Knowledge (XXG)

Network protector

Source 📝

135:
network will energize the primary feeder through the network transformer. This can be very dangerous, because a fault will continue to be 'fed' from the secondary network side of transformer. Even without a fault, if the electric utility wants to perform maintenance on that primary cable, they must have a way to fully disconnect that primary cable, without worrying about the cable being energized by the secondary network through the network transformer. Thus, the network protector is designed to open its contacts if the relay senses backwards flowing current.
22: 356: 935: 97:. The secondary grid system improves continuity of service for customers, since multiple sources are available to supply the load; a fault with any one supply is automatically isolated by the network protector and does not interrupt service from the other sources. Secondary grids are often used in downtown areas of cities where there are many customers in a small area. 115:
secondary contacts. The controlling relay monitors voltage and current in the transformer, and opens or closes the contact mechanism through electrical signals. The relay uses a power/time curve so that small, short term reverse power flow (such as from elevator hoists) are ignored. Spot units will be 277/480 and the grid units will be 120/208.
109:
Network protectors typically have three settings, "automatic", "open", and "close". The top side is fed from multiple protectors and is always energized unless all units on a spot network are in the open position. Grid units will always be energized on the top side from the many other units tied into
114:
set of contacts and a controlling protection relay. The components are enclosed in a protective housing; some network protectors are installed on transformers below grade and must be in water-resistant enclosures. The mechanism contains electrical and mechanical parts to switch open and close the
134:
on the primary feeder, the substation circuit-breaker is meant to open, disconnecting the primary feeder from one side. The problem is that this primary cable is also connected to a network transformer, which is interconnected to other network transformers on its secondary side. The secondary
146:
Analysis of the system is required to ensure that the system can, indeed, supply enough current to fuse the cables, wherever the fault is. This method tends to work well at 120 volts, but it is less reliable at higher voltages. The danger in depending on the cable to 'burn clear' is that some
105:
Typically the network protector is set to close when the voltage difference and phase angle are such that the transformer will supply power to the secondary grid, and is set to open when the secondary grid would back-feed through the transformer and supply power to the primary circuit.
143:(like fuses) to melt and disconnect the secondary fault under the right conditions. In other cases, the utility lets cable 'burn clear', in which case the fault is allowed to remain fed until the cables fuse, then the fault is isolated. 138:
However, if there is a fault on the secondary grid, the network protector is not designed to open its contacts up. The secondary fault will continue to be fed from the primary side of the system. In some cases, networks are designed with
147:
conditions will not cause the cable to burn in this manner and instead, the entire section of cable can be damaged from excessive, long-term overloading, causing fires and damage to the secondary network.
127:. The network protector is installed to protect the stability and reliability of the secondary grid by preventing power flow away from the customers and into the primary feeders. 180: 150:
Typically, network protectors are contained inside a submersible enclosure which is bolted to the throat of the network transformer and placed in underground vaults.
207: 880: 110:
the grid. A spot network is 2 or more transformers dedicated to a single customer. The grid feeds multiple customers. A network protector has a
