some designs of type A and AC RCD can be disabled if a DC current is present that saturates the core of the detector.
772:
Situation two is mostly installed just as described above, but some wall socket RCDs are available to fit the fourth situation, often by operating a switch on the fascia panel.
252:
2065:(states that there is "2 pole switching of phase and neutral ", but then only identifies the energized conductor as being protected against "overloads and short circuits").
425:, and has a trip threshold to ensure let-go can occur. The Let-go threshold was established through testing by C. F. Dalziel and published as part of an IEEE Paper titled "
1405:(VDE) 0100-410 Nr. 411.3.3). It is not allowed to use type "AC" RCDs since 1987, to be used to protect humans against electrical shocks. It must be Type "A" or type "B".
1115:, and Rubin, an engineer at the company C.J. Fuchs Electrical Industries of Alberton Johannesburg, initially developed a cold-cathode system in 1955 which operated at 525
968:
for composite residual currents, whether suddenly applied or slowly rising intended for circuit supplied between phase and neutral or phase and earthed middle conductor;
550:
However, an RCD and an MCB often come integrated in the same device, thus being able to detect both supply imbalance and overload current. Such a device is called an
2440:
761:
inside the unit housing the RCD that remains as set following any form of power outage, but has to be reset manually after the detection of an error condition.
1653:
RCDs used for shock protection must be of the 'immediate' operation type (not time-delayed) and must have a residual current sensitivity of no greater than 30
1416:
a) For a place of public entertainment, protection against earth leakage current must be provided by a residual current device of sensitivity not exceeding 10
3113:
2179:
1038:
protected.) To avoid needless tripping, only one RCD should be installed on any single circuit (excluding corded RCDs, such as bathroom small appliances).
2101:
Earl W. Roberts, Overcurrents and Undercurrents – All about GFCIs: Electrical Safety Advances through Electronics, Mystic Publications, Mystic CT, 1996
386:
2214:
1223:
614:((4) and another, hidden behind (5)) close, allowing current to pass. The solenoid (5) keeps the contacts closed when the reset button is released.
583:
674:
may be high, meaning that a ground fault might not cause sufficient current to trip an ordinary circuit breaker or fuse. In this case a special 100
456:
To reduce the risk of electrocution, RCDs should operate within 25–40 milliseconds with any leakage currents (through a person) of greater than 30
1646:
245:
71:
547:
like a fuse or a miniature circuit breaker (MCB) does (except for the special case of a short circuit from live to ground, not live to neutral).
1476:
mA and all equipment in wet places (water heater, water pump) need to be protected by a residual current device of sensitivity not exceeding 10
962:
Type A RCDs trip on alternating sinusoidal residual current and on residual pulsating direct current, suddenly applied or smoothly increasing.
2347:
1946:
1919:
1892:
543:
A pure RCD will detect imbalance in the currents of the supply and return conductors of a circuit. But it cannot protect against overload or
3171:
2413:
2092:
The Professional Engineer, Official Journal of the Federation of Societies of Professional Engineers of South Africa, pp 67, Vol 6(2) 1977
1617:
frames, public drinking fountains and so on. In principle, ELCBs should be installed on branch circuits, with trip current no more than 30
2402:
327:
is unbalanced between the supply and return conductors of the circuit. Any difference between the currents in these conductors indicates
3010:
1698:
1559:
requires both GFCIs for outlets and Equipment Leakage Circuit Interrupters (ELCI) for the entire boat. The difference is GFCIs trip on 5
135:
3118:
2588:
2433:
1963:"Second Peace Loan Campaign in Vic. - Mounted bugler, caged lion and kangaroo which paraded Melbourne streets during the Loan raising"
1830:"Construction eTool | Electrical Incidents - Ground-fault Circuit Interrupters (GFCI) | Occupational Safety and Health Administration"
1149:
598:
mA. This is an active RCD; that is, it latches electrically and therefore trips on power failure, a useful feature for equipment that
238:
66:
1854:
Accidents from the Electric Current: A Contribution to the Study of the Action of Current: of High Potential Upon the Human Organism.
2738:
2244:
2230:
2026:
1276:
procedure must meet a set standard – this is the AS/NZS 3760:2010 in-service safety inspection and testing of electrical equipment.
1245:
696:
devices offer both electrical fire prevention and shock prevention in one device making them a solution for many rooms in the home.
1866:
2200:
729:
The first three of those situations relate largely to usage as part of a power-distribution system and are almost always of the
666:
Having one RCD feeding another is generally unnecessary, provided they have been wired properly. One exception is the case of a
2901:
2826:
2697:
1556:
912:
are available to allow co-ordinated installations to minimise outage. For example, a power distribution system might have a 300
709:
Major differences exist regarding the manner in which an RCD unit will act to disconnect the power to a circuit or appliance.
1227:
1071:
847:. Preferred values have been defined by the IEC, thus making it possible to divide RCDs into three groups according to their
769:
off, or after any power outage; such arrangements are particularly applicable for connections to refrigerators and freezers.
31:
816:
The following terms are sometimes used to describe the manner in which conductors are connected and disconnected by an RCD:
352:
for any reason, then a single-pole RCD will leave this conductor still connected to the circuit when it detects the fault.
3073:
3005:
2995:
2871:
2771:
2426:
1718:
1185:
1025:
688:
630:
power from the solenoid and cause the contacts to open, causing the safe trip-on-power-failure behaviour mentioned above.
317:
181:
176:
2926:
2886:
2463:
1708:
160:
626:
nonzero sum of currents from among various conductors (for example, three phase conductors and one neutral conductor).
301:
or current flowing to another powered conductor. The device's purpose is to reduce the severity of injury caused by an
3153:
3148:
2866:
2841:
2831:
2807:
2802:
2508:
2414:
Testing of electrical leads and residual current devices (RCDs) (Government of Western Australia Department of Health)
2110:
Edward L. Owen, Power System Grounding Part II: RCD & GFCI, IEEE Industry Applications Magazine, July/August 1996
1472:
mA. Additionally, all power sockets need to be protected by a residual current device of sensitivity not exceeding 30
1155:
Following the accidental electrocution of a woman in a domestic accident at the Stilfontein gold mining village near
2374:
2327:
1497:
753:
of the power supply after any inadvertent form of power outage, as soon as the mains supply becomes re-established;
3202:
3192:
3068:
2786:
2756:
2533:
1048:
120:
1579:
In Norway, it has been required in all new homes since 2002, and on all new sockets since 2006. This applies to 32
3123:
2612:
2573:
1034:
Such a test may be performed on installation of the device and at any "downstream" outlet. (Upstream outlets are
524:
293:
when the current passing through a conductor is not equal and opposite in both directions, therefore indicating
3197:
3098:
2906:
2846:
2503:
1829:
1189:
947:
Type A RCDs, in addition to Type AC, also respond to pulsating or continuous direct current of either polarity.
