Knowledge

Inverter-based resource

Source 📝

652: 122:
situation. Adding the GFM capability to a GFL device is not expensive in terms of components, but affects the revenues: in order to support the grid stability by providing extra power when needed, the power semiconductors need to be oversized and energy storage added. Modeling demonstrates, however,
247:
700 MW of loss were caused by the poorly designed frequency estimation algorithm. The line faults had distorted the AC waveform and fooled the software into a wrong estimate of the grid frequency dropping below 57 Hz, a threshold where an emergency disconnect shall be initiated. However, the actual
255:
Additional 450 MW were lost when low line voltage caused the inverters to immediately cease to inject current, with gradual return to operative state within 2 minutes. At least one manufacturer had indicated that injecting the current when the voltage level is below 0.9
99:). The GFL inverters are built into an overwhelming majority of installed IBR devices. Due to their following nature, the GFL device will shut down if a large voltage/frequency disturbance is observed. The GFL devices cannot contribute to the 63:) and their features are almost entirely defined by the control algorithms, presenting specific challenges to system stability as their penetration increases, for example, a single software fault can affect all devices of a certain type in a 114:) device partially mimics the behavior of a synchronous generator: its voltage is controlled by a free-running oscillator that slows down when more energy is withdrawn from the device. Unlike a conventional generator, the GFM device has no 611: 169:
The electronic nature of IBRs limits their overload capability: the thermal stress causes their components to even temporarily be able to function at no more than 1-2 times the
232:), but the unexpected features of the algorithms in the photovoltaic inverter software triggered multiple massive losses of power, with the largest one of almost 1,200 629: 620: 240: 80: 220:
on August 16, 2016, has affected multiple high-voltage (500 kV and 287 kV) power transmission lines passing through the canyon. Throughout the day thirteen 500 kV
181:
New challenges to the system stability came with the increased penetration of IBRs. Incidences of disconnections during contingency events where the
95:) device is synchronized to the local grid voltage and injects an electric current vector aligned with the voltage (in other words, behaves like a 689: 598:
The Incidence of Inverter Incidents: Understanding and Quantifying Contributions to Risk in Systems with Large Amounts of Inverter-Based Resources
264:
As a result of the incident, NERC had issued multiple recommendations, involving the changes in inverter design and amendments to the standards.
155:), the delay is shorter if the voltage deviation is larger. Once the inverter is off, it will stay disconnected for a significant time (minutes); 564: 394: 379:
Hybridizing synchronous condensers with grid forming batteries for PV integration – a solution to enhance grid reliability and resiliency
248:
frequency during the event had never dropped below 59.867 Hz, well above the low limit of the normal frequency range (59.5 Hz for the
638: 713: 162:
state: while still connected, it will not inject any power into the grid. This state has a short duration (less than a second).
124: 64: 52: 682: 708: 224:
and two 287 kV faults were recorded. The faults themselves were transitory and self-cleared in a short time (2-3.5
166:
Once an IBR ceases to provide power, it can come back only gradually, ramping its output from zero to full power.
602: 514: 123:
that it is possible to run a power system that almost entirely is based on the GFL devices. A combination of GFM
48: 186: 147:
if the sensed line voltage significantly deviates from the nominal (usually outside the limits of 0.9 to 1.1
249: 675: 173:, while the synchronous machines can briefly tolerate an overload as high as 5-6 times their rated power. 128: 60: 574:
Khan, Akhlaque Ahmad; Minai, Ahmad Faiz (13 January 2023). "Introduction to Grid-Forming Inverters".
201: 533: 182: 170: 221: 560: 541: 390: 225: 104: 56: 581: 575: 525: 382: 257: 148: 32: 28: 659: 96: 702: 197: 190: 119: 100: 613:
1,200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report
554: 229: 115: 553:
Nabil Mohammed; Hassan Haes Alhelou; Behrooz Bahrani, eds. (28 February 2023).
529: 217: 545: 537: 143:
Compliance with IEEE 1547 standard makes the IBR to support safety features:
596: 585: 515:"Power System Stability With a High Penetration of Inverter-Based Resources" 196:
One of the most studied major power contingencies that involved IBRs is the
76: 386: 233: 205: 36: 651: 158:
if the voltage magnitude is unexpected, the inverter shall enter the
27:) is a source of electricity that is asynchronously connected to the 151:), the IBR shall disconnect from the after a delay (so called 381:. Institution of Engineering and Technology. p. 85–108. 75:. The design of inverters for the IBR generally follows the 663: 631:
Application of Advanced Grid-scale Inverters in the NEM
55:. These devices lack the intrinsic behaviors (like the 556:
Grid-Forming Power Inverters: Control and Applications
420: 418: 285: 283: 281: 279: 277: 118:
capacity and thus will react very differently in the
312: 310: 236:at 11:45:16 AM, persisting for multiple minutes. 39:"). The devices in this category, also known as 621:North American Electric Reliability Corporation 241:North American Electric Reliability Corporation 103:, dampen active power oscillations, or provide 683: 8: 208:of photovoltaic power in a very short time. 690: 676: 377:Gevorgian, V.; Shah, S.; Yan, W. (2021). 340: 328: 301: 364: 289: 273: 204:, with a temporary loss of more than a 658:This electricity-related article is a 513:Gu, Yunjie; Green, Timothy C. (2022). 424: 409: 7: 648: 646: 496: 484: 472: 460: 448: 436: 352: 316: 185:was expected, and poor damping of 71:below). IBRs are sometimes called 68: 14: 639:Australian Energy Market Operator 650: 260:would involve a major redesign. 87:Grid-following vs. grid-forming 41:converter interfaced generation 595:Popiel, Caroline Rose (2020). 239:The analysis performed by the 53:battery storage power stations 1: 125:battery storage power station 51:generators (wind, solar) and 662:. You can help Knowledge by 580:. CRC Press. pp. 1–14. 577:Grid-Forming Power Inverters 187:subsynchronous oscillations 730: 645: 530:10.1109/JPROC.2022.3179826 73:non-synchronous generators 603:The University of Vermont 216:The Blue Cut fire in the 49:variable renewable energy 69:section on Blue Cut fire 586:10.1201/9781003302520-1 522:Proceedings of the IEEE 250:Western Interconnection 243:(NERC) had shown that: 135:) is being researched. 21:inverter-based resource 714:Electrical engineering 129:synchronous condensers 387:10.1049/icp.2021.2488 341:Khan & Minai 2023 329:Khan & Minai 2023 302:Khan & Minai 2023 83:PRC-024-2 standards. 61:synchronous generator 16:Source of electricity 628:AEMO (August 2021). 365:Gu & Green 2022 290:Gu & Green 2022 202:Southern California 160:momentary cessation 610:NERC (June 2017). 