Knowledge (XXG)

Substation

Source 📝

910:. Although it is the most expensive, these gases are a much more effective insulator than air. GIS require only 10 to 20 percent of the land area as AIS, which can save on land acquisition cost in urban areas, and allow the substation to be built at the exact location where its power is being used in an industrial or urban area—which can be a significant cost savings. On the generation side, GIS can be installed closer to the generator which allows cost savings in cabling, bus duct connections, and civil construction and can increase reliability. GIS can replace AIS if power requirements increase without requiring additional land area. Additionally, GIS is commonly installed in an enclosed building that keeps the equipment protected from pollution and salt. Unless the substation is often used for switching, maintenance cost can be very low or even zero for many years. Because SF 633: 516: 504: 181: 488: 481:, which is the connecting and disconnecting of transmission lines or other components to and from the system. Switching events may be planned or unplanned. A transmission line or other component may need to be de-energized for maintenance or for new construction, for example, adding or removing a transmission line or a transformer. To maintain reliability of supply, companies aim at keeping the system up and running while performing maintenance. All work to be performed, from routine testing to adding entirely new substations, should be done while keeping the whole system running. 307: 38: 201:. Most commonly, the utility does the engineering and procurement while hiring a contractor for actual construction. Major design constraints for construction of substations include land availability and cost, limitations on the construction period, transportation restrictions, and the need to get the substation running quickly. Prefabrication is a common way to reduce the construction cost. For connecting the new substation, a partial outage at another substation may be required, but the utility often tries to minimize downtime. 710:. In some cases, the lines will not have both, with either a switch or a circuit breaker being all that is considered necessary. A disconnect switch is used to provide isolation, since it cannot interrupt load current. A circuit breaker is used as a protection device to interrupt fault currents automatically, and may be used to switch loads on and off, or to cut off a line when power is flowing in the 'wrong' direction. When a large fault current flows through the circuit breaker, this is detected through the use of 210: 692: 714:. The magnitude of the current transformer outputs may be used to trip the circuit breaker resulting in a disconnection of the load supplied by the circuit break from the feeding point. This seeks to isolate the fault point from the rest of the system, and allow the rest of the system to continue operating with minimal impact. Both switches and circuit breakers may be operated locally (within the substation) or remotely from a supervisory control center. 645: 355: 98: 617: 2246: 118: 2825: 703:, which shows in simplified form the switching and protection arrangement required, as well as the incoming supply lines and outgoing feeders or transmission lines. It is a usual practice by many electrical utilities to prepare one-line diagrams with principal elements (lines, switches, circuit breakers, transformers) arranged on the page similarly to the way the apparatus would be laid out in the actual station. 764: 781:. To this is added the necessary space for employees to work safely and vehicles to pass. Sometimes it is necessary to work on parts of the substation while energized, but employees must maintain a safe distance of at least 3 metres (9.8 ft). The aim to reduce substation footprints comes into conflict with ease of maintenance enhanced by including gaps where employees can safely work. 226: 347: 990:
when there is any unusual activity, to help reconstruct what happened after the fact. These control rooms typically are heated and air conditioned to ensure the reliable operation of this equipment. Additional equipment is necessary to handle power surges associated with intermittent renewable energy such as dispersed generation from wind or solar.
924:(called OCB for oil circuit breaker) provides a high resistance between the opened contacts, effectively stopping the flow of current. Although oil circuit breakers are suitable for a wide range of voltages, the oil becomes contaminated during the suppression of arcs and must be filtered or replaced periodically. 1012:
finds hot spots in the substation where electrical energy is being converted to heat, which indicates a problem and can cause additional damage from the high heat. Dissolved gas analysis can tell when an oil-insulated transformer needs to have the oil filtered or replace, and also detect other issues.
1026:
Early electrical substations required manual switching or adjustment of equipment, and manual collection of data for load, energy consumption, and abnormal events. As the complexity of distribution networks grew, it became economically necessary to automate supervision and control of substations from
1011:
Maintenance of substations involves inspections, data collection and analysis, and routine scheduled work. Using methods such as infrared scanning and dissolved gas analysis, it can be predicted when the substation will need maintenance and predict dangers before they materialize. Infrared technology
989:
Larger substations have control rooms for the equipment used to monitor, control, and protect the rest of the substation equipment. It often contains protective relays, meters, breaker controls, communications, batteries, and recorders that save detailed data about substation operations, particularly
845:
Substations may be on the surface in fenced enclosures, underground, or special-purpose buildings. High-rise buildings may have several indoor substations. Indoor substations are usually found in urban areas to reduce the noise from transformers, improve appearance, or protect switchgear from extreme
998:
Most transformers lose between 5 and 1.5 percent of their input as heat and noise. Iron losses are no-load and constant whenever the transformer is energized, while copper and auxiliary losses are proportionate to the square of the current. Auxiliary losses are due to running fans and pumps which is
890:
Air at atmospheric pressure (air-insulated switchgear (AIS)), which is the most common worldwide. Air is the cheapest insulator and is easy to modify, but AIS takes up more space, and leaves equipment exposed to the outside environment. One drawback of AIS is the visual impact of a larger substation
792:
in some countries, is used to ground circuits that are being worked on to prevent accidental re-energization while workers are in contact with a de-energized circuit. Often, earth rods are driven deeper into the ground from the grounding grid for lower resistance grounding, and may be surrounded by
777:
Based on the jurisdiction or company, there are safety standards with minimum required clearance between different live equipment or conductors or between live metal and the ground, which often varies with higher clearance being required for higher voltages because of the greater ability to generate
462:
A switching station is a substation without transformers and operating only at a single voltage level. Switching stations are sometimes used as collector and distribution stations. Sometimes they are used for switching the current to back-up lines or for parallelizing circuits in case of failure. An
374:
The input for a distribution substation is typically at least two transmission or sub-transmission lines. Input voltage may be, for example, 115 kV, or whatever is common in the area. The output is a number of feeders. Distribution voltages are typically medium voltage, between 2.4 kV and
856:
Outdoor, above-ground substation structures include wood pole, lattice metal tower, and tubular metal structures, although other variants are available. Where space is plentiful and appearance of the station is not a factor, steel lattice towers provide low-cost supports for transmission lines and
776:
Because of the risk of electrical shock, substations are inherently dangerous to electrical workers. To mitigate this hazard, substations are designed with various safety features. Live conductors and bare equipment are kept separate, either with protected equipment, or using screens or distance.