461:
186:
104:
99:
2083:
Charles F. Dalziel, Transistorized ground-fault interrupter reduces shock hazard, IEEE Spectrum, January 1970
1506:
A and can take either a NEMA 5-15 or a NEMA 5-20 plug, though the latter type is rare on household appliances.
3027:
3017:
1216:
477:
2062:
2958:
2821:
2604:
2493:
1911:
Proceedings of the Annual International Conference of the IEEE Engineering in Medicine and Biology Society
1296:
Additional requirements are placed on circuits in wet areas, construction sites and commercial buildings.
309:
2153:
995:
for residual smooth direct currents whether suddenly applied or slowly increased independent of polarity.
716:
At the consumer power distribution level, usually in conjunction with an RCBO resettable circuit breaker;
445:
The most common modern application is as a safety device to detect small leakage currents (typically 5–30
3093:
2861:
2856:
2836:
1988:
1723:
429:" The GFCI listed device is a requirement in many applications as part of the National Electrical Code (
294:
1013:
A "ring wave" impulse. The standards also require RCDs classified as "selective" to withstand a 3000
725:
Built into the cord of a portable appliance, such as those intended to be used in outdoor or wet areas.
464:, the most common cause of death through electric shock. By contrast, conventional circuit breakers or
1123:
mA. Prior to this, core balance earth leakage protection systems operated at sensitivities of about 10
959:
Type AC RCDs trip on alternating sinusoidal residual current, suddenly applied or smoothly increasing.
2687:
2449:
2119:
Forging ahead: South Africa’s Pioneering Engineers, G R Bozzoli, Witwatersrand University Press, 1997
671:
611:
509:
422:
298:
955:
The BEAMA RCD Handbook - Guide to the Selection and Application of RCDs summarises this as follows:
3058:
2891:
2791:
2766:
2719:
2528:
2518:
2483:
496:, all three live conductors and the neutral (if fitted) must pass through the current transformer.
473:
2362:
2932:
2543:
1976:
1670:
1356:
1347:
According to the NF C 15-100 regulation (1911 -> 2002), a general RCD not exceeding 100 to 300
1108:
532:
290:
211:
140:
130:
17:
2129:
426:
323:
These devices are designed to quickly interrupt the protected circuit when it detects that the
3083:
2963:
2568:
2407:
2343:
2240:
1942:
1936:
1915:
1888:
1882:
1703:
1351:
mA at the origin of the installation is mandatory. Moreover, all circuits must also include 30
1052:
599:
582:
574:
493:
465:
201:
52:
41:
2303:
316:. An earth leakage circuit breaker may be an RCD, although an older type of voltage-operated
3032:
2973:
2677:
2672:
2649:
2558:
2498:
1966:
1713:
1360:
940:) defines three types of RCD depending on the waveforms and frequency of the fault current.
806:
504:
349:
345:
324:
226:
2281:
1571:
ms. The greater values are intended to provide protection while minimizing nuisance trips.
1131:
Patent No. 2268/56 and Australian Patent No. 218360). The prototype magamp was rated at 220
3063:
3022:
3000:
2881:
2851:
2816:
2776:
2578:
2001:
1145:
1056:
667:
652:
472:
RCDs operate by measuring the current balance between two conductors using a differential
328:
191:
80:
2375:"What is an RCD and How Does it Work? - The RCD and the UK Electrical Wiring Regulations"
2050:
1388:. Since June 2007 Germany requires the use of RCDs with a trip current of no more than 30
1539:
ms. A GFCI device which protects equipment (not people) is allowed to trip as high as 30
1367:(electric panels of 1 to 4 DIN rails are the norm for residential). Before 1991, this 30
737:
variety, whereas the fourth relates solely to specific appliances and are always of the
3088:
3078:
2876:
2488:
1750:
1524:
1520:
1273:
449:
mA) and disconnecting quickly enough (<30 milliseconds) to prevent device damage or
336:
302:
150:
145:
992:
for residual pulsating rectified direct current which results from two or more phases;
825:
Double-pole or two-pole – the RCD will disconnect both the energized and return wires.
3186:
3108:
2896:
2781:
2761:
2692:
2682:
2639:
2523:
2478:
1980:
1762:
1690:
1666:
544:
528:
450:
216:
1971:
1962:
1608:
According to the NIBT regulation, the use of RCD type AC is forbidden (since 2010).
3128:
3103:
2968:
2937:
2751:
2553:
2014:
1871:, Scientific Journal of Control Engineering, Dec 2013, Vol. 3, Issue 6, p. 417–422.
1308:
mA residual current device that protects all circuits. Furthermore, at least one 30
1156:
1104:
481:
196:
155:
1909:
1868:
Effects of the Earth Current Frequency and Distortion on Residual Current Devices
1661:
risks considered; this may include the provision of alternative safety measures.
1637:
mA in all new homes since 2004. This rule was introduced in RG-16/06/2004-25494.
2953:
2921:
2714:
2702:
2622:
2548:
2538:
2468:
1205:
802:
798:
35:
2397:
2257:
989:
for residual pulsating direct currents superimposed on a smooth direct current;
691:(AFCI) are important as they offer added protection from potentially hazardous
2916:
2911:
2724:
2707:
2563:
1680:
1172:
618:
485:
125:
30:"GFCI" and "Trip switch" redirect here. For the financial center ranking, see
1583:
A sockets and below. The RCD must trigger after a maximum 0.4 seconds for 230
971:
for residual pulsating direct currents superimposed on smooth direct current.
