Knowledge (XXG)

Low-voltage network

Source 📝

116: 17: 209: 200: 260: 388:
the unaffected cables take over its load and continue to provide service. Primary feeder outages, as well as limiters and network protectors cleared because of previous faults, cause changes in load flow that are not readily detected, so their statuses may require a periodic inspection. The inherent system redundancy generally prevents any customer from experiencing outage.
371: 315: 288: 387:
on both ends, special fuses providing very fast short-circuit protection. Cable limiters do not have an ampere rating, and cannot be used to provide overload protection; their sole purpose is to isolate the fault. Under high short-circuit conditions, limiters blow and cut off the faulted cable, while
378:
A grid networks consist of an interconnected grid of circuits, energized from several primary feeders through distribution transformers at multiple locations. Grid networks are typically featured in downtowns of large cities, with connecting cables laid out in underground conduits along the streets.
284:, or their mixture; in an overhead network, service drops are drawn from pole tops to roof connections. In a cable network, all necessary connections and protection devices are typically placed in pad-mounted cabinets or, occasionally, manholes (buried T-joint connections are prone to failures). 328:
Spot networks are used when increased reliability of supply is required for important customers. The low-voltage network is supplied from two or more distribution transformers at a single site, each fed from a different MV feeder (which may originate from the same or different substations). The
352:
Spot systems are commonly applied in high load-density areas such as business districts, large hospitals, small industry and important facilities such as water supply systems. In normal operation, the energy supply is provided by both primary feeders in parallel. In case of an outage of either
267:
Radial operation is the most widespread and most economic design of both MV and LV networks. It provides a sufficiently high degree of reliability and service continuity for most customers. In American (120 V) systems, the customers are commonly supplied directly from the distribution
225:
ANSI standard C84.1 recommends a +5%, −2.5% tolerance for the voltage range at a service point. North American LV networks feature much shorter secondary connections, up to 250 feet (80 m), while in European design they can reach up to 1 mile (1,600 m). North American distribution
150:
level, typically 5–35 kV. Feeders range in length from a few kilometers to several tens of kilometers. As they must supply all customers in the designated distribution area, they often curve and branch along the assigned corridors. A substation typically supplies 3–30 feeders.
226:
transformers must be therefore placed much closer to consumers, and are smaller (25–50 kVA), while European ones can cover larger areas and thus have higher ratings (300–1000 kVA); only the remote rural areas in European design are served by single-phase transformers.
169:). Typically, a rural primary feeder supplies up to 50 distribution transformers, spread over a wide region, but the figure significantly varies depending on configuration. They are sited on pole tops, cellars or designated small plots. From these transformers, 361:
is located at the paralleling bus, or a total loss of primary supply occurs, the customer will remain out of service. Faults on the low-voltage network are handled by fuses or local circuit breakers, resulting in loss of service only for the affected loads.
133:
systems are designed to serve their customers with reliable and high-quality power. The most common distribution system consists of simple radial circuits (feeders) that can be overhead, underground, or a combination. From the
382:
As with spot networks, network protectors are used to protect against primary feeder faults, and prevent fault current to propagate from the grid to the primary feeder. Individual cable sections may be protected by
229:
As the low-voltage distribute the electric power to the widest class of end users, another main design concern is safety of consumers who use the electric appliances and their protection against electric shocks. An
357:
device at the corresponding spot transformer secondary automatically opens; the remaining transformers continue to provide supply through their respective primary feeders. Only in cases when the