759:
The arrangement of switches, circuit breakers, and buses used affects the cost and reliability of the substation. For important substations a ring bus, double bus, or so-called "breaker and a half" setup can be used, so that the failure of any one circuit breaker does not interrupt power to other
663:
Selection of the location of a substation must consider many factors. Sufficient land area is required for installation of equipment with necessary clearances for electrical safety, and for access to maintain large apparatus such as transformers. The site must have room for expansion due to load
881:
are commonly used to interrupt the flow of current in substation equipment. At the time of interruption, current could be normal, too high due to excessive load, unusual due to a fault, or tripped by protective relays prior to anticipated trouble. The most common technologies to extinguish the
801:
to further reduce resistance and ensure effective grounding for the lifetime of the substation. Above ground, the grounding conductors may be steel, aluminum, or copper. They must be thick enough to carry the expected current of a fault for 1-3 seconds and remain undamaged. Substation fences,
370:
transfers power from the transmission system to the distribution system of an area. It is uneconomical to directly connect electricity consumers to the main transmission network, unless they use large amounts of power, so the distribution station reduces voltage to a level suitable for local
941:
are similar to breakers, and can be cheaper because they do not require separate protective relays. Often used in distribution, they often are programmed to trip when the amps exceed a certain amount over a period of time. Reclosers will attempt to re-energize the circuit after a delay. If
414:
up into the transmission grid. Usually for economy of construction the collector system operates around 35 kV, although some collector systems are 12 kV, and the collector substation steps up voltage to a transmission voltage for the grid. The collector substation can also provide
385:
The downtown areas of large cities feature complicated distribution substations, with high-voltage switching, and switching and backup systems on the low-voltage side. More typical distribution substations have a switch, one transformer, and minimal facilities on the low-voltage side.
282:
connects two or more transmission lines. The simplest case is where all transmission lines have the same voltage. In such cases, substation contains high-voltage switches that allow lines to be connected or isolated for fault clearance or maintenance. A transmission station may have
671:
The substation site must be reasonably central to the distribution area to be served. The site must be secure from intrusion by passers-by, both to protect people from injury by electric shock or arcs, and to protect the electrical system from misoperation due to vandalism.
549:
The function of the switching station is to isolate the faulty portion of the system in the shortest possible time. De-energizing faulty equipment protects it from further damage, and isolating a fault helps keep the rest of the electrical grid operating with stability.
1002:
Oil-based transformers are often built with bunded areas to prevent the escape of flaming or leaking oil. Fire separation areas or firewalls are built around the transformer to stop the spread of fire. Firefighting vehicles are allowed a path to access the area.
802:
typically at least 2 metres (6 ft 7 in) in height, both protect the public from electrical hazards and also protect the substation from vandalism. Internal fences can also be incorporated to protect employees from areas that are unsafe when energized.
154:
to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. There are 55,000 substations in the United States.
503: 173:. As central generation stations became larger, smaller generating plants were converted to distribution stations, receiving their energy supply from a larger plant instead of using their own generators. The first substations were connected to only one 861:(at high voltages, with gas insulated switchgear), or use metal-enclosed or metal-clad switchgear at lower voltages. Urban and suburban indoor substations may be finished on the outside so as to blend in with other buildings in the area. 375:
33 kV, depending on the size of the area served and the practices of the local utility. The feeders run along streets overhead (or underground, in some cases) and power the distribution transformers at or near the customer premises.
149:
from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A substation may include
1027:
a centrally attended point, to allow overall coordination in case of emergencies and to reduce operating costs. Early efforts to remote control substations used dedicated communication wires, often run alongside power circuits.
474:. In this case the generators from the power station supply their power into the yard onto the generator bus on one side of the yard, and the transmission lines take their power from a Feeder Bus on the other side of the yard. 362:, Canada, disguised as a house, complete with a driveway, front walk and a mown lawn and shrubs in the front yard. A warning notice can be clearly seen on the "front door". Disguises for substations are common in many cities. 580:(AC) at frequencies other than that of the public grid. Sometimes they are also transmission substations or collector substations if the railway network also operates its own grid and generators to supply the other stations. 760:
circuits, and so that parts of the substation may be de-energized for maintenance and repairs. Substations feeding only a single industrial load may have minimal switching provisions, especially for small installations.
1059:, to list a few, are used to allow multiple intelligent electronic devices to communicate with each other and supervisory control centers. Distributed automatic control at substations is one element of the so-called 868:
is generally an outdoor substation built in a metal enclosure, in which each item of the electrical equipment is located very near to each other to create a relatively smaller footprint size of the substation.
450:, or interconnected non-synchronous networks. These stations contain power electronic devices to change the frequency of current, or else convert from alternating to direct current or the reverse. Formerly 933:
Mixed, including both gas and air insulation. Although it’s the least common option it can be useful when an air-insulated substation needs to be expanded but there is very limited location for additional
1418: 767:
This single-line diagram illustrates the breaker-and-a-half configuration often used in switchyards of small utilities. In large utilities the double-bus-double-breaker configuration is often preferred.
1080: 487: 977:
or enabling extra power to be sent through the conductors. Capacitors may be left on in response to constant inductive load or turned on when inductive load is increased, such as in the summer for
322:. The largest transmission substations can cover a large area (several acres/hectares) with multiple voltage levels, many circuit breakers, and a large amount of protection and control equipment ( 930:
is a better insulator than air but less than gas or oil. Vacuum circuit breakers (VCB) are smaller than air circuit breakers and are commonly used in distribution and other switchgear under 35kv.
515: 378:
In addition to transforming voltage, distribution substations also isolate faults in either the transmission or distribution systems. Distribution substations are typically the points of
999:
noisy when the transformer is operating at maximum capacity. To reduce noise, enclosures are often built around the transformer and can also be added after the substation is built.
891:
with overhead power lines entering and exiting, which may be unacceptable in scenic or urban areas. AIS requires additional bracing in a seismically active area, and emits more
158:
Substations may be owned and operated by an electrical utility, or may be owned by a large industrial or commercial customer. Generally substations are unattended, relying on
422:
Collector substations also exist where multiple thermal or hydroelectric power plants of comparable output power are in proximity. Examples for such substations are
2097: 1047:
made for an exponential increase in the number of points that could be economically controlled and monitored. Today, standardized communication protocols such as
737:
are used to protect substation equipment accordingly. Insulation Coordination studies are carried out extensively to ensure equipment failure (and associated
2770: 636:
Substation in a castle-like building from the 1910s serves as distribution point next to the Lésna dam. It is one of several hydroelectric stations at the
652:
Substation design is aimed at minimizing cost while ensuring power availability and reliability, and enabling changes to the substation in the future.