959: 938: 777: 885: 355: 200: 505: 56: 41:
Please help improve this article by looking for better, more reliable sources. Unreliable citations may be challenged and removed.
964: 668: 593: 464: 840: 772: 762: 638: 538: 193: 35: 693: 653: 230: 920: 915: 633: 608: 598: 574: 569: 275: 30: 835: 553: 523: 300: 890: 379: 340: 131: 865: 673: 613: 270: 82: 78: 804: 794: 784: 90: 74: 725: 588: 371: 260: 21: 860: 628: 623: 603: 454: 216: 825: 658: 558: 533: 486: 295: 285: 250: 124: 94: 699: 310: 850: 730: 335: 86: 799: 740: 444: 439: 416: 325: 265: 830: 789: 767: 648: 618: 583: 543: 345: 111: 89:
when the power starts flowing in reverse direction. Network protectors are used on both
855: 845: 643: 255: 953: 875: 663: 548: 528: 459: 449: 406: 290: 245: 140: 895: 870: 735: 704: 518: 320: 163: 720: 688: 481: 469: 389: 315: 305: 235: 683: 678: 491: 474: 330: 399: 394: 280: 240: 123:
The network protector does not protect the (secondary) network cable from
513: 434: 424: 185: 81:
systems. The network protector automatically disconnect its associated
429: 384: 151: 189: 175: 15: 904: 814: 751: 713: 567: 504: 415: 370: 363: 223: 154:standard C57.12.44 covers network protectors. 201: 8: 367: 208: 194: 186: 57:Learn how and when to remove this message 7: 886:Renewable energy commercialization 14: 934: 933: 354: 20: 176:Richards Manufacturing Company 1: 881:Renewable Energy Certificates 841:Cost of electricity by source 763:Arc-fault circuit interrupter 639:High-voltage shore connection 896:Spark/Dark/Quark/Bark spread 694:Transmission system operator 654:Mains electricity by country 231:Automatic generation control 960:Electric power distribution 921:List of electricity sectors 916:Electric energy consumption 634:High-voltage direct current 609:Electric power transmission 599:Electric power distribution 276:Energy return on investment 981: 836:Carbon offsets and credits 554:Three-phase electric power 929: 891:Renewable Energy Payments 380:Fossil fuel power station 352: 674:Single-wire earth return 614:Electrical busbar system 271:Energy demand management 181:Eaton network protectors 83:distribution transformer 79:electricity distribution 805:Residual-current device 795:Power system protection 785:Generator interlock kit 29:Some of this article's 965:Electrical engineering 589:Distributed generation 261:Electric power quality 73:is a type of electric 861:Fossil fuel phase-out 629:Electricity retailing 624:Electrical substation 604:Electric power system 217:Electricity delivery 826:Availability factor 778:Sulfur hexafluoride 659:Overhead power line 559:Virtual power plant 534:Induction generator 487:Sustainable biofuel 296:Home energy storage 286:Grid energy storage 251:Droop speed control 700:Transmission tower 311:Nameplate capacity 947: 946: 851:Environmental tax 731:Cascading failure 500: 499: 336:Utility frequency 87:secondary network 75:protective device 71:network protector 67: 66: 59: 972: 937: 936: 846:Energy subsidies 800:Protective relay 741:Rolling blackout 368: 358: 326:Power-flow study 266:Electrical fault 210: 203: 196: 187: 112:circuit breaker 62: 55: 51: 48: 42: 24: 16: 980: 979: 975: 974: 973: 971: 970: 969: 950: 949: 948: 943: 925: 909: 907: 900: 831:Capacity factor 819: 817: 810: 790:Numerical relay 768:Circuit breaker 756: 754: 747: 709: 649:Load management 619:Electrical grid 584:Demand response 577: 572: 563: 544:Microgeneration 496: 411: 359: 350: 346:Vehicle-to-grid 219: 214: 172: 160: 121: 103: 63: 52: 46: 43: 40: 25: 12: 11: 5: 978: 976: 968: 967: 962: 952: 951: 945: 944: 942: 941: 930: 927: 926: 924: 923: 918: 912: 910: 906:Statistics and 905: 902: 901: 899: 898: 893: 888: 883: 878: 873: 868: 863: 858: 856:Feed-in tariff 853: 848: 843: 838: 833: 828: 822: 820: 815: 812: 811: 809: 808: 802: 797: 792: 787: 782: 781: 780: 775: 765: 759: 757: 752: 749: 748: 746: 745: 744: 743: 733: 728: 723: 717: 715: 711: 710: 708: 707: 702: 697: 691: 686: 681: 676: 671: 666: 661: 656: 651: 646: 644:Interconnector 641: 636: 631: 626: 621: 616: 611: 606: 601: 596: 594:Dynamic