Knowledge (XXG)

Damper (flow)

Source 📝

300:-return mechanism and a shaded-pole synchronous motor. In this case, the damper is normally opened by the force of the spring but can be closed by the force of the motor. Removal of electrical power re-opens the damper. This style of damper is advantageous because it is "fail safe"; if the control to the damper fails, the damper opens and allows air to flow. However, in most applications "fail safe" indicates the damper will close upon loss of power thus preventing the spread of smoke and fire to other areas. These dampers also may allow adjustment of the "closed" position so that they only obstruct, for example, 75% of the air flow when closed. 43: 243: 235: 1909: 140: 210:, a damper closes off the flue to keep the weather and animals (e.g. birds) out and warm or cool air in. This is usually done in the summer, but also may be done in the winter between uses. In some cases, the damper may also be partly closed to help control the rate of combustion. The damper may be accessible only by reaching up into the 303:
For vacuum-operated or pneumatically operated zone dampers, the thermostat usually switches the pressure or vacuum on or off, causing a spring-loaded rubber diaphragm to move and actuate the damper. As with the second style of electrical zone dampers, these dampers automatically return to the default
292:
power source that is used for the rest of the control system. This allows the zone dampers to be directly controlled by low-voltage thermostats and wired with low-voltage wiring. Because simultaneous closure of all dampers might harm the furnace or air handler, this style of damper is often designed
262:
heating or cooling system. In order to improve efficiency and occupant comfort, HVAC systems are commonly divided up into multiple zones. For example, in a house, the main floor may be served by one heating zone while the upstairs bedrooms are served by another. In this way, the heat can be directed
284:
combined with a rotary switch that can disconnect the motor at either of the two stopping points ("damper open" or "damper closed"). In this way, applying power to the "open damper" terminal causes the motor to run until the damper is open while applying power at the "close damper" terminal causes
419:
Fire dampers are fitted where ductwork passes through fire compartment walls and fire curtains as part of a fire control strategy. In normal circumstances, these dampers are held open by means of fusible links. When subjected to heat, these links fracture and allow the damper to close under the
386:
Zone dampers are not 100% reliable. Most styles of motor-to-open/motor-to-closed electrically operated zone dampers aren't "fail safe" (that is, they do not fail to the open condition). However, zone dampers that are of the "Normally Open" type are fail-safe, in that they will fail to the open
420:
influence of the integral closing spring. The links are attached to the damper such that the dampers can be released manually for testing purposes. The damper is provided with an access door in the adjacent ductworks for the purpose of inspection and resetting in the event of closure.
323:
Regardless of the style of damper employed, the systems are often designed so that when no thermostat is calling for air, all dampers in the system are opened. This allows air to continue to flow while the heat exchanger in a furnace cools down after a heating period completes.
410:
actuation is preferred for these dampers. It is easier to provide zone-classified solenoid valves for pneumatic actuation, as compared to electrical actuation. The physical size of such solenoid valves have come down very considerably over the years.
319:
to control the zone dampers. The dampers may also support positions other than fully open or fully closed and are usually capable of reporting their current position and, often, the temperature and volume of the air flowing past the smart damper.
183:- for example, in the case of Volume Control Dampers. Its operation can be manual or automatic. Manual dampers are turned by a handle on the outside of a duct. Automatic dampers are used to regulate airflow constantly and are operated by 304:
position without the application of any power, and the default position is usually "open", allowing air to flow. Like the second style of electrical zone damper, these dampers may allow adjustment of the "closed" position.
1805: 203:, and the degree of air-flow calibrated, perhaps according to signals from the thermostat going to the actuator of the damper in order to modulate the flow of air-conditioned air in order to effect climate control. 332:
Multiple zones can be implemented using either multiple, individually controlled furnaces/air handlers or a single furnace/air handler and multiple zone dampers. Each approach has advantages and disadvantages.
246:
Close-up of the motor connections. This damper can switch the electrical power to control additional "slave" dampers, minimizing the electrical load on the damper's control circuitry and power transformer
359:
Power consumption. Operating furnaces draw power whereas a zone damper only draws power while in motion from one state to the other (or, in some cases, a very small amount of power while holding closed)
1755: 1785: 1928: 1800: 390:
No inherent redundancy for the furnace. A system with zone dampers is dependent upon a single furnace. If it fails, the system becomes completely inoperable.