784:
Underneath a substation, a mat or grid of conductors laid around 0.5 or 0.6 metres (1 ft 8 in or 2 ft 0 in) underground provides
564:
Electrified railways also use substations, often distribution substations. In some cases a conversion of the current type takes place, commonly with
509:
Former high-voltage substation in Stuttgart, Germany, now 110 kV switching station. The 220 kV level is eliminated for grid simplification.
1291: 608:. Mobile substations are usually rated much lower than permanent installations, and may be built in several units to meet road travel limitations. 914:
turns to solid around −40 °C (−40 °F), in some climates these circuit breakers require heaters to function in extremely cold weather. SF
419:
if it is needed, metering, and control of the wind farm. In some special cases a collector substation can also contain an HVDC converter station.
632: 110: 434:-fired power plants. If no transformers are required for increasing the voltage to transmission level, the substation is a switching station. 2066: 2047: 1972: 1950: 1856: 1822: 1803: 1784: 1765: 1739: 1711: 1624: 1605: 1574: 1404: 1385: 1195: 1176: 1157: 1138: 406:, a collector substation may be required. It resembles a distribution substation although power flow is in the opposite direction, from many 2828: 382:, although on long distribution circuits (of several miles/kilometers), voltage regulation equipment may also be installed along the line. 853:
as conductors between electrical equipment. Busbars may be aluminum tubing 3–6 inches (76–152 mm) thick, or else wires (strain bus).
121:
A 115 kV to 41.6/12.47 kV 5 MVA 60 Hz substation with circuit switcher, regulators, reclosers and control building at
2667: 2775: 2245: 2090: 2395: 1449: 857:
apparatus. Low-profile substations may be specified in suburban areas where appearance is more critical. Indoor substations may be
180: 2849: 2558: 2483: 2354: 628:
is Canada's oldest substation. It has a facade in clay brick with gray stone ornaments to blend in to its downtown environment.
113:, each with a capacity of 150 MVA. This substation uses steel lattice structures to support strain bus wires and apparatus. 2730: 2662: 2652: 2528: 2428: 2083: 1107: 2583: 2543: 2120: 470:
A switching station may also be known as a switchyard, and these are commonly located directly adjacent to or nearby a
2810: 2805: 2523: 2498: 2488: 2464: 2459: 2165: 1339: 443: 255: 242: 170: 142: 138: 31: 2725: 2443: 2413: 2190: 718: 403: 306: 2780: 2269: 2230: 810:
Substations generally have switching, protection and control equipment, and transformers. In a large substation,
527: 314:
Transmission substations can range from simple to complex. A small "switching station" may be little more than a
238: 2755: 2563: 2503: 2160: 1081:"Joint Consultation Paper: Western Metropolitan Melbourne Transmission Connection and Subtransmission Capacity" 1028: 966: 858: 327: 664:
growth or planned transmission additions. Environmental effects of the substation must be considered, such as
621: 37: 2694: 2684: 2674: 1021: 730: 600:. They are designed to be compact for travel on public roads, and are used for temporary backup in times of 416: 209: 826:
for protection of distribution circuits. Substations themselves do not usually have generators, although a
2615: 2478: 2261: 2150: 1032: 892: 395: 323: 296: 134: 2750: 2518: 2513: 2493: 973:) are added to the system. Capacitors can reduce the current in wires, helping stem system losses from 691: 592:
is a substation on wheels, containing a transformer, breakers and buswork mounted on a self-contained
2344: 2106: 962: 785: 288: 2715: 2548: 2448: 2423: 2376: 2185: 2175: 2140: 1423: 958: 942:
unsuccessful for a few times, the recloser will have to be manually reset by an electrical worker.
899: 711: 655:
Substations may be built outdoors, indoors, or underground or in a combination of these locations.
577: 559: 262: 2589: 2200: 839: 680: 542: 379: 350:
Transformer tower in Germany. Medium voltage supply at the front, low voltage output on the side.
300: 198: 883: 2740: 2620: 2225: 2062: 2043: 1445: 1419:
Electricity Substation Leases: Considerations for Utility Companies, Landowners and Developers
1312: 835: 823: 644: 427: 125:. It shows elements of low-profile construction, with apparatus mounted on individual columns. 122: 675:
If not owned and operated by a utility company, substations are typically occupied on a long
2689: 2630: 2334: 2329: 2306: 2215: 2155: 700: 601: 573: 494: 451: 447: 354: 97: 1261: 2720: 2679: 2657: 2538: 2508: 2473: 2433: 2235: 978: 878: 818:
or overload currents that may occur on the network. Smaller distribution stations may use
811: 789: 707: 616: 319: 248: 464: 744:
Once past the switching components, the lines of a given voltage connect to one or more
2745: 2735: 2533: 2145: 1044: 954: 734: 569: 266: 334:
systems). Modern substations may be implemented using international standards such as
117: 2843: 2765: 2553: 2438: 2418: 2349: 2339: 2296: 2180: 2135: 1036: 815: 726: 471: 174: 2785: 2760: 2625: 2594: 2408: 2210: 1039:
cables as well as dedicated wired remote control circuits have all been applied to
974: 970: 819: 738: 625: 597: 593: 535: 454:
changed frequency to interconnect two systems; nowadays such substations are rare.
407: 292: 17: 763: 898:
Gas (gas circuit breaker (GCB) or gas-insulated switchgear (GIS)), most commonly
177:, where the generators were housed, and were subsidiaries of that power station. 2610: 2578: 2371: 2359: 2279: 2205: 2195: 2125: 921: 827: 753: 284: 225: 151: 1108:"Attacks on Pacific north-west power stations raise fears for US electric grid" 2573: 2568: 2381: 2364: 2220: 1060: 423: 194: 2289: 2284: 2170: 2130: 1052: 950: 831: 798: 794: 778: 722: 565: 411: 399: 335: 109:, showing three of the five 220 kV/66 kV transformers, as well as 106: 102: 2403: 1292:"Lights On but Nobody Home: Behind the Fake Buildings that Power Chicago" 981:. The switching may be remote and can be done manually or automatically. 957:(such as motors, transformers, and some industrial equipment) with their 938: 665: 346: 2324: 2314: 2075: 2057:
Finn, John (2019). "Introduction to Substation Planning and Concepts".
953:
banks are used in substations to balance the lagging current draw from
699:
The first step in planning a substation layout is the preparation of a
637: 431: 359: 146: 2319: 1255: 1253: 1251: 1056: 927: 850: 756:
electrical power distribution is largely universal around the world.