722:
Plugged into a wall socket, which may be part of a power-extension cable; and
2632:
2627:
2513:
2473:
2130:"What is an RCBO and how does it work? Residual Current Overload Protection"
1684:
1112:
1074:, for example when a ground fault occurs on a circuit protected by a 30 mA I
840:
RCD sensitivity is expressed as the rated residual operating current, noted
692:
638:
RCD with additional overcurrent protection circuitry (RCBO or GFCI breaker)
344:
disconnects the energized conductor. If the fault has left the return wire "
94:
1455:
mA residual current (informally called "salvavita"—life saver, after early
986:
for residual alternating currents superimposed on a smooth direct current;
822:
Single-pole or one-pole – the RCD will disconnect the energized wire only.
712:
There are four situations in which different types of RCD units are used:
335:(0.020 amperes) through the human body is potentially sufficient to cause
2746:
1381:
1364:
603:
520:
331:, which presents a shock hazard. Alternating 60 Hz current above 20
2063:
http://docs-asia.electrocomponents.com/webdocs/01e3/0900766b801e3b4d.pdf
2667:
2657:
2418:
1456:
1451:
The Italian law (n. 46 March 1990) prescribes RCDs with no more than 30
1372:
electrical devices and water or the floor are described and mandatory.
1230: in this section. Unsourced material may be challenged and removed.
89:
2403:
Test of RCCB as per IEC 61008/61009 (Residual Current Device Testing)
1171:
At the time that he worked on the magamp, Rubin also considered using
527:; much like in miniature circuit breakers, the busbar arrangements in
2662:
1809:
Using an RCBO for each circuit can be much more expensive as of 2020.
1766:
1754:
1385:
1304:
Belgian domestic installations are required to be equipped with a 300
938:
General requirements for residual current operated protective devices
332:
221:
1139:
A and had an internally adjustable tripping sensitivity of 12.5–17.5
775:
RCDs for the first and third situation are most commonly rated at 30
642:
476:. This measures the difference between current flowing through the
469:
breaker to isolate the circuit, and not fast enough to save a life.
2074:
BEAMA RCD Handbook - Guide to the Selection and Application of RCDs
976:
Type B RCDs trip in the same conditions as Type F and in addition:
965:
Type F RCDs trip in the same conditions as Type A and in addition:
1496:
1024:
909:
641:
581:
573:
40:
2154:
SAA Wiring Rules AS/NZS 3000:2007, Including Amendments 1 & 2
920:
ms device at the service entry of a building, feeding several 100
655:. In the US, GFCI breakers are more expensive than GFCI outlets.
651:
and Australia. They are effectively a combination of a RCD and a
2617:
1935:
Bill Atkinson; Roger Lovegrove; Gary Gundry (26 November 2012).
1758:
2422:
1413:
According to Regulation 36 of the Electricity Regulations 1990
1531:
GFCIs approved for protection against electric shock trip at 5
1402:
Verband der Elektrotechnik, Elektronik und Informationstechnik
1397:
1199:
1519:
plates. In both Canada and the US older two-wire, ungrounded
2051:
Explanation on voltimum.com.au, by specialist Ian Richardson
1111:. Electrical hazards were of great concern in South African
1086:
are available to provide selectivity in such installations.
556:
residual-current circuit breaker with overcurrent protection
2215:"GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS"
1380:
Since 1 May 1984, RCDs are mandatory for all rooms with a
687:
In addition to ground fault circuit interrupters (GFCIs),
2398:
GFCIs Fact Sheet (US Consumer Product Safety Commission)
2235:
by Ministry of Consumer Affairs’ Energy Safety Service (
430:
2304:"Microsoft Word - ELCI White Paper September 1 2010.DOC"
1629:
Turkey requires the use of RCDs with no more than 30
979:
for residual sinusoidal alternating currents up to 1
594:
A and is designed to trip on a leakage current of 30
312:
integrated in the same device, it is referred to as
289:) is an electrical safety device that interrupts an
3137:
3047:
2984:
2946:
2800:
2737:
2648:
2603:
2596:
2456:
460:mA, before electric shock can drive the heart into
377:Log–log graph of the effect of alternating current
1881:Ken Oldham Smith; John M. Madden (15 April 2008).
862:mA (for direct-contact or life injury protection),
683:RCD with additional arc fault protection circuitry
1621:mA within 0.1 second according to Taiwanese law.
944:Type AC RCDs trip on sinusoidal residual current.
27:Electrical safety device used in household wiring
2328:The Importance of Installing Earth Leakage Units
1180:protection is still in common use in the U.S.A.
1083:
600:could be dangerous on unexpected re-energisation
2364:, Procedure of Electrical Installation Projects
1017:A impulse surge current of specified waveform.
865:medium sensitivity (MS): 100 – 300 – 500 – 1000
1168:mA single phase and three phase magamp units.
45:Typical GFCI receptacle found in North America
2434:
809:at all times and therefore safe on its own).
535:provides protection for anything downstream.
385:passing from left hand to feet as defined in
246:
8:
884:mA sensitivity is typical for GFCI outlets.
1908:Joachim H. Nagel; William M. Smith (1991).
2600:
2441:
2427:
2419:
646:Opened three-phase residual-current device
253:
239:
48:
2410:- Explanation of nuisance tripping causes
1970:
1246:Learn how and when to remove this message
403:2: Current transformer secondary winding
1941:. John Wiley & Sons. pp. 114–.
1887:. John Wiley & Sons. pp. 186–.
1865:Weineng Wang, Zhiqiang Wang, Xiao Peng,
1547:. RCDs with trip currents as high as 500
932:Type (types of leakage current detected)
876:A (typically for protection of machine).
2263:. US Consumer Product Safety Commission
1821:
1735:
1119:V and had a tripping sensitivity of 250
417:Ground-Fault Circuit-Interrupter (GFCI)
401:1: Electromagnet with help electronics
354:
168:
112:
79:
58:
51:
1997:
1986:
1563:mA of current whereas ELCIs trip on 30
1528:appropriate installation description.
1317:mA RCD. These RCDs must be of type A.
606:part as illustrated are now dominant.
81:Regulation of electrical installations
1794:leakage current detection interrupter
1786:appliance leakage current interrupter
924:mA 'S' type at each sub-board, and 30
442:registering their power consumption.
7:
2302:Gropper; Criner (1 September 2010).