1293: 542: 1795: 1727: 1600: 218:
or similar device, it is usually a handle on the vent duct as in an air conditioning system. Forgetting to open a damper before beginning a
1760: 1722: 1583: 1625: 1338: 874: 603: 126: 263:
principally to the main floor during the day and principally to the bedrooms at night, allowing the unoccupied areas to cool down.
694: 1933: 1775: 1589: 969: 533: 64: 60: 1737: 1681: 1676: 1253: 781: 440: 281: 107: 1298: 849: 770: 729: 79: 1641: 1443: 954: 889: 807: 719: 583: 403:) and the ability of the system to withstand the fault condition whereby all zone dampers are closed simultaneously. 1790: 1671: 1378: 1143: 987: 86: 53: 1843: 1702: 1666: 1468: 1098: 1053: 981: 833: 776: 1890: 1712: 1408: 1008: 787: 678: 663: 266:
Zone dampers as used in home HVAC systems are usually electrically powered. In large commercial installations,
274:
may be used instead. In either case, the motor is usually connected to the damper via a mechanical coupling.
93: 1885: 1810: 1732: 1661: 1605: 1537: 1433: 1348: 1258: 1223: 699: 31: 1913: 1875: 1837: 1717: 1428: 859: 1895: 1573: 1532: 1248: 919: 739: 75: 1697: 1687: 1631: 1568: 1463: 1043: 992: 558: 238:
An opposed-blade, motor-closed, motor-opened zone damper. The damper is shown in the "open" position.
383:
New US residential building codes require permanent access to dampers through ceiling access panels.
1563: 1553: 1527: 1313: 975: 884: 854: 754: 724: 618: 578: 434: 308: 289: 196: 164: 1826: 1770: 1707: 1484: 1363: 1358: 1148: 959: 944: 526: 215: 1398: 1353: 1108: 1103: 1033: 929: 765: 568: 445: 511: 1865: 1620: 1615: 1198: 904: 802: 797: 792: 709: 285:
the motor to run until the damper is closed. The motor is commonly powered from the same 24
172: 214:
by hand or with a woodpoker, or sometimes by a lever or knob that sticks down or out. On a
1860: 1832: 1474: 1388: 1383: 1328: 1318: 1308: 1238: 1178: 1093: 1078: 899: 894: 869: 864: 734: 658: 297: 188: 180: 396:
Supply and return ducts need dampers to avoid pressurization of portions of the building.
100: 1610: 1507: 1283: 1263: 1228: 1163: 1083: 924: 914: 823: 673: 643: 598: 593: 271: 184: 490: 1922: 1692: 1543: 1438: 1403: 1173: 1168: 1118: 964: 939: 934: 909: 879: 749: 648: 628: 608: 519: 1870: 1548: 1448: 1423: 1418: 1413: 1343: 1278: 1158: 1128: 1068: 1063: 1038: 949: 828: 744: 668: 653: 638: 1880: 1522: 1479: 1453: 1393: 1373: 1368: 1243: 1203: 1188: 1133: 1058: 1028: 1023: 839: 704: 623: 176: 168: 156: 42: 393:
Low total flow when only some dampers are open can cause inefficient operation.
1636: 1558: 1489: 1458: 1333: 1303: 1233: 1183: 1153: 1138: 1113: 1018: 818: 714: 633: 573: 429: 407: 192: 1595: 1273: 1268: 1218: 1193: 1048: 844: 465: 399:
The system can be harder to a design, requiring both "SPDT" thermostats (or
211: 242: 234: 175:(heating or cooling) to an unused room, or to regulate it for room-by-room 171:, or other air-handling equipment. A damper may be used to cut off central 17: 1908: 1578: 1512: 1013: 813: 613: 588: 563: 316: 200: 27:
Valve or plate for regulating airflow inside a duct, chimney, vent, etc.