749: 745: 478: 315: 214: 233:
Substations typically serve at least one of the following purposes:
197:
or alternately all phases of its development may be handled by the
1040: 762: 706:
In a common design, incoming lines have a disconnect switch and a
690: 676: 643: 631: 615: 353: 345: 331: 305: 224: 208: 179: 159: 116: 96: 36: 2274: 1048: 218: 2079: 2040:
Electric Power System Basics for the Nonelectrical Professional
1087:. Powercor Australia, Jemena, Australian Energy Market Operator 1962: 1960: 1564: 1562: 1560: 679:
such as a renewable 99-year lease, giving the utility company
605: 530:
in a transmission line or any other component, for example:
430:
in the Czech Republic, where power is collected from nearby
169:
comes from the days before the distribution system became a
1442:
Standard Handbook for Electrical Engineers Eleventh Edition
695:
Tottenham Substation, set in wild parkland in North London.
521:
High-voltage switching station in Washington, United States
27:
Part of an electrical transmission, and distribution system
1755: 1753: 1751: 1749: 788:. This grid, which is typically copper although it may be 303:
to control power flow between two adjacent power systems.
2042:. IEEE Press Series on Power and Energy Systems. Wiley. 254:
Reducing the voltage from transmission to lower-voltage
1729: 1727: 1725: 1723: 1721: 1701: 1699: 1697: 886:
from separating the conductors in the breaker include:
1892: 1890: 1834: 1832: 1684: 1682: 1475: 1473: 1238: 1236: 184:
220 kV/110 kV/20 kV station in Germany
2061:. Springer International Publishing. pp. 7–10. 830:
may have a substation nearby. Other devices such as
2794: 2704: 2641: 2603: 2457: 2394: 2305: 2260: 2253: 2113: 1223: 1221: 1219: 1217: 497:, United States, 2006. This is a 500 kV switchyard. 477:An important function performed by a substation is 1403:sfn error: no target: CITEREFGlaubitz_et_al.2018 ( 1384:sfn error: no target: CITEREFGlaubitz_et_al.2018 ( 733:failures into substation equipment. Line entrance 961:. Additional capacitor capacity may be needed if 1043:(SCADA) for substations. The development of the 258:lines that supply individual homes or businesses 1971:sfn error: no target: CITEREFNixon_et_al.2018 ( 1949:sfn error: no target: CITEREFNixon_et_al.2018 ( 1855:sfn error: no target: CITEREFNixon_et_al.2018 ( 1623:sfn error: no target: CITEREFNixon_et_al.2018 ( 1604:sfn error: no target: CITEREFNixon_et_al.2018 ( 1573:sfn error: no target: CITEREFNixon_et_al.2018 ( 1398: 1379: 245:over long distances, using step-up transformers 66:Transformer for measurement of electric voltage 287:to convert between two transmission voltages, 2091: 442:Converter substations may be associated with 8: 1966: 1944: 1850: 1618: 1599: 1568: 918:has been used in switchgear since the 1960s. 1821:sfn error: no target: CITEREFGlaubitz2018 ( 1802:sfn error: no target: CITEREFGlaubitz2018 ( 1783:sfn error: no target: CITEREFGlaubitz2018 ( 1764:sfn error: no target: CITEREFGlaubitz2018 ( 534:a line is hit by lightning and develops an 526:Unplanned switching events are caused by a 193:Substations may be designed and built by a 2257: 2098: 2084: 2076: 1431:, 26 January 2018, accessed 22 August 2023 965:(such as small diesel generators, rooftop 463:example is the switching stations for the 1738:sfn error: no target: CITEREFTwomey2018 ( 1710:sfn error: no target: CITEREFTwomey2018 ( 1271:. United States Department of Agriculture 1816: 1797: 1778: 1759: 1194:sfn error: no target: CITEREFOkada2018 ( 1175:sfn error: no target: CITEREFOkada2018 ( 1156:sfn error: no target: CITEREFOkada2018 ( 1137:sfn error: no target: CITEREFOkada2018 ( 1041:Supervisory Control and Data Acquisition 895:and noise than alternative technologies. 648:15 kV/400 V distribution tower in Poland 620:In continuous operation since 1901, the 295:devices such as capacitors, reactors or 1072: 752:, usually in multiples of three, since 483: 1733: 1705: 111:high-voltage transformer fire barriers 101:A 50 Hz electrical substation in 2021: 2009: 1920: 1896: 1881: 1869: 1838: 1688: 1673: 1661: 1242: 1189: 1170: 1151: 1132: 842:may also be located at a substation. 7: 1997: 1985: 1932: 1908: 1649: 1637: 1587: 1551: 1539: 1527: 1515: 1503: 1491: 1479: 1464: 1367: 1290:Steinberg, Neil (13 December 2013). 1262:"Design Guide for Rural Substations" 1227: 1208: 906:) or a mixture of gases including SF 162:for remote supervision and control. 1106:Anguiano, Dani (10 December 2022). 237:Increasing the voltage produced by 2776:Renewable energy commercialization 668:, noise and road traffic effects. 