2284:. Independent Electrical Contractors
1289:mA and a maximum rated current of 16
1228:adding citations to reliable sources
858:high sensitivity (HS): 5** – 10 – 30
792:Number of poles and pole terminology
705:Differences in disconnection actions
519:In Europe, RCDs can fit on the same
95:IEC 60364 IEC international standard
59:Wiring practice by region or country
2201:"NF C 15-100 evolution (in French)"
1856:Damrell & Upham, 1890, page 13
1699:Domestic AC power plugs and sockets
1543:mA of current; this is known as an
1359:, with each RCD protecting up to 8
136:Mineral-insulated copper-clad cable
105:U.S. National Electrical Code (NEC)
3119:Renewable energy commercialization
2176:"Quando o uso do DR Ă© obrigatĂłrio"
1645:The current (18th) edition of the
1587:V circuits, or 0.2 seconds for 400
1259:RCBO for each individual circuit.
1150:University of California, Berkeley
100:Canadian Electrical Code (CE Code)
25:
2342:. SABS Standards Division. 2009.
1647:IEE Electrical Wiring Regulations
1545:Equipment Protective Device (EPD)
872:low sensitivity (LS): 3 – 10 – 30
578:An example of a rail-mounted RCBO
558:, in Europe and Australia, and a
308:If the RCD device has additional
3167:
3166:
2587:
1770:ground fault circuit interrupter
1683:
1204:
619:differential current transformer
564:ground fault circuit interrupter
394:
370:
357:
283:ground fault circuit interrupter
275:residual-current circuit breaker
169:Switching and protection devices
18:Ground fault circuit interrupter
1972:10.47688/rba_archives_pn-001832
1938:Electrical Installation Designs
1557:American Boat and Yacht Council
1215:needs additional citations for
480:and that returning through the
2232:Residual current devices - ACC
1396:A which are for general use. (
951:etc., equipped with DC motors.
700:Common features and variations
689:arc-fault circuit interrupters
32:Global Financial Centres Index
1:
3114:Renewable Energy Certificates
3074:Cost of electricity by source
2996:Arc-fault circuit interrupter
2872:High-voltage shore connection
1884:Electrical Safety and the Law
1719:Arc-fault circuit interrupter
1523:sockets may be replaced with
1355:mA protections in the user's
1082:RCD either or both may trip.
1078:RCD in series with a 300 mA I
421:The GFCI device is listed to
318:earth leakage circuit breaker
90:BS 7671 UK wiring regulations
3129:Spark/Dark/Quark/Bark spread
2927:Transmission system operator
2887:Mains electricity by country
2464:Automatic generation control
1709:Insulation monitoring device
1392:mA on sockets rated up to 32
1051:). Over-current protection (
1021:Testing of correct operation
586:Internal mechanism of an RCD
161:Thermoplastic-sheathed cable
3154:List of electricity sectors
3149:Electric energy consumption
2867:High-voltage direct current
2842:Electric power transmission
2832:Electric power distribution
2509:Energy return on investment
888:Break time (response speed)
610:button (3) is pressed, the
427:Let-Go Currents and Voltage
3219:
3069:Carbon offsets and credits
2787:Three-phase electric power
1084:Special time-delayed types
1049:three-phase electric power
901:ms at twice rated, and 150
525:miniature circuit breakers
313:
121:AC power plugs and sockets
29:
3162:
3124:Renewable Energy Payments
2613:Fossil fuel power station
2585:
2165:Ă–VE E8001-1/A1:2013-11-01
2015:Jordfelsbrytare (Swedish)
1555:In the United States the
1159:, a few hundred F.W.J. 20
908:Programmable earth fault
869:mA (for fire protection),
719:Built into a wall socket;
566:, in the USA and Canada.
348:" or not at its expected
146:Steel wire armoured cable
2907:Single-wire earth return
2847:Electrical busbar system
2504:Energy demand management
1778:ground fault interrupter
1512:National Electrical Code
1098:History and nomenclature
1005:Surge current resistance
905:ms at five times rated.
897:ms at rated current, 200
749:means prevention of any
617:The sense coil (6) is a
462:ventricular fibrillation
187:Electrical busbar system
53:Electrical installations
3038:Residual-current device
3028:Power system protection
3018:Generator interlock kit
2027:"RCBOs | RS Components"
1196:Regulation and adoption
267:residual-current device
207:Residual-current device
113:Cabling and accessories
72:United Kingdom practice
67:North American practice
2822:Distributed generation
2494:Electric power quality
1996:Cite journal requires
1507:
1363:, usually on the same
1030:
647:
587:
579:
310:overcurrent protection
46:
3094:Fossil fuel phase-out
2862:Electricity retailing
2857:Electrical substation
2837:Electric power system
2377:. Consumer Unit World
1852:Philip Coombs Knapp,
1724:Isolation transformer
1500:
1028:
645:
585:
577:
492:For an RCD used with
437:Purpose and operation
411:N: Neutral conductor
44:
2450:Electricity delivery
2408:Why RCD is tripping?
2156:, SAI Global Limited
1224:improve this article
936:IEC Standard 60755 (
672:earth loop impedance
407:4: Test push-button
405:3: Transformer core
320:(ELCB) also exists.
34:. For the song, see
3059:Availability factor
3011:Sulfur hexafluoride
2892:Overhead power line
2792:Virtual power plant
2767:Induction generator
2720:Sustainable biofuel
2529:Home energy storage
2519:Grid energy storage
2484:Droop speed control
2309:. Paneltronics, Inc
1334:Denmark requires 30
533:distribution boards
474:current transformer
2933:Transmission tower
2544:Nameplate capacity
2282:"2014 NEC Changes"
2258:"GFCIs Fact Sheet"
1567:mA after up to 100
1508:
1357:distribution board
1186:distribution panel
1031:
788:mA are available.