1088: 760: 160: 152: 139: 1765: 1517: 1323: 1073: 312: 267: 258:) is a specific type of damper used to control the flow of air in an 30:
This article is about the architectural element. For other uses, see
348:
Redundancy: If one zone furnace fails, the others can remain working
199:
system. Automatic or motorized dampers may also be controlled by a
1780: 1213: 400: 223: 138: 1288: 1208: 286: 259: 219: 207: 515: 293:
to only obstruct a portion of the air duct, for example, 75%.
277:
For electrical zone dampers, there are two principal designs.
36: 345:
Simple mechanical and control design ("SPST thermostats")
226:
damage to the interior of a home, if not a house fire.
296:
Another style of electrically powered damper uses a
1853: 1819: 1746: 1650: 1498: 1001: 687: 549: 67:. Unsourced material may be challenged and removed. 307:Highly sophisticated systems may use some form of 151:is a valve or plate that stops or regulates the 356:Cost. Furnaces cost much more than zone dampers 527: 8: 328:Comparison to multiple furnaces/air handlers 1929:Heating, ventilation, and air conditioning 1294:High efficiency glandless circulating pump 543:Heating, ventilation, and air conditioning 534: 520: 512: 280:In one design, the motor is often a small 127:Learn how and when to remove this message 1728:Mold growth, assessment, and remediation 241: 233: 457: 143:Opposed blade dampers in a mixing duct. 1601:Programmable communicating thermostat 7: 1723:Mechanical, electrical, and plumbing 65:adding citations to reliable sources 1584:Minimum efficiency reporting value 25: 1626:Standard temperature and pressure 1339:Packaged terminal air conditioner 875:Passive daytime radiative cooling 604:Heat pump and refrigeration cycle 1907: 695:Absorption-compression heat pump 191:motors, in turn controlled by a 41: 1590:Normal temperature and pressure 970:Vapor-compression refrigeration 250:A zone damper (also known as a 52:needs additional citations for 337:Multiple furnaces/air handlers 1: 1738:Testing, adjusting, balancing 1682:Building information modeling 1677:Building services engineering 1254:Ground-coupled heat exchanger 782:Demand controlled ventilation 730:Building insulation materials 441:Testing, adjusting, balancing 282:shaded-pole synchronous motor 1299:High-pressure cut-off switch 850:Ice storage air conditioning 771:Dedicated outdoor air system 1642:Thermostatic radiator valve 1444:Thermostatic radiator valve 955:Underfloor air distribution 890:Radiant heating and cooling 808:Energy recovery ventilation 720:Automobile air conditioning 584:Domestic energy consumption 466:"Louvres and Dampers - HVC" 1950: 1791:Institute of Refrigeration 1672:Architectural technologist 1144:Electrostatic precipitator 489:Matot, Cece (2019-10-17). 