25: 2824: 2823: 2244: 1440:Donald G. Fink, H. Wayne Beatty 514: 502: 486: 324:voltage and current transformers 1349:. IEEE Power and Energy Society 859:gas insulated substations (GIS) 145:system. Substations transform 1: 2771:Renewable Energy Certificates 2731:Cost of electricity by source 2653:Arc-fault circuit interrupter 2529:High-voltage shore connection 358:A distribution substation in 310:Minimal HV station in Germany 2786:Spark/Dark/Quark/Bark spread 2584:Transmission system operator 2544:Mains electricity by country 2121:Automatic generation control 2811:List of electricity sectors 2806:Electric energy consumption 2524:High-voltage direct current 2499:Electric power transmission 2489:Electric power distribution 2166:Energy return on investment 1417:Chapman, A. and Broom, R., 719:overhead transmission lines 545:is blown down by high wind. 301:phase shifting transformers 213:High-voltage substation in 133:is a part of an electrical 50:Secondary power lines' side 32:Substation (disambiguation) 2866: 2726:Carbon offsets and credits 2444:Three-phase electric power 1427:, originally published by 1338:Boyd, Dan; Rampaul, Glen. 1019: 814:are used to interrupt any 596:, meant to be pulled by a 557: 404:photovoltaic power station 29: 2819: 2781:Renewable Energy Payments 2270:Fossil fuel power station 2242: 1347:IEEE Winnipeg PES Chapter 967:photovoltaic solar panels 820:recloser circuit breakers 239:electric power generation 47:Primary power lines' side 2564:Single-wire earth return 2504:Electrical busbar system 2161:Energy demand management 1313:"Transformer Fire Video" 251:of different power grids 42:Elements of a substation 2695:Residual-current device 2685:Power system protection 2675:Generator interlock kit 1022:Power-system automation 417:power factor correction 368:distribution substation 342:Distribution substation 297:static VAR compensators 293:power factor correction 280:transmission substation 274:Transmission substation 2850:Electrical substations 2479:Distributed generation 2151:Electric power quality 1269:USDA Rural Development 893:electromagnetic fields 849:Substations often use 846:climate or pollution. 768: 696: 649: 641: 629: 396:distributed generation 363: 351: 311: 299:and equipment such as 230: 222: 185: 126: 114: 94: 2751:Fossil fuel phase-out 2519:Electricity retailing 2514:Electrical substation 2494:Electric power system 766: 721:, the propagation of 694: 647: 635: 619: 438:Converter substations 357: 349: 309: 228: 212: 183: 120: 100: 90:Secondary power lines 40: 2107:Electricity delivery 2038:Blume, S.W. (2016). 1399:Glaubitz et al. 2018 1380:Glaubitz et al. 2018 1340:"Mobile Substations" 963:dispersed generation 748:. These are sets of 712:current transformers 390:Collector substation 229:Substation in Russia 30:For other uses, see 2716:Availability factor 2668:Sulfur hexafluoride 2549:Overhead power line 2449:Virtual power plant 2424:Induction generator 2377:Sustainable biofuel 2186:Home energy storage 2176:Grid energy storage 2141:Droop speed control 1621:, pp. 314–315. 1602:, pp. 313–314. 1444:, McGraw Hill 1978 1424:Squire Patton Boggs 900:sulfur hexafluoride 578:alternating current 560:Traction substation 467:transmission line. 398:projects such as a 263:alternating current 75:Current transformer 57:Primary power lines 18:Electric substation 2590:Transmission tower 2201:Nameplate capacity 1494:, pp. 46, 53. 1260:Stockton, Blaine. 1029:Power-line carrier 866:compact substation 836:voltage regulators 769: 697: 681:security of tenure 659:Location selection 650: 642: 630: 446:converter plants, 380:voltage regulation 364: 352: 336:IEC Standard 61850 312: 231: 223: 199:electrical utility 186: 127: 115: 95: 78:Lightning arrester 2837: 2836: 2741:Environmental tax 2621:Cascading failure 2390: 2389: 2226:Utility frequency 2068:978-3-319-49574-3 2049:978-1-119-18019-7 1967:Nixon et al. 2018 1945:Nixon et al. 2018 1923:, pp. 87–88. 1851:Nixon et al. 2018 1619:Nixon et al. 2018 1600:Nixon et al. 2018 1569:Nixon et al. 2018 1554:, pp. 55–56. 1518:, pp. 48–49. 1506:, pp. 46–47. 1454:Substation Design 590:mobile substation 584:Mobile substation 576:for trains using 574:rotary converters 458:Switching station 452:rotary converters 123:Warren, Minnesota 69:Disconnect switch 16:(Redirected from 2857: 2827: 2826: 2736:Energy subsidies 2690:Protective relay 2631:Rolling blackout 2258: 2248: 2216:Power-flow study 2156:Electrical fault 2100: 2093: 2086: 2077: 2072: 2053: 2025: 2019: 2013: 2007: 2001: 1995: 1989: 1983: 1977: 1976: 1964: 1955: 1954: 1942: 1936: 1930: 1924: 1918: 1912: 1906: 1900: 1894: 1885: 1879: 1873: 1867: 1861: 1860: 1848: 1842: 1836: 1827: 1826: 1814: 1808: 1807: 1795: 1789: 1788: 1776: 1770: 1769: 1757: 1744: 1743: 1731: 1716: 1715: 1703: 1692: 1686: 1677: 1671: 1665: 1659: 1653: 1647: 1641: 1635: 1629: 1628: 1616: 1610: 1609: 1597: 1591: 1585: 1579: 1578: 1566: 1555: 1549: 1543: 1537: 1531: 1525: 1519: 1513: 1507: 1501: 1495: 1489: 1483: 1477: 1468: 1462: 1456: 1438: 1432: 1415: 1409: 1408: 1396: 1390: 1389: 1377: 1371: 1365: 1359: 1358: 1356: 1354: 1344: 1335: 1329: 1328: 1326: 1324: 1319:. User Eagle Eye 1309: 1303: 1302: 