242:, must ultimately ensure that a person must not come into touch with a metallic object whose potential relative to the person's potential (which is, in turn, equal to the ground potential unless 349:. In some cases, fast-acting secondary bus tie breakers may be applied between bus sections to isolate faults in the secondary switchgear and limit loss of service. 83:
lines from the transformer to the customer premises. Low-voltage radial feeders supply multiple customers. For increased reliability, so-called
724: 703: 661: 609: 298:
in radial networks is simple to design and implement, since short-circuit currents have only one possible path that needs to be interrupted.
743: 20:
A pole-mounted three-phase distribution transformer. Low-voltage feeders distributing power to households are placed below the transformer
682: 222:
rating. In Europe and most of the world 220–240 V is the dominant choice, while in North America 120 V is the standard.
291:
Low-voltage side switching cabinet of a European MV/LV substation. Four LV cable feeders equipped with circuit breakers featured.
272:
lines, in star-like topology. In 240 V systems, the customers are served by several low-voltage feeders, realized by
115: 68: 621:"Secondary Network Distribution Systems Background and Issues Related to the Interconnection of Distributed Resources" 130: 33: 582: 402: 154: 37: 323: 295: 239: 135: 79:) and required reliability dictate topology and configuration of the network. The simplest form are radial 16: 634:
Confidence Interval Estimation for Distribution Systems Power Consumption by using the Bootstrap Method
379:
Numerous cables allow for multiple current paths from every transformer to every load within the grid.
277: 100: 243: 147: 273: 96: 56: 208: 199: 720: 699: 678: 657: 651: 605: 354: 299: 235: 178: 41: 672: 599: 638: 397: 303: 231: 124: 92: 302:
are most commonly used for both short-circuit and overload protection, while low-voltage
218:
Most of differences in the layout and design of low-voltage networks are dictated by the
91:
provide supply of customers from multiple distribution transformers and supply paths.
737: 384: 358: 219: 177:
network branches off to the customer connections at customer premises, equipped with
166: 49: 329:
transformers are connected together with a bus or a cable on secondary side, termed
269: 80: 76: 714: 693: 192:
Typical layouts of European (left) and North American (right) distribution system
281: 162: 120: 104: 72: 45: 637:(Doctoral dissertation). Virginia Polytechnic Institute and State University. 620: 259: 619:
Behnke, Michael; Soudi, Farajollah; Feero, William; Dawson, Douglas (2005).
370: 314: 246:
are used) exceeds a "safe" threshold, typically set at about 50 V.
642: 287: 632: 583:"ANSI C84.1 Electric Power Systems And Equipment - Voltage Ranges" 369: 313: 286: 258: 114: 64: 60: 15: 341:) to other network units, in which case such networks are termed 337:. The paralleling bus typically does not have connecting cables ( 161:, placed along feeders, convert the voltage from the medium to a 653:
Design Fundamentals for Low-Voltage Distribution and Control
138:, feeders carry the power to the end customers, forming the 119:
A house cable connection cabinet equipped with a meter, a
601:
Electric Power Distribution Systems: A Nontechnical Guide
165:
level, suitable for direct consumption by end customers (
631:
Cugnet, Pierre (1997). "2. Power Distribution Systems".
44:
of end customers. Secondary networks are operated at a
514: 512: 510: 473: 471: 446: 444: 431: 429: 695:Electric Power Distribution Equipment and Systems 234:, in combination with protective devices such as 71:). Operating voltage, required number of phases ( 55:Most modern secondary networks are operated at 674:Electrical Raceways & Other Wiring Methods 263:Typical layouts of radial low-voltage networks 8: 716:Newnes Electrical Power Engineer's Handbook 345:; when they have, they are referred to as 59:rated voltage of 100–127 or 220–240  626:. National Renewable Energy Laboratory. 413: 48:level, which is typically equal to the 306:may be used in special circumstances. 554: 477: 462: 450: 420: 7: 566: 542: 530: 518: 501: 489: 435: 374:Layout of a grid low-voltage network 318:Layout of a spot low-voltage network 63:, at the frequency of 50 or 60  36:which carries electric energy from 268:transformers via relatively short 14: 650:Kussy, Frank (8 December 1986). 604:. PennWell Books. pp. 82–. 207: 198: 1: 692:Short, Thomas Allen (2005). 69:mains electricity by country 744:Electric power distribution 713:Warne, D.F. (2 June 2005). 131:Electric power distribution 34:electric power distribution 760: 403:Split-phase electric power 321: 671:Loyd, Richard E. (2004). 155:Distribution transformers 38:distribution transformers 598:Beaty, H. Wayne (1998). 