29: 1844:Volatile organic compound 1703:Environmental engineering 1667:Architectural engineering 1469:Ultra-low particulate air 1054:Automatic balancing valve 982:Variable refrigerant flow 834:Heat recovery ventilation 777:Deep water source cooling 1891:Template:Home automation 1713:Kitchen exhaust cleaning 1409:Solar-assisted heat pump 1009:Air conditioner inverter 788:Displacement ventilation 679:Vapour pressure of water 664:Thermal destratification 1886:World Refrigeration Day 1733:Refrigerant reclamation 1662:Architectural acoustics 1606:Programmable thermostat 1538:Clean air delivery rate 1434:Thermal expansion valve 1349:Pressurisation ductwork 1259:Ground source heat pump 700:Absorption refrigerator 32:Damper (disambiguation) 1934:Mechanical engineering 1876:Glossary of HVAC terms 1838:Sick building syndrome 1718:Mechanical engineering 1429:Smoke exhaust ductwork 860:Mixed-mode ventilation 247: 239: 230:Automated zone dampers 144: 1916:at Wikimedia Commons 1896:Template:Solar energy 1574:Intelligent buildings 1533:Carbon dioxide sensor 920:Room air distribution 740:Central solar heating 252:Volume Control Damper 245: 237: 142: 1698:Duct leakage testing 1688:Deep energy retrofit 1632:Thermographic camera 1569:Infrared thermometer 1044:Air source heat pump 993:Water heat recycling 559:Air changes per hour 61:improve this article 1564:HVAC control system 1554:Home energy monitor 1528:Building automation 1314:Inverter compressor 976:Variable air volume 885:Passive ventilation 855:Kitchen ventilation 755:Constant air volume 725:Autonomous building 491:"What are Dampers?" 435:Variable air volume 309:building automation 197:building automation 1827:Indoor air quality 1771:ASTM International 1708:Hydronic balancing 1485:Wood-burning stove 1364:Radiator reflector 1149:Evaporative cooler 960:Underfloor heating 945:Thermal insulation 375:Power consumption. 248: 240: 222:can cause serious 216:wood-burning stove 145: 76:"Damper" flow 1912:Media related to 1904: 1903: 1820:Health and safety 1399:Scroll compressor 1354:Process duct work 1109:Convection heater 1104:Condensing boiler 1034:Air-mixing plenum 930:Solar combisystem 766:Cross ventilation 569:Building envelope 446:Air-mixing plenum 137: 136: 129: 111: 16:(Redirected from 1941: 1911: 1866:Building science 1621:Smart thermostat 1616:Room temperature 1199:Fireplace insert 905:Radon mitigation 803:Electric heating 798:District heating 793:District cooling 710:Air conditioning 536: 529: 522: 513: 501: 500: 498: 497: 486: 480: 479: 477: 476: 462: 173:air conditioning 132: 125: 121: 118: 112: 110: 69: 45: 37: 21: 1949: 1948: 1944: 1943: 1942: 1940: 1939: 1938: 1919: 1918: 1905: 1900: 1861:ASHRAE Handbook 1849: 1833:Passive smoking 1815: 1748: 1742: 1654: 1652: 1646: 1500: 1494: 1475:Whole-house fan 1389:Run-around coil 1384:Reversing valve 1329:Mechanical room 1319:Kerosene heater 1309:Infrared heater 1239:Gasoline heater 1179:Fan filter unit 1094:Condensate pump 1079:Centrifugal fan 997: 900:Radiant heating 895:Radiant cooling 870:Passive cooling 865:Microgeneration 735:Central heating 683: 659:Thermal comfort 551: 545: 540: 510: 505: 504: 495: 493: 488: 487: 483: 474: 472: 464: 463: 459: 454: 426: 417: 379:Disadvantages: 366: 352:Disadvantages: 339: 330: 232: 181:climate control 133: 122: 116: 113: 70: 68: 58: 46: 35: 28: 23: 22: 15: 12: 11: 5: 1947: 1945: 1937: 1936: 1931: 1921: 1920: 1902: 1901: 1899: 1898: 1893: 1888: 1883: 1878: 1873: 1868: 1863: 1857: 1855: 1851: 1850: 1848: 1847: 1841: 