1300: 1298: 1287: 1281: 1280: 1278: 1276: 1266: 1257: 1246: 1240: 1231: 1225: 1212: 1206: 1200: 1199: 1187: 1181: 1180: 1168: 1162: 1161: 1149: 1143: 1142: 1130: 1124: 1123: 1121: 1119: 1103: 1097: 1096: 1094: 1092: 1077: 979:air conditioners 879:circuit breakers 812:circuit breakers 701:one-line diagram 602:natural disaster 572:(DC) trains, or 518: 506: 495:Grand Coulee Dam 490: 448:traction current 320:circuit breakers 261:Converting from 84:Control building 81:Main transformer 21: 2865: 2864: 2860: 2859: 2858: 2856: 2855: 2854: 2840: 2839: 2838: 2833: 2815: 2799: 2797: 2790: 2721:Capacity factor 2709: 2707: 2700: 2680:Numerical relay 2658:Circuit breaker 2646: 2644: 2637: 2599: 2539:Load management 2509:Electrical grid 2474:Demand response 2467: 2462: 2453: 2434:Microgeneration 2386: 2301: 2249: 2240: 2236:Vehicle-to-grid 2109: 2104: 2069: 2056: 2050: 2037: 2034: 2032:Further reading 2029: 2028: 2020: 2016: 2008: 2004: 1996: 1992: 1984: 1980: 1970: 1965: 1958: 1948: 1943: 1939: 1931: 1927: 1919: 1915: 1907: 1903: 1895: 1888: 1880: 1876: 1868: 1864: 1854: 1849: 1845: 1837: 1830: 1820: 1815: 1811: 1801: 1796: 1792: 1782: 1777: 1773: 1763: 1758: 1747: 1737: 1732: 1719: 1709: 1704: 1695: 1687: 1680: 1672: 1668: 1660: 1656: 1648: 1644: 1636: 1632: 1622: 1617: 1613: 1603: 1598: 1594: 1586: 1582: 1572: 1567: 1558: 1550: 1546: 1538: 1534: 1526: 1522: 1514: 1510: 1502: 1498: 1490: 1486: 1478: 1471: 1463: 1459: 1439: 1435: 1416: 1412: 1402: 1397: 1393: 1383: 1378: 1374: 1366: 1362: 1352: 1350: 1342: 1337: 1336: 1332: 1322: 1320: 1311: 1310: 1306: 1296: 1294: 1289: 1288: 1284: 1274: 1272: 1264: 1259: 1258: 1249: 1241: 1234: 1226: 1215: 1211:, pp. 7 8. 1207: 1203: 1193: 1188: 1184: 1174: 1169: 1165: 1155: 1150: 1146: 1136: 1131: 1127: 1117: 1115: 1105: 1104: 1100: 1090: 1088: 1079: 1078: 1074: 1069: 1033:microwave radio 1024: 1018: 1009: 996: 987: 955:inductive loads 948: 917: 913: 909: 905: 875: 808: 790:galvanized iron 774: 735:surge arrestors 708:circuit breaker 689: 687:Design diagrams 661: 622:Adélard-Godbout 614: 586: 562: 556: 522: 519: 510: 507: 498: 491: 465:HVDC Inga–Shaba 460: 440: 426:in Germany and 392: 344: 289:voltage control 276: 249:Interconnection 207: 191: 93: 72:Circuit breaker 53: 35: 28: 23: 22: 15: 12: 11: 5: 2863: 2861: 2853: 2852: 2842: 2841: 2835: 2834: 2832: 2831: 2820: 2817: 2816: 2814: 2813: 2808: 2802: 2800: 2796:Statistics and 2795: 2792: 2791: 2789: 2788: 2783: 2778: 2773: 2768: 2763: 2758: 2753: 2748: 2746:Feed-in tariff 2743: 2738: 2733: 2728: 2723: 2718: 2712: 2710: 2705: 2702: 2701: 2699: 2698: 2692: 2687: 2682: 2677: 2672: 2671: 2670: 2665: 2655: 2649: 2647: 2642: 2639: 2638: 2636: 2635: 2634: 2633: 2623: 2618: 2613: 2607: 2605: 2601: 2600: 2598: 2597: 2592: 2587: 2581: 2576: 2571: 2566: 2561: 2556: 2551: 2546: 2541: 2536: 2534:Interconnector 2531: 2526: 2521: 2516: 2511: 2506: 2501: 2496: 2491: 2486: 2484:Dynamic demand 2481: 2476: 2470: 2468: 2458: 2455: 2454: 2452: 2451: 2446: 2441: 2436: 2431: 2426: 2421: 2416: 2414:Combined cycle 2411: 2406: 2400: 2398: 2392: 2391: 2388: 2387: 2385: 2384: 2379: 2374: 2369: 2368: 2367: 2362: 2357: 2352: 2347: 2337: 2332: 2327: 2322: 2317: 2311: 2309: 2303: 2302: 2300: 2299: 2294: 2293: 2292: 2287: 2282: 2277: 2266: 2264: 2255: 2251: 2250: 2243: 2241: 2239: 2238: 2233: 2228: 2223: 2218: 2213: 2208: 2203: 2198: 2193: 2191:Load-following 2188: 2183: 2178: 2173: 2168: 2163: 2158: 2153: 2148: 2146:Electric power 2143: 2138: 2133: 2128: 2123: 2117: 2115: 2111: 2110: 2105: 2103: 2102: 2095: 2088: 2080: 2074: 2073: 2067: 2054: 2048: 2033: 2030: 2027: 2026: 2014: 2002: 1990: 1978: 1969:, p. 322. 1956: 1947:, p. 321. 1937: 1925: 1913: 1901: 1886: 1874: 1862: 1853:, p. 329. 1843: 1828: 1819:, p. 368. 1809: 1800:, p. 361. 1790: 1781:, p. 365. 1771: 1762:, p. 363. 1745: 1717: 1693: 1678: 1666: 1654: 1642: 1630: 1611: 1592: 1580: 1571:, p. 313. 1556: 1544: 1532: 1520: 1508: 1496: 1484: 1469: 1457: 1433: 1410: 1401:, p. 422. 1391: 1382:, p. 375. 1372: 1360: 1330: 1304: 1282: 1247: 1232: 1213: 1201: 1192:, p. 342. 1182: 1173:, p. 341. 1163: 1154:, p. 335. 1144: 1135:, p. 334. 1125: 1098: 1071: 1070: 1068: 1065: 1045:microprocessor 1020:Main article: 1017: 1014: 1008: 1005: 995: 992: 986: 983: 947: 944: 936: 935: 931: 925: 919: 915: 911: 907: 903: 896: 874: 871: 816:short circuits 807: 804: 773: 770: 741:) is minimal. 725:and switching 688: 685: 660: 657: 624:substation in 613: 610: 585: 582: 570:direct current 558:Main article: 555: 552: 547: 546: 539: 524: 523: 520: 513: 511: 508: 501: 499: 493:Switchyard at 492: 485: 459: 456: 439: 436: 391: 388: 371:distribution. 