demand 591: 586: 580: 578: 568: 565: 564: 562: 561: 556: 551: 546: 541: 536: 531: 526: 524:Combined cycle 521: 516: 510: 508: 502: 501: 498: 497: 495: 494: 489: 484: 479: 478: 477: 472: 467: 462: 457: 447: 442: 437: 432: 427: 421: 419: 413: 412: 410: 409: 404: 403: 402: 397: 392: 387: 376: 374: 365: 361: 360: 353: 351: 349: 348: 343: 338: 333: 328: 323: 318: 313: 308: 303: 301:Load-following 298: 293: 288: 283: 278: 273: 268: 263: 258: 256:Electric power 253: 248: 243: 238: 233: 227: 225: 221: 220: 215: 213: 212: 205: 198: 190: 184: 183: 178: 171: 168: 167: 166: 159: 156: 141:cable limiters 130:If there is a 120: 117: 102: 99: 65: 64: 31:listed sources 28: 26: 19: 13: 10: 9: 6: 4: 3: 2: 977: 966: 963: 961: 958: 957: 955: 940: 932: 931: 928: 922: 919: 917: 914: 913: 911: 903: 897: 894: 892: 889: 887: 884: 882: 879: 877: 876:Pigouvian tax 874: 872: 869: 867: 864: 862: 859: 857: 854: 852: 849: 847: 844: 842: 839: 837: 834: 832: 829: 827: 824: 823: 821: 813: 806: 803: 801: 798: 796: 793: 791: 788: 786: 783: 779: 776: 774: 773:Earth-leakage 771: 770: 769: 766: 764: 761: 760: 758: 750: 742: 739: 738: 737: 734: 732: 729: 727: 724: 722: 719: 718: 716: 714:Failure modes 712: 706: 703: 701: 698: 695: 692: 690: 687: 685: 682: 680: 677: 675: 672: 670: 667: 665: 664:Power station 662: 660: 657: 655: 652: 650: 647: 645: 642: 640: 637: 635: 632: 630: 627: 625: 622: 620: 617: 615: 612: 610: 607: 605: 602: 600: 597: 595: 592: 590: 587: 585: 582: 581: 579: 576: 571: 566: 560: 557: 555: 552: 550: 549:Rankine cycle 547: 545: 542: 540: 537: 535: 532: 530: 529:Cooling tower 527: 525: 522: 520: 517: 515: 512: 511: 509: 507: 503: 493: 490: 488: 485: 483: 480: 476: 473: 471: 468: 466: 463: 461: 458: 456: 453: 452: 451: 448: 446: 443: 441: 438: 436: 433: 431: 428: 426: 423: 422: 420: 418: 414: 408: 405: 401: 398: 396: 393: 391: 388: 386: 383: 382: 381: 378: 377: 375: 373: 372:Non-renewable 369: 366: 362: 357: 347: 344: 342: 339: 337: 334: 332: 329: 327: 324: 322: 319: 317: 314: 312: 309: 307: 304: 302: 299: 297: 294: 292: 291:Grid strength 289: 287: 284: 282: 279: 277: 274: 272: 269: 267: 264: 262: 259: 257: 254: 252: 249: 247: 246:Demand factor 244: 242: 239: 237: 234: 232: 229: 228: 226: 222: 218: 211: 206: 204: 199: 197: 192: 191: 188: 182: 179: 177: 174: 173: 169: 165: 162: 161: 157: 155: 153: 148: 144: 142: 136: 133: 128: 126: 118: 116: 113: 107: 100: 98: 96: 95:grid networks 92: 91:spot networks 88: 84: 80: 76: 72: 61: 58: 50: 38: 37: 32: 27: 23: 18: 17: 871:Net metering 818:and policies 736:Power outage 705:Utility pole 669:Pumped hydro 575:distribution 570:Transmission 519:Cogeneration 321:Power factor 164:Autorecloser 149: 145: 137: 129: 122: 108: 104: 70: 68: 53: 44: 33: 866:Load factor 721:Black start 689:Transformer 390:Natural gas 341:Variability 316:Peak demand 306:Merit order 236:Backfeeding 119:Application 34:may not be 954:Categories 908:production 753:Protective 684:Super grid 679:Smart grid 506:Generation 440:Geothermal 331:Repowering 170:References 816:Economics 539:Micro CHP 417:Renewable 400:Petroleum 395:Oil shale 281:Grid code 241:Base load 101:Operation 85:from the 47:July 2014 939:Category 726:Brownout 514:AC power 224:Concepts 158:See also 125:overload 77:used in 36:reliable 755:devices 465:Thermal 460:Osmotic 455:Current 435:Biomass 425:Biofuel 407:Nuclear 364:Sources 450:Marine 430:Biogas 807:(GFI) 696:(TSO) 482:Solar 470:Tidal 445:Hydro 132:fault 573:and 492:Wind 475:Wave 385:Coal 152:IEEE 93:and 956:: 69:A 209:e 202:t 195:v 60:) 54:( 49:) 45:( 39:.

Index


listed sources
reliable
Learn how and when to remove this message
protective device
electricity distribution
distribution transformer
secondary network
spot networks
grid networks
circuit breaker
overload
fault
cable limiters
IEEE
Autorecloser
Richards Manufacturing Company
Eaton network protectors
v
t
e
Electricity delivery
Automatic generation control
Backfeeding
Base load
Demand factor
Droop speed control
Electric power
Electric power quality
Electrical fault

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.