1835: 1830: 1823: 1821: 1817: 1816: 1814: 1813: 1808: 1803: 1798: 1793: 1788: 1783: 1778: 1773: 1768: 1763: 1758: 1752: 1750: 1744: 1743: 1741: 1740: 1735: 1730: 1725: 1720: 1715: 1710: 1705: 1700: 1695: 1690: 1685: 1679: 1674: 1669: 1664: 1658: 1656: 1648: 1647: 1645: 1644: 1639: 1634: 1629: 1623: 1618: 1613: 1611:Psychrometrics 1608: 1603: 1598: 1593: 1587: 1581: 1576: 1571: 1566: 1561: 1556: 1551: 1546: 1541: 1535: 1530: 1525: 1520: 1515: 1510: 1508:Air flow meter 1504: 1502: 1496: 1495: 1493: 1492: 1487: 1482: 1477: 1472: 1466: 1461: 1456: 1451: 1446: 1441: 1436: 1431: 1426: 1421: 1416: 1411: 1406: 1401: 1396: 1391: 1386: 1381: 1376: 1371: 1366: 1361: 1356: 1351: 1346: 1341: 1336: 1331: 1326: 1321: 1316: 1311: 1306: 1301: 1296: 1291: 1286: 1284:Heating system 1281: 1276: 1271: 1266: 1264:Heat exchanger 1261: 1256: 1251: 1246: 1241: 1236: 1231: 1229:Gas compressor 1226: 1221: 1216: 1211: 1206: 1201: 1196: 1191: 1186: 1181: 1176: 1171: 1166: 1164:Expansion tank 1161: 1156: 1151: 1146: 1141: 1136: 1131: 1126: 1121: 1116: 1111: 1106: 1101: 1096: 1091: 1086: 1084:Ceramic heater 1081: 1076: 1071: 1066: 1061: 1056: 1051: 1046: 1041: 1036: 1031: 1026: 1021: 1016: 1011: 1005: 1003: 999: 998: 996: 995: 990: 985: 979: 973: 967: 962: 957: 952: 947: 942: 937: 932: 927: 925:Solar air heat 922: 917: 915:Renewable heat 912: 907: 902: 897: 892: 887: 882: 877: 872: 867: 862: 857: 852: 847: 842: 837: 831: 826: 824:Forced-air gas 821: 816: 811: 805: 800: 795: 790: 785: 779: 774: 768: 763: 758: 752: 747: 742: 737: 732: 727: 722: 717: 712: 707: 702: 697: 691: 689: 685: 684: 682: 681: 676: 674:Thermodynamics 671: 666: 661: 656: 651: 646: 644:Psychrometrics 641: 636: 631: 626: 621: 616: 611: 606: 601: 599:Gas compressor 596: 594:Fluid dynamics 591: 586: 581: 576: 571: 566: 561: 555: 553: 547: 546: 541: 539: 538: 531: 524: 516: 509: 508:External links 506: 503: 502: 481: 456: 455: 453: 450: 449: 448: 443: 438: 432: 425: 422: 416: 413: 405: 404: 397: 394: 391: 388: 384: 377: 376: 373: 365: 362: 361: 360: 357: 350: 349: 346: 338: 335: 329: 326: 272:compressed air 231: 228: 135: 134: 117:September 2014 49: 47: 40: 26: 24: 14: 13: 10: 9: 6: 4: 3: 2: 1946: 1935: 1932: 1930: 1927: 1926: 1924: 1917: 1915: 1910: 1897: 1894: 1892: 1889: 1887: 1884: 1882: 1879: 1877: 1874: 1872: 1869: 1867: 1864: 1862: 1859: 1858: 1856: 1852: 1845: 1842: 1839: 1836: 1834: 1831: 1828: 1825: 1824: 1822: 1818: 1812: 1809: 1807: 1804: 1802: 1799: 1797: 1794: 1792: 1789: 1787: 1784: 1782: 1779: 1777: 1774: 1772: 1769: 1767: 1764: 1762: 1759: 1757: 1754: 1753: 1751: 1749:organizations 1745: 1739: 1736: 1734: 1731: 1729: 1726: 1724: 1721: 1719: 1716: 1714: 1711: 1709: 1706: 1704: 1701: 1699: 1696: 1694: 1693:Duct cleaning 1691: 1689: 1686: 1683: 1680: 1678: 1675: 1673: 1670: 1668: 1665: 1663: 1660: 1659: 1657: 1649: 1643: 1640: 1638: 1635: 1633: 1630: 1627: 1624: 1622: 1619: 1617: 1614: 1612: 1609: 1607: 1604: 1602: 1599: 1597: 1594: 1591: 1588: 1585: 1582: 1580: 1577: 1575: 1572: 1570: 1567: 1565: 1562: 1560: 1557: 1555: 1552: 1550: 1547: 1545: 1544:Control valve 1542: 1539: 1536: 1534: 1531: 1529: 1526: 1524: 1521: 1519: 