343: 340: 275: 272: 271: 270: 267:direct current 259: 252: 246: 241:for efficient 206: 203: 190: 187: 92: 91: 88: 87:Security fence 85: 82: 79: 76: 73: 70: 67: 64: 63:Overhead lines 61: 58: 54: 52: 51: 48: 44: 26: 24: 14: 13: 10: 9: 6: 4: 3: 2: 2862: 2851: 2848: 2847: 2845: 2830: 2822: 2821: 2818: 2812: 2809: 2807: 2804: 2803: 2801: 2793: 2787: 2784: 2782: 2779: 2777: 2774: 2772: 2769: 2767: 2766:Pigouvian tax 2764: 2762: 2759: 2757: 2754: 2752: 2749: 2747: 2744: 2742: 2739: 2737: 2734: 2732: 2729: 2727: 2724: 2722: 2719: 2717: 2714: 2713: 2711: 2703: 2696: 2693: 2691: 2688: 2686: 2683: 2681: 2678: 2676: 2673: 2669: 2666: 2664: 2663:Earth-leakage 2661: 2660: 2659: 2656: 2654: 2651: 2650: 2648: 2640: 2632: 2629: 2628: 2627: 2624: 2622: 2619: 2617: 2614: 2612: 2609: 2608: 2606: 2604:Failure modes 2602: 2596: 2593: 2591: 2588: 2585: 2582: 2580: 2577: 2575: 2572: 2570: 2567: 2565: 2562: 2560: 2557: 2555: 2554:Power station 2552: 2550: 2547: 2545: 2542: 2540: 2537: 2535: 2532: 2530: 2527: 2525: 2522: 2520: 2517: 2515: 2512: 2510: 2507: 2505: 2502: 2500: 2497: 2495: 2492: 2490: 2487: 2485: 2482: 2480: 2477: 2475: 2472: 2471: 2469: 2466: 2461: 2456: 2450: 2447: 2445: 2442: 2440: 2439:Rankine cycle 2437: 2435: 2432: 2430: 2427: 2425: 2422: 2420: 2419:Cooling tower 2417: 2415: 2412: 2410: 2407: 2405: 2402: 2401: 2399: 2397: 2393: 2383: 2380: 2378: 2375: 2373: 2370: 2366: 2363: 2361: 2358: 2356: 2353: 2351: 2348: 2346: 2343: 2342: 2341: 2338: 2336: 2333: 2331: 2328: 2326: 2323: 2321: 2318: 2316: 2313: 2312: 2310: 2308: 2304: 2298: 2295: 2291: 2288: 2286: 2283: 2281: 2278: 2276: 2273: 2272: 2271: 2268: 2267: 2265: 2263: 2262:Non-renewable 2259: 2256: 2252: 2247: 2237: 2234: 2232: 2229: 2227: 2224: 2222: 2219: 2217: 2214: 2212: 2209: 2207: 2204: 2202: 2199: 2197: 2194: 2192: 2189: 2187: 2184: 2182: 2181:Grid strength 2179: 2177: 2174: 2172: 2169: 2167: 2164: 2162: 2159: 2157: 2154: 2152: 2149: 2147: 2144: 2142: 2139: 2137: 2136:Demand factor 2134: 2132: 2129: 2127: 2124: 2122: 2119: 2118: 2116: 2112: 2108: 2101: 2096: 2094: 2089: 2087: 2082: 2081: 2078: 2070: 2064: 2060: 2055: 2051: 2045: 2041: 2036: 2035: 2031: 2024:, p. 89. 2023: 2018: 2015: 2012:, p. 88. 2011: 2006: 2003: 2000:, p. 63. 1999: 1994: 1991: 1988:, p. 62. 1987: 1982: 1979: 1974: 1968: 1963: 1961: 1957: 1952: 1946: 1941: 1938: 1935:, p. 77. 1934: 1929: 1926: 1922: 1917: 1914: 1911:, p. 76. 1910: 1905: 1902: 1899:, p. 83. 1898: 1893: 1891: 1887: 1884:, p. 74. 1883: 1878: 1875: 1872:, p. 71. 1871: 1866: 1863: 1858: 1852: 1847: 1844: 1841:, p. 72. 1840: 1835: 1833: 1829: 1824: 1818: 1817:Glaubitz 2018 1813: 1810: 1805: 1799: 1798:Glaubitz 2018 1794: 1791: 1786: 1780: 1779:Glaubitz 2018 1775: 1772: 1767: 1761: 1760:Glaubitz 2018 1756: 1754: 1752: 1750: 1746: 1741: 1736:, p. 13. 1735: 1730: 1728: 1726: 1724: 1722: 1718: 1713: 1708:, p. 12. 1707: 1702: 1700: 1698: 1694: 1691:, p. 70. 1690: 1685: 1683: 1679: 1676:, p. 69. 1675: 1670: 1667: 1664:, p. 81. 1663: 1658: 1655: 1652:, p. 65. 1651: 1646: 1643: 1640:, p. 64. 1639: 1634: 1631: 1626: 1620: 1615: 1612: 1607: 1601: 1596: 1593: 1590:, p. 56. 1589: 1584: 1581: 1576: 1570: 1565: 1563: 1561: 1557: 1553: 1548: 1545: 1542:, p. 54. 1541: 1536: 1533: 1530:, p. 51. 1529: 1524: 1521: 1517: 1512: 1509: 1505: 1500: 1497: 1493: 1488: 1485: 1482:, p. 42. 1481: 1476: 1474: 1470: 1467:, p. 41. 1466: 1461: 1458: 1455: 1451: 1450:0-07-020974-X 1447: 1443: 1437: 1434: 1430: 1426: 1425: 1420: 1414: 1411: 1406: 1400: 1395: 1392: 1387: 1381: 1376: 1373: 1370:, p. 68. 1369: 1364: 1361: 1348: 1341: 1334: 1331: 1318: 1314: 1308: 1305: 1293: 1286: 1283: 1270: 1263: 1256: 1254: 1252: 1248: 1245:, p. 54. 1244: 1239: 1237: 1233: 1229: 1224: 1222: 1220: 1218: 1214: 1210: 1205: 1202: 1197: 1191: 1186: 1183: 1178: 1172: 1167: 1164: 1159: 1153: 1148: 1145: 1140: 1134: 1129: 1126: 1114:. Los Angeles 1113: 1109: 1102: 1099: 1086: 1082: 1076: 1073: 1066: 1064: 1062: 1058: 1054: 1050: 1046: 1042: 1038: 1034: 1030: 1023: 1015: 1013: 1006: 1004: 1000: 993: 991: 985:Control rooms 984: 982: 980: 976: 972: 971:wind turbines 968: 964: 960: 959:reactive load 956: 952: 945: 943: 940: 934:construction. 932: 929: 926: 923: 920: 901: 897: 894: 889: 888: 887: 885: 880: 877:High-voltage 872: 870: 867: 862: 860: 854: 852: 847: 843: 841: 837: 833: 829: 825: 821: 817: 813: 805: 803: 800: 796: 791: 787: 782: 780: 771: 765: 761: 757: 755: 751: 747: 742: 740: 736: 732: 728: 724: 720: 715: 713: 709: 704: 702: 693: 686: 684: 682: 678: 673: 669: 667: 658: 656: 653: 646: 639: 634: 627: 623: 618: 611: 609: 607: 603: 599: 595: 591: 583: 581: 579: 575: 571: 567: 561: 553: 551: 544: 540: 537: 533: 532: 531: 529: 517: 512: 505: 500: 496: 489: 484: 482: 480: 475: 473: 472:power station 468: 466: 457: 455: 453: 449: 445: 437: 435: 433: 429: 425: 420: 418: 413: 409: 408:wind turbines 405: 401: 397: 389: 387: 383: 381: 376: 372: 369: 361: 356: 348: 341: 339: 337: 333: 329: 325: 321: 317: 308: 304: 302: 298: 294: 290: 286: 281: 273: 268: 264: 260: 257: 253: 250: 247: 244: 240: 236: 235: 234: 227: 220: 216: 211: 204: 202: 200: 196: 188: 182: 178: 176: 175:power station 172: 168: 163: 161: 156: 153: 148: 144: 140: 136: 132: 124: 119: 112: 108: 104: 99: 89: 86: 83: 80: 77: 74: 71: 68: 65: 62: 59: 56: 55: 49: 46: 45: 43: 39: 33: 19: 2761:Net metering 2708:and policies 2626:Power outage 2595:Utility pole 2559:Pumped hydro 2465:distribution 2460:Transmission 2409:Cogeneration 2211:Power factor 2058: 2039: 2017: 2005: 1993: 1981: 1940: 1928: 1916: 1904: 1877: 1865: 1846: 1812: 1793: 1774: 1669: 1657: 1645: 1633: 1614: 1595: 1583: 1547: 1535: 1523: 1511: 1499: 1487: 1460: 1453: 1441: 1436: 1429:Utility Week 1428: 1422: 1413: 1394: 1375: 1363: 1351:. Retrieved 1346: 1333: 1321:. Retrieved 1316: 1307: 1295:. Retrieved 1285: 1273:. Retrieved 1268: 1230:, p. 7. 