183:fault ride through 171:nameplate capacity 91:A grid-following ( 31:via an electronic 709:Electricity stubs 671: 670: 566:978-1-00-083929-6 396:978-1-83953-680-9 57:inertial response 721: 692: 685: 678: 654: 647: 642: 636: 624: 618: 606: 589: 570: 549: 519: 500: 494: 488: 482: 476: 470: 464: 458: 452: 446: 440: 434: 428: 422: 413: 407: 401: 400: 374: 368: 362: 356: 350: 344: 338: 332: 326: 320: 314: 305: 299: 293: 287: 153:ridethrough time 110:A grid-forming ( 729: 728: 724: 723: 722: 720: 719: 718: 699: 698: 697: 696: 634: 627: 616: 609: 594: 573: 567: 552: 517: 512: 509: 504: 503: 495: 491: 483: 479: 471: 467: 459: 455: 447: 443: 435: 431: 423: 416: 412:, pp. 4–5. 408: 404: 397: 376: 375: 371: 363: 359: 351: 347: 339: 335: 331:, pp. 1–2. 327: 323: 315: 308: 300: 296: 288: 275: 270: 228:, less than 60 214: 193:were reported. 179: 177:Vulnerabilities 141: 89: 47:), include the 33:power converter 29:electrical grid 17: 12: 11: 5: 727: 725: 717: 716: 711: 701: 700: 695: 694: 687: 680: 672: 669: 668: 655: 644: 643: 625: 607: 592: 591: 590: 565: 550: 508: 505: 502: 501: 489: 477: 465: 453: 441: 429: 414: 402: 395: 369: 357: 345: 333: 321: 306: 294: 272: 271: 269: 266: 262: 261: 253: 213: 210: 178: 175: 164: 163: 156: 140: 137: 97:current source 88: 85: 15: 13: 10: 9: 6: 4: 3: 2: 726: 715: 712: 710: 707: 706: 704: 693: 688: 686: 681: 679: 674: 673: 667: 665: 661: 656: 653: 649: 640: 633: 632: 626: 622: 615: 614: 608: 604: 600: 599: 593: 587: 583: 579: 578: 572: 571: 568: 562: 559:. CRC Press. 558: 557: 551: 547: 543: 539: 535: 531: 527: 523: 516: 511: 510: 506: 498: 493: 490: 486: 481: 478: 474: 469: 466: 462: 457: 454: 450: 445: 442: 439:, p. 16. 438: 433: 430: 426: 421: 419: 415: 411: 406: 403: 398: 392: 388: 384: 380: 373: 370: 366: 361: 358: 355:, p. 15. 354: 349: 346: 342: 337: 334: 330: 325: 322: 319:, p. 10. 318: 313: 311: 307: 303: 298: 295: 291: 286: 284: 282: 280: 278: 274: 267: 265: 259: 254: 251: 246: 245: 244: 242: 237: 235: 231: 227: 223: 219: 212:Blue Cut fire 211: 209: 207: 203: 199: 198:Blue Cut Fire 194: 192: 188: 184: 176: 174: 172: 167: 161: 157: 154: 150: 146: 145: 144: 138: 136: 134: 130: 126: 121: 120:short-circuit 117: 113: 108: 106: 102: 101:grid strength 98: 94: 86: 84: 82: 78: 74: 70: 66: 62: 58: 54: 50: 46: 42: 38: 34: 30: 26: 22: 664:expanding it 657: 630: 612: 597: 576: 555: 521: 499:, p. 9. 492: 487:, p. 8. 480: 475:, p. 5. 468: 463:, p. 2. 456: 451:, p. v. 444: 432: 427:, p. 5. 405: 378: 372: 367:, p. 2. 360: 348: 343:, p. 4. 336: 324: 304:, p. 1. 297: 292:, p. 1. 263: 238: 230:milliseconds 215: 195: 180: 168: 165: 159: 152: 142: 132: 111: 109: 92: 90: 72: 44: 40: 24: 20: 18: 425:Popiel 2020 410:Popiel 2020 222:line faults 200:of 2016 in 116:overcurrent 65:contingency 703:Categories 268:References 218:Cajon Pass 191:weak grids 133:SuperFACTS 546:0018-9219 538:1558-2256 497:NERC 2017 485:NERC 2017 473:NERC 2017 461:NERC 2017 449:NERC 2017 437:AEMO 2021 353:AEMO 2021 317:NERC 2017 234:megawatts 77:IEEE 1547 524:: 1–22. 206:gigawatt 139:Features 37:inverter 601:(MSc). 507:Sources 105:inertia 563:  544:  536:  393:  226:cycles 635:(PDF) 617:(PDF) 534:eISSN 518:(PDF) 67:(cf. 59:of a 660:stub 561:ISBN 542:ISSN 391:ISBN 127:and 81:NERC 79:and 582:doi 526:doi 383:doi 189:in 112:GFM 93:GFL 45:CIG 25:IBR 19:An 705:: 637:. 619:. 540:. 532:. 520:. 417:^ 389:. 309:^ 276:^ 258:pu 252:). 149:pu 107:. 35:(" 691:e 684:t 677:v 666:. 641:. 623:. 605:. 588:. 584:: 569:. 548:. 528:: 399:. 385:: 131:( 43:( 23:(

Index

electrical grid
power converter
inverter
variable renewable energy
battery storage power stations
inertial response
synchronous generator
contingency
section on Blue Cut fire
IEEE 1547
NERC
current source
grid strength
inertia
overcurrent
short-circuit
battery storage power station
synchronous condensers
pu
nameplate capacity
fault ride through
subsynchronous oscillations
weak grids
Blue Cut Fire
Southern California
gigawatt
Cajon Pass
line faults
cycles
milliseconds

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.