1516: 1514: 1511: 1509: 1506: 1505: 1503: 1497: 1491: 1488: 1486: 1483: 1481: 1478: 1476: 1473: 1470: 1467: 1465: 1464:Turning vanes 1462: 1460: 1457: 1455: 1452: 1450: 1447: 1445: 1442: 1440: 1439:Thermal wheel 1437: 1435: 1432: 1430: 1427: 1425: 1422: 1420: 1417: 1415: 1412: 1410: 1407: 1405: 1404:Solar chimney 1402: 1400: 1397: 1395: 1392: 1390: 1387: 1385: 1382: 1380: 1377: 1375: 1372: 1370: 1367: 1365: 1362: 1360: 1357: 1355: 1352: 1350: 1347: 1345: 1342: 1340: 1337: 1335: 1332: 1330: 1327: 1325: 1322: 1320: 1317: 1315: 1312: 1310: 1307: 1305: 1302: 1300: 1297: 1295: 1292: 1290: 1287: 1285: 1282: 1280: 1277: 1275: 1272: 1270: 1267: 1265: 1262: 1260: 1257: 1255: 1252: 1250: 1247: 1245: 1242: 1240: 1237: 1235: 1232: 1230: 1227: 1225: 1222: 1220: 1217: 1215: 1212: 1210: 1207: 1205: 1202: 1200: 1197: 1195: 1192: 1190: 1187: 1185: 1182: 1180: 1177: 1175: 1174:Fan coil unit 1172: 1170: 1167: 1165: 1162: 1160: 1157: 1155: 1152: 1150: 1147: 1145: 1142: 1140: 1137: 1135: 1132: 1130: 1127: 1125: 1122: 1120: 1119:Cooling tower 1117: 1115: 1112: 1110: 1107: 1105: 1102: 1100: 1097: 1095: 1092: 1090: 1087: 1085: 1082: 1080: 1077: 1075: 1072: 1070: 1067: 1065: 1062: 1060: 1057: 1055: 1052: 1050: 1047: 1045: 1042: 1040: 1037: 1035: 1032: 1030: 1027: 1025: 1022: 1020: 1017: 1015: 1012: 1010: 1007: 1006: 1004: 1000: 994: 991: 989: 986: 983: 980: 977: 974: 971: 968: 966: 965:Vapor barrier 963: 961: 958: 956: 953: 951: 948: 946: 943: 941: 940:Solar heating 938: 936: 935:Solar cooling 933: 931: 928: 926: 923: 921: 918: 916: 913: 911: 910:Refrigeration 908: 906: 903: 901: 898: 896: 893: 891: 888: 886: 883: 881: 880:Passive house 878: 876: 873: 871: 868: 866: 863: 861: 858: 856: 853: 851: 848: 846: 843: 841: 838: 835: 832: 830: 827: 825: 822: 820: 817: 815: 812: 809: 806: 804: 801: 799: 796: 794: 791: 789: 786: 783: 780: 778: 775: 772: 769: 767: 764: 762: 759: 756: 753: 751: 750:Chilled water 748: 746: 743: 741: 738: 736: 733: 731: 728: 726: 723: 721: 718: 716: 713: 711: 708: 706: 703: 701: 698: 696: 693: 692: 690: 686: 680: 677: 675: 672: 670: 667: 665: 662: 660: 657: 655: 652: 650: 649:Sensible heat 647: 645: 642: 640: 637: 635: 632: 630: 629:Noise control 627: 625: 622: 620: 617: 615: 612: 610: 609:Heat transfer 607: 605: 602: 600: 597: 595: 592: 590: 587: 585: 582: 580: 577: 575: 572: 570: 567: 565: 562: 560: 557: 556: 554: 548: 544: 537: 532: 530: 525: 523: 518: 517: 514: 507: 492: 485: 482: 471: 470:www.h-v-c.com 467: 461: 458: 451: 447: 444: 442: 439: 436: 433: 431: 428: 427: 423: 421: 414: 412: 409: 402: 398: 395: 392: 389: 385: 382: 381: 380: 374: 371: 370: 369: 363: 358: 355: 354: 353: 347: 344: 343: 342: 336: 334: 327: 325: 321: 318: 314: 310: 305: 301: 299: 294: 291: 288: 283: 278: 275: 273: 269: 264: 261: 257: 253: 244: 236: 229: 227: 225: 221: 217: 213: 209: 206:In a chimney 204: 202: 198: 194: 190: 186: 182: 178: 174: 170: 166: 162: 158: 154: 150: 141: 131: 128: 120: 109: 106: 102: 99: 95: 92: 88: 85: 81: 78: –  77: 73: 72:Find sources: 66: 62: 56: 55: 50:This article 48: 44: 39: 38: 33: 19: 1906: 1871:Fireproofing 1655:and services 1651:Professions, 1549:Gas detector 1449:Trickle