1204: 1185: 1166: 1147: 1128: 1116:. Retrieved 1112:The Guardian 1111: 1101: 1089:. Retrieved 1084: 1075: 1025: 1010: 1001: 997: 994:Transformers 988: 975:voltage drop 949: 937: 876: 865: 863: 855: 848: 844: 809: 783: 775: 758: 743: 716: 705: 698: 674: 670: 662: 654: 651: 626:Old Montreal 594:semi-trailer 589: 587: 563: 548: 525: 476: 469: 461: 441: 421: 393: 384: 377: 373: 367: 365: 313: 285:transformers 279: 277: 256:distribution 243:transmission 232: 192: 189:Construction 166: 164: 157: 152:transformers 143:distribution 139:transmission 130: 128: 41: 2756:Load factor 2611:Black start 2579:Transformer 2280:Natural gas 2231:Variability 2206:Peak demand 2196:Merit order 2126:Backfeeding 2059:Substations 1734:Twomey 2018 1706:Twomey 2018 1452:Chapter 17 1297:14 December 1118:10 December 1037:fiber optic 1007:Maintenance 922:Mineral oil 828:power plant 754:three-phase 60:Ground wire 2798:production 2643:Protective 2574:Super grid 2569:Smart grid 2396:Generation 2330:Geothermal 2221:Repowering 2022:Blume 2016 2010:Blume 2016 1921:Blume 2016 1897:Blume 2016 1882:Blume 2016 1870:Blume 2016 1839:Blume 2016 1689:Blume 2016 1674:Blume 2016 1662:Blume 2016 1353:11 October 1323:4 February 1275:4 February 1243:Blume 2016 1190:Okada 2018 1171:Okada 2018 1152:Okada 2018 1133:Okada 2018 1091:4 February 1067:References 1061:smart grid 1016:Automation 946:Capacitors 873:Switchgear 832:capacitors 806:Components 731:insulation 729:can cause 566:rectifiers 424:Brauweiler 318:plus some 195:contractor 167:substation 135:generation 131:substation 2706:Economics 2429:Micro CHP 2307:Renewable 2290:Petroleum 2285:Oil shale 2171:Grid code 2131:Base load 1998:Finn 2019 1986:Finn 2019 1933:Finn 2019 1909:Finn 2019 1650:Finn 2019 1638:Finn 2019 1588:Finn 2019 1552:Finn 2019 1540:Finn 2019 1528:Finn 2019 1516:Finn 2019 1504:Finn 2019 1492:Finn 2019 1480:Finn 2019 1465:Finn 2019 1368:Finn 2019 1228:Finn 2019 1209:Finn 2019 1053:IEC 61850 951:Capacitor 939:Reclosers 884:power arc 799:marconite 795:bentonite 786:grounding 779:flashover 723:lightning 479:switching 412:inverters 400:wind farm 221:, Finland 165:The word 107:Australia 103:Melbourne 2844:Category 2829:Category 2616:Brownout 2404:AC power 2114:Concepts 1317:metacafe 840:reactors 666:drainage 554:Railways 265:(AC) to 2645:devices 2355:Thermal 2350:Osmotic 2345:Current 2325:Biomass 2315:Biofuel 2297:Nuclear 2254:Sources 851:busbars 750:busbars 739:outages 432:lignite 360:Toronto 147:voltage 2340:Marine 2320:Biogas 2065:  2046:  1448:  1085:Jemena 1057:Modbus 928:Vacuum 838:, and 772:Safety 727:surges 640:river. 612:Design 428:Hradec 328:relays 215:Kaanaa 141:, and 2697:(GFI) 2586:(TSO) 2372:Solar 2360:Tidal 2335:Hydro 1343:(PDF) 1265:(PDF) 969:, or 824:fuses 746:buses 717:With 677:lease 598:truck 543:tower 528:fault 332:SCADA 205:Types 160:SCADA 2463:and 2382:Wind 2365:Wave 2275:Coal 2063:ISBN 2044:ISBN 1973:help 1951:help 1857:help 1823:help 1804:help 1785:help 1766:help 1740:help 1712:help 1625:help 1606:help 1575:help 1446:ISBN 1405:help 1386:help 1355:2017 1325:2016 1299:2013 1277:2016 1196:help 1177:help 1158:help 1139:help 1120:2022 1093:2016 1055:and 1049:DNP3 638:Bóbr 568:for 444:HVDC 330:and 269:(DC) 219:Pori 171:grid 902:(SF 822:or 797:or 606:war 604:or 536:arc 410:or 402:or 394:In 316:bus 2846:: 1959:^ 1889:^ 1831:^ 1748:^ 1720:^ 1696:^ 1681:^ 1559:^ 1472:^ 1421:, 1345:. 1315:. 1267:. 1250:^ 1235:^ 1216:^ 1110:. 1083:. 1063:. 1051:, 1035:, 1031:, 864:A 834:, 683:. 588:A 541:a 366:A 338:. 326:, 278:A 217:, 137:, 129:A 105:, 2099:e 2092:t 2085:v 2071:. 2052:. 1975:) 1953:) 1859:) 1825:) 1806:) 1787:) 1768:) 1742:) 1714:) 1627:) 1608:) 1577:) 1407:) 1388:) 1357:. 1327:. 1301:. 1279:. 1198:) 1179:) 1160:) 1141:) 1122:. 1095:. 916:6 912:6 908:6 904:6 538:, 291:/ 34:. 20:)

Index

Electric substation
Substation (disambiguation)


Melbourne
Australia
high-voltage transformer fire barriers

Warren, Minnesota
generation
transmission
distribution
voltage
transformers
SCADA
grid
power station

contractor
electrical utility

Kaanaa
Pori

electric power generation
transmission
Interconnection
distribution
alternating current
direct current

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.