347:spot networks with reach 240:residual current devices 52:of electric appliances. 343:isolating spot networks 324:Spot network substation 296:Power-system protection 146:network, operated at a 136:distribution substation 375: 319: 292: 264: 159:secondary transformers 127: 21: 373: 317: 290: 262: 185:Design considerations 118: 19: 677:. Cengage Learning. 274:overhead power lines 107:, or their mixture. 97:overhead power lines 95:can be realized by 26:low-voltage network 376: 320: 293: 265: 179:electricity meters 128: 42:electricity meters 22: 726:978-0-08-047969-9 705:978-1-4200-3647-3 663:978-0-8247-7515-5 611:978-0-87814-731-1 355:network protector 30:secondary network 751: 730: 709: 688: 667: 646: 627: 625: 615: 594: 592: 590: 570: 564: 558: 552: 546: 540: 534: 528: 522: 516: 505: 499: 493: 487: 481: 475: 466: 460: 454: 448: 439: 433: 424: 418: 353:primary feeder, 304:circuit breakers 211: 202: 759: 758: 754: 753: 752: 750: 749: 748: 734: 733: 727: 712: 706: 691: 685: 670: 664: 649: 630: 623: 618: 612: 597: 588: 586: 581: 578: 573: 565: 561: 553: 549: 541: 537: 529: 525: 521:, pp. 6–8. 517: 508: 500: 496: 488: 484: 476: 469: 461: 457: 449: 442: 434: 427: 419: 415: 411: 398:Earthing system 394: 368: 331:paralleling bus 326: 312: 280:or underground 257: 255:Radial networks 252: 244:insulating mats 232:earthing system 216: 215: 214: 213: 212: 204: 203: 194: 193: 187: 125:circuit breaker 113: 103:or underground 93:Electric wiring 12: 11: 5: 757: 755: 747: 746: 736: 735: 732: 731: 725: 710: 704: 689: 683: 668: 662: 647: 628: 616: 610: 595: 577: 574: 572: 571: 559: 557:, p. 298. 547: 535: 523: 506: 494: 482: 467: 465:, p. 387. 455: 440: 425: 423:, p. 385. 412: 410: 407: 406: 405: 400: 393: 390: 385:cable limiters 367: 364: 322:Main article: 311: 308: 256: 253: 251: 248: 206: 205: 197: 196: 195: 191: 190: 189: 188: 186: 183: 148:medium voltage 140:medium-voltage 112: 109: 13: 10: 9: 6: 4: 3: 2: 756: 745: 742: 741: 739: 728: 722: 718: 717: 711: 707: 701: 698:. CRC Press. 697: 696: 690: 686: 684:1-4018-5183-5 680: 676: 675: 669: 665: 659: 656:. CRC Press. 655: 654: 648: 644: 640: 636: 635: 629: 622: 617: 613: 607: 603: 602: 596: 584: 580: 579: 575: 569:, p. 10. 568: 563: 560: 556: 551: 548: 544: 539: 536: 532: 527: 524: 520: 515: 513: 511: 507: 504:, p. 18. 503: 498: 495: 491: 486: 483: 480:, p. 23. 479: 474: 472: 468: 464: 459: 456: 453:, p. 84. 452: 447: 445: 441: 437: 432: 430: 426: 422: 417: 414: 408: 404: 401: 399: 396: 395: 391: 389: 386: 380: 372: 366:Grid networks 365: 363: 360: 359:short circuit 356: 350: 348: 344: 340: 336: 335:collector bus 332: 325: 316: 310:Spot networks 309: 307: 305: 301: 297: 289: 285: 283: 279: 275: 271: 261: 254: 249: 247: 245: 241: 237: 233: 227: 223: 221: 220:mains voltage 210: 201: 184: 182: 180: 176: 172: 168: 167:mains voltage 164: 160: 156: 152: 149: 145: 141: 137: 132: 126: 122: 117: 110: 108: 106: 102: 98: 94: 90: 89:grid networks 86: 85:spot networks 82: 78: 74: 70: 66: 62: 58: 53: 51: 50:mains voltage 47: 43: 39: 35: 32:is a part of 31: 27: 18: 719:. Elsevier. 715: 694: 673: 652: 633: 600: 589:21 September 587:. Retrieved 562: 550: 545:, p. 7. 538: 533:, p. 9. 526: 497: 485: 458: 438:, p. 1. 416: 381: 377: 351: 346: 342: 338: 334: 330: 327: 294: 282:power cables 270:service drop 266: 228: 224: 217: 174: 170: 158: 153: 143: 139: 129: 105:power cables 88: 84: 81:service drop 77:single-phase 54: 29: 25: 23: 643:10919/36841 171:low-voltage 163:low voltage 121:time switch 73:three-phase 46:low voltage 576:References 555:Kussy 1986 478:Warne 2005 463:Warne 2005 451:Beaty 1998 421:Warne 2005 567:NREL 2005 543:NREL 2005 531:NREL 2005 519:NREL 2005 502:Loyd 2004 490:ANSI 2011 436:NREL 2005 409:Footnotes 175:secondary 738:Category 392:See also 250:Topology 111:Overview 339:reaches 144:primary 723:  702:  681:  660:  608:  585:. 2011 278:aerial 123:and a 101:aerial 624:(PDF) 300:Fuses 236:fuses 67:(see 65:hertz 61:volts 721:ISBN 700:ISBN 679:ISBN 658:ISBN 606:ISBN 591:2017 238:and 87:and 639:hdl 333:or 173:or 157:or 142:or 75:or 40:to 28:or 740:: 509:^ 470:^ 443:^ 428:^ 276:, 181:. 99:, 57:AC 24:A 729:. 708:. 687:. 666:. 645:. 641:: 614:. 593:. 492:.

Index


electric power distribution
distribution transformers
electricity meters
low voltage
mains voltage
AC
volts
hertz
mains electricity by country
three-phase
single-phase
service drop
Electric wiring
overhead power lines
aerial
power cables

time switch
circuit breaker
Electric power distribution
distribution substation
medium voltage
Distribution transformers
low voltage
mains voltage
electricity meters


mains voltage

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.