vent 1424:Smoke damper 1419:Smoke canopy 1414:Space heater 1344:Plenum space 1279:Heating film 1159:Exhaust hood 1129:Dehumidifier 1123: 1069:Blast damper 1064:Barrier pipe 1039:Air purifier 950:Thermosiphon 829:Free cooling 745:Chilled beam 669:Thermal mass 654:Stack effect 639:Particulates 619:Infiltration 550:Fundamental 494:. Retrieved 484: 473:. Retrieved 469: 460: 418: 415:Fire dampers 406: 378: 368:Advantages: 367: 364:Zone dampers 351: 341:Advantages: 340: 331: 322: 306: 302: 295: 279: 276: 265: 255: 251: 249: 205: 148: 146: 123: 114: 104: 97: 90: 83: 71: 59:Please help 54:verification 51: 1914:Air dampers 1881:Warm Spaces 1523:Blower door 1501:and control 1499:Measurement 1480:Windcatcher 1454:Trombe wall 1394:Sail switch 1374:Refrigerant 1369:Recuperator 1244:Grease duct 1204:Freeze stat 1189:Fire damper 1059:Back boiler 1029:Air ionizer 1024:Air handler 988:Ventilation 840:Hybrid heat 705:Air barrier 624:Latent heat 177:temperature 169:air handler 153:flow of air 18:Zone damper 1923:Categories 1637:Thermostat 1559:Humidistat 1490:Zone valve 1459:TurboSwing 1334:Oil heater 1304:Humidifier 1234:Gas heater 1184:Fan heater 1154:Evaporator 1139:Economizer 1114:Compressor 1019:Air filter 1002:Components 819:Forced-air 715:Antifreeze 688:Technology 634:Outgassing 574:Convection 496:2023-11-17 475:2022-09-21 452:References 430:Zone valve 387:condition. 193:thermostat 87:newspapers 1747:Industry 1596:OpenTherm 1274:Heat pump 1269:Heat pipe 1219:Fume hood 1194:Fireplace 1099:Condenser 1049:Attic fan 845:Hydronics 408:Pneumatic 212:fireplace 189:pneumatic 155:inside a 1854:See also 1579:LonWorks 1513:Aquastat 1379:Register 1359:Radiator 1014:Air door 814:Firestop 614:Humidity 589:Enthalpy 579:Dilution 564:Bake-out 552:concepts 424:See also 317:LonWorks 311:such as 201:solenoid 185:electric 1653:trades, 1224:Furnace 1089:Chiller 761:Coolant 165:VAV box 161:chimney 101:scholar 1806:SMACNA 1766:ASHRAE 1586:(MERV) 1540:(CADR) 1518:BACnet 1471:(ULPA) 1324:Louver 1249:Grille 1124:Damper 1074:Boiler 972:(VCRS) 773:(DOAS) 401:relays 313:BACnet 298:spring 268:vacuum 149:damper 103:  96:  89:  82:  74:  1846:(VOC) 1840:(SBS) 1829:(IAQ) 1786:CIBSE 1781:BSRIA 1684:(BIM) 1628:(STP) 1592:(NTP) 1214:Freon 984:(VRF) 978:(VAV) 836:(HRV) 810:(ERV) 784:(DCV) 757:(CAV) 437:(VAV) 372:Cost. 224:smoke 108:JSTOR 94:books 1801:LEED 1761:AMCA 1756:AHRI 1289:HEPA 1209:Flue 1134:Duct 287:volt 260:HVAC 220:fire 208:flue 179:and 157:duct 80:news 1811:UMC 1796:IIR 1776:BRE 1169:Fan 315:or 270:or 256:VCD 254:or 195:or 187:or 63:by 1925:: 468:. 290:AC 167:, 163:, 159:, 147:A 535:e 528:t 521:v 499:. 478:. 130:) 124:( 119:) 115:( 105:· 98:· 91:· 84:· 57:. 34:. 20:)

Index

Zone damper
Damper (disambiguation)

verification
improve this article
adding citations to reliable sources
"Damper" flow
news
newspapers
books
scholar
JSTOR
Learn how and when to remove this message

flow of air
duct
chimney
VAV box
air handler
air conditioning
temperature
climate control
electric
pneumatic
thermostat
building automation
solenoid
flue
fireplace
wood-burning stove

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.