668:TT earthing system
648:
588:
580:
409:L: Line conductor
291:electrical circuit
212:Distribution board
141:Multiway switching
131:Electrical conduit
47:
3203:Electrical safety
3193:Electrical wiring
3180:
3179:
3084:Environmental tax
2964:Cascading failure
2733:
2732:
2569:Utility frequency
2349:978-0-626-23226-9
1948:978-1-118-47776-2
1921:978-0-7803-0216-7
1894:978-0-470-77746-6
1704:Electrical injury
1256:
1255:
1248:
494:three-phase power
482:neutral conductor
263:
262:
222:Electrical switch
16:(Redirected from
3210:
3170:
3169:
3079:Energy subsidies
3033:Protective relay
2974:Rolling blackout
2601:
2591:
2559:Power-flow study
2499:Electrical fault
2443:
2436:
2429:
2420:
2386:
2385:
2383:
2382:
2371:
2365:
2360:
2354:
2353:
2336:
2330:
2325:
2319:
2318:
2316:
2314:
2308:
2299:
2293:
2292:
2290:
2289:
2278:
2272:
2271:
2269:
2268:
2262:
2254:
2248:
2239:, December 2002
2228:
2222:
2221:
2219:
2211:
2205:
2204:
2197:
2191:
2190:
2188:
2187:
2178:. Archived from
2172:
2166:
2163:
2157:
2151:
2145:
2144:
2142:
2140:
2134:www.fusebox.shop
2126:
2120:
2117:
2111:
2108:
2102:
2099:
2093:
2090:
2084:
2081:
2075:
2072:
2066:
2060:
2054:
2048:
2042:
2041:
2039:
2037:
2031:sg.rs-online.com
2023:
2017:
2012:
2006:
2005:
1999:
1994:
1992:
1984:
1974:
1959:
1953:
1952:
1932:
1926:
1925:
1905:
1899:
1898:
1878:
1872:
1863:
1857:
1850:
1844:
1843:
1841:
1840:
1826:
1810:
1807:
1801:
1749:are used in the
1740:
1714:Protective relay
1693:
1688:
1687:
1656:
1636:
1632:
1620:
1590:
1586:
1582:
1570:
1566:
1562:
1550:
1542:
1538:
1534:
1505:
1479:
1475:
1471:
1454:
1442:
1435:
1427:
1419:
1395:
1391:
1370:
1361:circuit breakers
1354:
1350:
1337:
1316:
1311:
1307:
1292:
1288:
1251:
1244:
1240:
1237:
1231:
1208:
1200:
1167:
1162:
1142:
1138:
1134:
1126:
1122:
1118:
1057:circuit breakers
1016:
1012:
982:
927:
923:
919:
915:
904:
900:
896:
883:
875:
868:
861:
807:ground potential
787:
782:
778:
677:
597:
593:
505:Electrical plugs
459:
448:
398:
374:
361:
350:ground potential
325:electric current
255:
248:
241:
227:Earthing systems
192:Circuit breakers
49:
21:
3218:
3217:
3213:
3212:
3211:
3209:
3208:
3207:
3198:Safety switches
3183:
3182:
3181:
3176:
3158:
3142:
3140:
3133:
3064:Capacity factor
3052:
3050:
3043:
3023:Numerical relay
3001:Circuit breaker
2989:
2987:
2980:
2942:
2882:Load management
2852:Electrical grid
2817:Demand response
2810:
2805:
2796:
2777:Microgeneration
2729:
2644:
2592:
2583:
2579:Vehicle-to-grid
2452:
2447:
2394:
2389:
2380:
2378:
2373:
2372:
2368:
2361:
2357:
2350:
2338:
2337:
2333:
2326:
2322:
2312:
2310:
2306:
2301:
2300:
2296:
2287:
2285:
2280:
2279:
2275:
2266:
2264:
2260:
2256:
2255:
2251:
2229:
2225:
2217:
2213:
2212:
2208:
2199:
2198:
2194:
2185:
2183:
2174:
2173:
2169:
2164:
2160:
2152:
2148:
2138:
2136:
2128:
2127:
2123:
2118:
2114:
2109:
2105:
2100:
2096:
2091:
2087:
2082:
2078:
2073:
2069:
2061:
2057:
2049:
2045:
2035:
2033:
2025:
2024:
2020:
2013:
2009:
1995:
1985:
1961:
1960:
1956:
1949:
1934:
1933:
1929:
1922:
1907:
1906:
1902:
1895:
1880:
1879:
1875:
1864:
1860:
1851:
1847:
1838:
1836:
1828:
1827:
1823:
1819:
1814:
1813:
1808:
1804:
1741:
1737:
1732:
1689:
1682:
1679:
1654:
1643:
1634:
1630:
1627:
1618:
1614:
1606:
1597:
1588:
1584:
1580:
1577:
1568:
1564:
1560:
1548:
1540:
1536:
1532:
1503:
1495:
1486:
1477:
1473:
1469:
1466:
1452:
1449:
1440:
1433:
1425:
1417:
1411:
1393:
1389:
1378:
1368:
1352:
1348:
1345:
1335:
1332:
1323:
1314:
1309:
1305:
1302:
1290:
1286:
1282:
1265:
1252:
1241:
1235:
1232:
1221:
1209:
1198:
1190:electrical-code
1165:
1160:
1146:Charles Dalziel
1140:
1136:
1132:
1124:
1120:
1116:
1100:
1081:
1077:
1044:
1023:
1014:
1010:
1007:
980:
934:
925:
921:
917:
913:
902:
898:
894:
890:
881:
873:
866:
859:
852:
845:
838:
794:
785:
780:
776:
707:
702:
685:
675:
640:
595:
591:
572:
541:
502:
457:
446:
439:
412:
410:
408:
406:
404:
402:
399:
390:
375:
366:
362:
329:leakage current
295:leakage current
259:
39:
28:
23:
22:
15:
12:
11:
5:
3216:
3214:
3206:
3205:
3200:
3195:
3185:
3184:
3178:
3177:
3175:
3174:
3163:
3160:
3159:
3157:
3156:
3151:
3145:
3143:
3139:Statistics and
3138:
3135:
3134:
3132:
3131:
3126:
3121:
3116:
3111:
3106:
3101:
3096:
3091:
3089:Feed-in tariff
3086:
3081:
3076:
3071:
3066:
3061:
3055:
3053:
3048:
3045:
3044:
3042:
3041:
3035:
3030:
3025:
3020:
3015:
3014:
3013:
3008:
2998:
2992:
2990:
2985:
2982:
2981:
2979:
2978:
2977:
2976:
2966:
2961:
2956:
2950:
2948:
2944:
2943:
2941:
2940:
2935:
2930:
2924:
2919:
2914:
2909:
2904:
2899:
2894:
2889:
2884:
2879:
2877:Interconnector
2874:
2869:
2864:
2859:
2854:
2849:
2844:
2839:
2834:
2829:
2827:Dynamic demand
2824:
2819:
2813:
2811:
2801:
2798:
2797:
2795:
2794:
2789:
2784:
2779:
2774:
2769:
2764:
2759:
2757:Combined cycle
2754:
2749:
2743:
2741:
2735:
2734:
2731:
2730:
2728:
2727:
2722:
2717:
2712:
2711:
2710:
2705:
2700:
2695:
2690:
2680:
2675:
2670:
2665:
2660:
2654:
2652:
2646:
2645:
2643:
2642:
2637:
2636:
2635:
2630:
2625:
2620:
2609:
2607:
2598:
2594:
2593:
2586:
2584:
2582:
2581:
2576:
2571:
2566:
2561:
2556:
2551:
2546:
2541:
2536:
2534:Load-following
2531:
2526:
2521:
2516:
2511:
2506:
2501:
2496:
2491:
2489:Electric power
2486:
2481:
2476:
2471:
2466:
2460:
2458:
2454:
2453:
2448:
2446:
2445:
2438:
2431:
2423:
2417:
2416:
2411:
2405:
2400:
2393:
2392:External links
2390:
2388:
2387:
2366:
2355:
2348:
2331:
2320:
2294:
2273:
2249:
2223:
2206:
2192:
2167:
2158:
2146:
2121:
2112:
2103:
2094:
2085:
2076:
2067:
2055:
2043:
2018:
2007:
1998:|journal=
1965:. 2021-03-08.
1954:
1947:
1927:
1920:
1900:
1893:
1873:
1858:
1845:
1820:
1818:
1815:
1812:
1811:
1802:
1751:United Kingdom
1734:
1733:
1731:
1728:
1727:
1726:
1721:
1716:
1711:
1706:
1701:
1695:
1694:
1678:
1675:
1642:
1641:United Kingdom
1639:
1626:
1623:
1613:
1610:
1605:
1602:
1596:
1593:
1576:
1573:
1494:
1491:
1485:
1482:
1465:
1462:
1448:
1445:
1410:
1407:
1377:
1374:
1344:
1341:
1331:
1328:
1322:
1319:
1301:
1298:
1281:
1278:
1264:
1261:
1254:
1253:
1212:
1210:
1203:
1197:
1194:
1099:
1096:
1079:
1075:
1043:
1040:
1022:
1019:
1006:
1003:
999:
998:
997:
996:
993:
990:
987:
984:
974:
973:
972:
969:
963:
960:
953:
952:
948:
945:
933:
930:
889:
886:
878:
877:
870:
863:
850:
843:
837:
834:
833:
832:
831:
830:
826:
823:
793:
790:
727:
726:
723:
720:
717:
706:
703:
701:
698:
684:
681:
639:
636:
571:
570:Typical design
568:
540:
537:
529:consumer units
501:
498:
478:live conductor
438:
435:
414:
413:
400:
393:
391:
376:
369:
367:
363:
356:
337:cardiac arrest
303:electric shock
261:
260:
258:
257:
250:
243:
235:
232:
231:
230:
229:
224:
219:
214:
209:
204:
199:
194:
189:
184:
179:
171:
170:
166:
165:
164:
163:
158:
153:
151:Ring main unit
148:
143:
138:
133:
128:
123:
115:
114:
110:
109:
108:
107:
102:
97:
92:
84:
83:
77:
76:
75:
74:
69:
61:
60:
56:
55:
26:
24:
14:
13:
10:
9:
6:
4:
3:
2:
3215:
3204:
3201:
3199:
3196:
3194:
3191:
3190:
3188:
3173:
3165:
3164:
3161:
3155:
3152:
3150:
3147:
3146:
3144:
3136:
3130:
3127:
3125:
3122:
3120:
3117:
3115:
3112:
3110:
3109:Pigouvian tax
3107:
3105:
3102:
3100:
3097:
3095:
3092:
3090:
3087:
3085:
3082:
3080:
3077:
3075:
3072:
3070:
3067:
3065:
3062:
3060:
3057:
3056:
3054:
3046:
3039:
3036:
3034:
3031:
3029:
3026:
3024:
3021:
3019:
3016:
3012:
3009:
3007:
3006:Earth-leakage
3004:
3003:
3002:
2999:
2997:
2994:
2993:
2991:
2983:
2975:
2972:
2971:
2970:
2967:
2965:
2962:
2960:
2957:
2955:
2952:
2951:
2949:
2947:Failure modes
2945:
2939:
2936:
2934:
2931:
2928:
2925:
2923:
2920:
2918:
2915:
2913:
2910:
2908:
2905:
2903:
2900:
2898:
2897:Power station
2895:
2893:
2890:
2888:
2885:
2883:
2880:
2878:
2875:
2873:
2870:
2868:
2865:
2863:
2860:
2858:
2855:
2853:
2850:
2848:
2845:
2843:
2840:
2838:
2835:
2833:
2830:
2828:
2825:
2823:
2820:
2818:
2815:
2814:
2812:
2809:
2804:
2799:
2793:
2790:
2788:
2785:
2783:
2782:Rankine cycle
2780:
2778:
2775:
2773:
2770:
2768:
2765:
2763:
2762:Cooling tower
2760:
2758:
2755:
2753:
2750:
2748:
2745:
2744:
2742:
2740:
2736:
2726:
2723:
2721:
2718:
2716:
2713:
2709:
2706:
2704:
2701:
2699:
2696:
2694:
2691:
2689:
2686:
2685:
2684:
2681:
2679:
2676:
2674:
2671:
2669:
2666:
2664:
2661:
2659:
2656:
2655:
2653:
2651:
2647:
2641:
2638:
2634:
2631:
2629:
2626:
2624:
2621:
2619:
2616:
2615:
2614:
2611:
2610:
2608:
2606:
2605:Non-renewable
2602:
2599:
2595:
2590:
2580:
2577:
2575:
2572:
2570:
2567:
2565:
2562:
2560:
2557:
2555:
2552:
2550:
2547:
2545:
2542:
2540:
2537:
2535:
2532:
2530:
2527:
2525:
2524:Grid strength
2522:
2520:
2517:
2515:
2512:
2510:
2507:
2505:
2502:
2500:
2497:
2495:
2492:
2490:
2487:
2485:
2482:
2480:
2479:Demand factor
2477:
2475:
2472:
2470:
2467:
2465:
2462:
2461:
2459:
2455:
2451:
2444:
2439:
2437:
2432:
2430:
2425:
2424:
2421:
2415:
2412:
2409:
2406:
2404:
2401:
2399:
2396:
2395:
2391:
2376:
2370:
2367:
2363:
2359:
2356:
2351:
2345:
2341:
2335:
2332:
2329:
2324:
2321:
2305:
2298:
2295:
2283:
2277:
2274:
2259:
2253:
2250:
2246:
2245:0-478-26322-8
2242:
2238:
2234:
2233:
2227:
2224:
2216:
2210:
2207:
2202:
2196:
2193:
2182:on 2014-08-08
2181:
2177:
2171:
2168:
2162:
2159:
2155:
2150:
2147:
2135:
2131:
2125:
2122:
2116:
2113:
2107:
2104:
2098:
2095:
2089:
2086:
2080:
2077:
2071:
2068:
2064:
2059:
2056:
2052:
2047:
2044:
2032:
2028:
2022:
2019:
2016:
2011:
2008:
2003:
1990:
1982:
1978:
1973:
1968:
1964:
1958:
1955:
1950:
1944:
1940:
1939:
1931:
1928:
1923:
1917:
1913:
1912:
1904:
1901:
1896:
1890:
1886:
1885:
1877:
1874:
1870:
1869:
1862:
1859:
1855:
1849:
1846:
1835:
1831:
1825:
1822:
1816:
1806:
1803:
1799:
1795:
1791:
1787:
1783:
1779:
1775:
1771:
1768:
1764:
1763:United States
1760:
1756:
1752:
1748:
1744:
1739:
1736:
1729:
1725:
1722:
1720:
1717:
1715:
1712:
1710:
1707:
1705:
1702:
1700:
1697:
1696:
1692:
1691:Energy portal
1686:
1681:
1676:
1674:
1672:
1668:
1667:consumer unit
1662:
1658:
1651:
1648:
1640:
1638:
1624:
1622:
1611:
1609:
1603:
1601:
1594:
1592:
1574:
1572:
1558:
1553:
1546:
1529:
1526:
1522:
1516:
1513:
1499:
1493:North America
1492:
1490:
1483:
1481:
1463:
1461:
1458:
1446:
1444:
1437:
1429:
1421:
1414:
1408:
1406:
1404:
1403:
1399:
1387:
1383:
1375:
1373:
1366:
1362:
1358:
1342:
1340:
1329:
1327:
1320:
1318:
1299:
1297:
1294:
1285:current of 30
1279:
1277:
1275:
1269:
1262:
1260:
1250:
1247:
1239:
1236:February 2012
1229:
1225:
1219:
1218:
1213:This section
1211:
1207:
1202:
1201:
1195:
1193:
1191:
1187:
1181:
1177:
1174:
1169:
1158:
1153:
1151:
1147:
1128:
1114:
1110:
1106:
1097:
1095:
1091:
1087:
1085:
1073:
1070:RCDs are not
1068:
1064:
1060:
1058:
1054:
1050:
1041:
1039:
1037:
1027:
1020:
1018:
1004:
1002:
994:
991:
988:
985:
978:
977:
975:
970:
967:
966:
964:
961:
958:
957:
956:
949:
946:
943:
942:
941:
939:
931:
929:
911:
906:
887:
885:
871:
864:
857:
856:
855:
853:
846:
835:
827:
824:
821:
820:
819:
818:
817:
814:
810:
808:
804:
800:
791:
789:
773:
770:
766:
762:
760:
757:relates to a
756:
752:
751:re-activation
748:
744:
740:
736:
732:
724:
721:
718:
715:
714:
713:
710:
704:
699:
697:
694:
690:
682:
680:
673:
669:
664:
660:
656:
654:
644:
637:
635:
631:
627:
623:
620:
615:
613:
607:
605:
601:
584:
576:
569:
567:
565:
561:
557:
553:
548:
546:
545:short circuit
538:
536:
534:
530:
526:
522:
517:
513:
511:
510:knob and tube
506:
499:
497:
495:
490:
487:
483:
479:
475:
470:
467:
463:
454:
452:
451:electrocution
443:
436:
434:
432:
428:
424:
419:
418:
397:
392:
388:
384:
380:
373:
368:
360:
355:
353:
351:
347:
341:
338:
334:
330:
326:
321:
319:
315:
311:
306:
304:
300:
296:
292:
288:
284:
280:
276:
272:
268:
256:
251:
249:
244:
242:
237:
236:
234:
233:
228:
225:
223:
220:
218:
217:Consumer unit
215:
213:
210:
208:
205:
203:
200:
198:
195:
193:
190:
188:
185:
183:
180:
178:
175:
174:
173:
172:
167:
162:
159:
157:
154:
152:
149:
147:
144:
142:
139:
137:
134:
132:
129:
127:
124:
122:
119:
118:
117:
116:
111:
106:
103:
101:
98:
96:
93:
91:
88:
87:
86:
85:
82:
78:
73:
70:
68:
65:
64:
63:
62:
57:
54:
50:
43:
37:
33:
19:
3104:Net metering
3051:and policies
3037:
2969:Power outage
2938:Utility pole
2902:Pumped hydro
2808:distribution
2803:Transmission
2752:Cogeneration
2554:Power factor
2379:. Retrieved
2369:
2358:
2340:SANS 10142-1
2339:
2334:
2323:
2311:. Retrieved
2297:
2286:. Retrieved
2276:
2265:. Retrieved
2252:
2236:
2231:
2226:
2209:
2195:
2184:. Retrieved
2180:the original
2170:
2161:
2149:
2137:. Retrieved
2133:
2124:
2115:
2106:
2097:
2088:
2079:
2070:
2058:
2046:
2034:. Retrieved
2030:
2021:
2010:
1989:cite journal
1957:
1937:
1930:
1910:
1903:
1883:
1876:
1867:
1861:
1853:
1848:
1837:. Retrieved
1834:www.osha.gov
1833:
1824:
1805:
1797:
1793:
1789:
1785:
1781:
1777:
1773:
1769:
1746:
1742:
1738:
1663:
1659:
1652:
1644:
1628:
1615:
1607:
1598:
1595:South Africa
1591:V circuits.
1578:
1554:
1544:
1535:mA within 25
1530:
1517:
1511:
1509:
1487:
1467:
1450:
1438:
1430:
1422:
1415:
1412:
1400:
1379:
1346:
1333:
1324:
1303:
1295:
1283:
1270:
1266:
1257:
1242:
1233:
1222:Please help
1217:verification
1214:
1182:
1178:
1170:
1157:Johannesburg
1154:
1129:
1105:South Africa
1101:
1092:
1088:
1069:
1065:
1061:
1045:
1035:
1032:
1008:
1000:
954:
937:
935:
907:
891:
879:
848:
841:
839:
815:
811:
795:
774:
771:
767:
763:
758:
754:
750:
746:
743:non-latching
742:
738:
734:
730:
728:
711:
708:
686:
670:, where the
665:
661:
657:
649:
632:
628:
624:
616:
608:
589:
563:
560:GFCI breaker
559:
555:
551:
549:
542:
518:
514:
503:
491:
471:
455:
444:
440:
420:
416:
415:
382:
381:of duration
378:
342:
322:
307:
286:
282:
278:
274:
270:
266:
264:
206:
197:Disconnector
156:Ring circuit
3099:Load factor
2954:Black start
2922:Transformer
2623:Natural gas
2574:Variability
2549:Peak demand
2539:Merit order
2469:Backfeeding
2237:ACC Website
1800:) are used.
1604:Switzerland
1484:New Zealand
1274:RCD testing
1173:transistors
1109:Henri Rubin
1042:Limitations
1029:Test button
836:Sensitivity
803:double-pole
500:Application
365:conductors.
36:Trip Switch
3187:Categories
3141:production
2986:Protective
2917:Super grid
2912:Smart grid
2739:Generation
2673:Geothermal
2564:Repowering
2381:2017-12-23
2288:2016-07-04
2267:2009-06-28
2186:2014-07-23
1839:2019-04-05
1817:References
1633:mA and 300
1113:gold mines
745:variety.
693:arc faults
486:earth wire
126:Cable tray
3049:Economics
2772:Micro CHP
2650:Renewable
2633:Petroleum
2628:Oil shale
2514:Grid code
2474:Base load
2139:2 January
1981:241748775
1761:. In the
1263:Australia
1072:selective
779:mA and 40
3172:Category
2959:Brownout
2747:AC power
2457:Concepts
2313:16 March
1914:. IEEE.
1677:See also
1671:TT earth
1464:Malaysia
1382:bath tub
1365:DIN rail
612:contacts
604:solenoid
521:DIN rail
346:floating
2988:devices
2698:Thermal
2693:Osmotic
2688:Current
2668:Biomass
2658:Biofuel
2640:Nuclear
2597:Sources
2036:15 June
1792:), and
1457:BTicino
1376:Germany
1330:Denmark
1300:Belgium
1280:Austria
1148:of the
916:mA, 300
854:value:
799:single-
735:latched
731:passive
523:as the
431:NFPA 70
389:60479-1
2683:Marine
2663:Biogas
2346:
2243:
1979:
1945:
1918:
1891:
1767:Canada
1755:Europe
1655:
1635:
1631:
1625:Turkey
1619:
1612:Taiwan
1589:
1585:
1581:
1575:Norway
1569:
1565:
1561:
1549:
1541:
1537:
1533:
1525:NEMA 5
1521:NEMA 1
1504:
1478:
1474:
1470:
1453:
1441:
1434:
1426:
1418:
1394:
1390:
1386:shower
1369:
1353:
1349:
1343:France
1336:
1321:Brazil
1315:
1310:
1306:
1291:
1287:
1166:
1161:
1141:
1137:
1133:
1125:
1121:
1117:
1015:
1011:
981:
926:
922:
918:
914:
910:relays
903:
899:
895:
882:
874:
867:
860:
786:
781:
777:
759:switch
747:Active
739:active
676:
596:
592:
562:, for
554:, for
458:
447:
423:UL 943
299:ground
3040:(GFI)
2929:(TSO)
2715:Solar
2703:Tidal
2678:Hydro
2307:(PDF)
2261:(PDF)
2218:(PDF)
1977:S2CID
1730:Notes
1447:Italy
1409:India
1384:or a
1135:V, 60
1053:fuses
880:The 5
755:latch
466:fuses
281:) or
2806:and
2725:Wind
2708:Wave
2618:Coal
2344:ISBN
2315:2015
2241:ISBN
2141:2022
2038:2020
2002:help
1943:ISBN
1916:ISBN
1889:ISBN
1798:LCDI
1790:ALCI
1774:GFCI
1765:and
1759:Asia
1757:and
1747:RCCB
1745:and
1657:mA.
1480:mA.
1443:mA.
1436:mA.
1428:mA.
1420:mA.
983:kHz;
801:and
552:RCBO
539:RCBO
531:and
314:RCBO
287:GFCI
279:RCCB
202:Fuse
182:ELCB
177:AFCI
1967:doi
1784:),
1782:GFI
1776:),
1743:RCD
1398:DIN
1313:100
1293:A.
1226:by
1127:A.
1107:by
1055:or
1036:not
741:or
733:or
653:MCB
387:IEC
297:to
273:),
271:RCD
3189::
2132:.
2029:.
1993::
1991:}}
1987:{{
1975:.
1832:.
1753:,
1502:20
1432:30
1424:10
1164:20
1080:Δn
1076:Δn
851:Δn
844:Δn
333:mA
265:A
2442:e
2435:t
2428:v
2384:.
2352:.
2317:.
2291:.
2270:.
2247:)
2220:.
2203:.
2189:.
2143:.
2053:.
2040:.
2004:)
2000:(
1983:.
1969::
1951:.
1924:.
1897:.
1842:.
1796:(
1788:(
1780:(
1772:(
1249:)
1243:(
1238:)
1234:(
1220:.
849:I
842:I
383:T
379:I
285:(
277:(
269:(
254:e
247:t
240:v
38:.
20:)
Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.