Knowledge (XXG)

Islanding

Source đź“ť

254: 111:" (NDZ), the range of conditions where a real grid failure will be filtered out. For this reason, before field deployment, grid-interactive inverters are typically tested by reproducing at their output terminals specific grid conditions and evaluating the effectiveness of the anti-islanding methods in detecting island conditions. 326:
fed by the inverter. When the circuit is grid-connected, there is almost no voltage response to slight variations in inverter current; but an island will observe a change in voltage. In principle, this technique has a vanishingly small NDZ, but in practice the grid is not always an infinitely-stiff
314:
Many passive methods rely on the inherent stress of operating an island. Each device in the island comprises a much larger proportion of the total load, such that the voltage and frequency changes as devices are added or removed are likely to be much larger than in normal grid conditions. However,
444:
generally have large distortions â€” as much as 5%. When the grid disconnects, the local circuit then exhibits inverter-induced distortion. Modern inverters attempt to minimize harmonic distortion, in some cases to unmeasurable limits, but in principle it is straightforward to design one which
412:
on the island suddenly decreases, and inverter's current no longer produces the proper waveform. By the time the waveform is completed and returns to zero, the signal will be out of phase. However, many common events, like motors starting, also cause phase jumps as new impedances are added to the
551:
if there is unexpected voltage on a purportedly-isolated line. A UK-based study concluded that "The risk of electric shock associated with islanding of PV systems under worst-case PV penetration scenarios to both network operators and customers is typically <10 per year." Likewise, damage to
310:
Automatically detecting an island is the subject of considerable research. These can be performed passively, looking for transient events on the grid; or actively, by creating small instances of those transient events that will be negligible on a large grid but detectable on a small one. Active
559:
are commonly used to divide up the grid into smaller sections that will automatically, and quickly, re-energize the branch as soon as the fault condition (a tree branch on lines for instance) clears. There is some concern that the reclosers may not re-energize in the case of an island or that an
106:
Methods that detect islands without a large number of false positives constitute the subject of considerable research. Each method has some threshold that needs to be crossed before a condition is considered to be a signal of grid interruption, which leads to a
606: 493:. A 2004 Canadian report concluded that "Anti-islanding technology for inverter based DG systems is much better developed, and published risk assessments suggest that the current technology and standards provide adequate protection." 338:
matching standard grid power. However, many devices, like televisions, deliberately synchronize to the grid frequency. Motors, in particular, may be able to stabilize circuit frequency close to the grid standard as they "wind down".
1158:"Negative-Sequence Current Injection for Fast Islanding Detection of a Distributed Resource Unit", Houshang Karimi, Amirnaser Yazdani, and Reza Iravani, IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 1, JANUARY 2008. 614: 560:
intervening loss of synchrony might damage distributed generators on the island. However, it is neither clear that reclosers are still useful in modern utility practice nor that breaker-reclosers must act on all
472:. A 1999 test in the Netherlands was unable to find distributed-generation islands 60 seconds after grid collapse. Moreover, moments when distributed generation only matched distributed loads occurred at a rate 416:
A more effective technique inverts the islanding phase shift: the inverter is designed to produce output slightly mis-aligned with the grid, with the expectation that the grid will overwhelm the signal. The
188:, and is typically a last resort applied when the grid is known to be unstable but has not yet collapsed. In particular, islanding improves resilience to threats with known time but not location, such as 987:
Balaguer, Irvin J.; Qin Lei; Yang, Shuitao; Supatti, Uthane; Peng, Fang Zheng (Jan 2011) . "Control for grid-connected and intentional islanding operations of distributed power generation".
440:(THD) sources that match an inverter. Even noisy sources, like motors, do not effect measurable distortion on a grid-connected circuit, as the latter has essentially infinite filtration capacity. 1534:
accidental islanding of a generator during transformer maintenance causes severe overfrequency on the island and requires manual control of the turbines to reintegrate with the larger grid
581: 1278: 123:
in each fragment to supply that fragment's loads. In practice, balancing generation and load in each fragment is difficult, and often the formation of islands requires temporarily
49:
cooling systems that are typically powered from the general grid. The coolant loops typically lie on a separate circuit that can also operate off of reactor power or emergency
476:
10 yr, and that the chance that the grid would disconnect at that point in time was even less, so that the "probability of encountering an islanding [
1297: 517:
close to standard, and nonstandard currents can damage customer equipment. Depending on the circuit configuration, the utility may be liable for the damage.
216:
systems are too small to power all appliances in a home simultaneously, it is possible for them to manage critical household power needs through traditional
1045:
Scala, Antonio; Lucentini, Pier Giorgio De Santis; Caldarelli, Guido; D'Agostino, Gregorio (1 June 2016) . "Cascades in interdependent flow networks".
1529: 1018:
Li, Juan; Liu, Chen-Ching; Schneider, Kevin P. (Dec 2010). "Controlled partitioning of a power network considering real and reactive power balance".
721:
Caldognetto, T.; Dalla Santa, L.; Magnone, P.; Mattavelli, P. (2017). "Power Electronics Based Active Load for Unintentional Islanding Testbenches".
264: 544: 1488: 457:
or other distributed generation systems, on the grounds that they may create uncontrolled grid islands. In Ontario, a 2009 modification to the
656: 1275: 75:
Unintentional islanding is a dangerous condition that may induce severe stress on the generator, as the generator must match any changes in
1565: 155: 1466:
H. Karimi, A. Yazdani, and R. Iravani, "Negative-Sequence Current Injection for Fast Islanding Detection of a Distributed Resource Unit",
1491:, UL 1741: Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources 408:
output, varying the current to produce the proper voltage waveform given the previous cycle's load. When the main grid disconnects, the
316: 421:
then becomes unstable when the grid signal is missing; the system drifts away from the design frequency; and the inverter shuts down.
297: 99:
that are designed to supply power to the grid are generally required to have some sort of automatic anti-islanding circuitry, which
1460: 871: 358: 1522: 34: 468:
The issue can be hotly political, in part because distributed generation proponents believe the islanding concern is largely
209: 140: 1503: 221: 212:, there was a rise in interest in the possibility of operating a house's electrical grid as an island. While typical 828:"Constrained spectral clustering-based methodology for intentional controlled islanding of large-scale power systems" 461:
induced many rural customers to establish small (10 kW) systems under the "capacity exempt" microFIT. However,
279: 165:
However, islanding localizes any failures to the containing island, preventing failures from spreading. In general,
524: 441: 159: 136: 68:, the microgrid controller disconnects the local circuit from the grid on a dedicated switch and forces any online 23: 1294: 437: 350:
and shut down. This practice, however, relies on the expensive widespread provision of high-impedance devices.
954: 756:
Mureddu, Mario; Caldarelli, Guido; Damiano, Alfonso; Scala, Antonio; Meyer-Ortmanns, Hildegard (2016-10-07).
1570: 536: 378: 132: 926:
Yang, Bo; Vittal, Vijay; Heydt, Gerald T. (30 Oct 2006). "Slow coherency based controlled islanding".
87:. Unlike unpowered wires, islands require special techniques to reconnect to the larger grid, because the 1391: 1313: 401: 347: 237: 217: 213: 166: 46: 38: 486: 69: 826:
Quirós-Tortós, Jairo; Sánchez-García, Rubén; Brodzki, Jacek; Bialek, Janusz; Terzija, Vladimir (2015).
527:. Procedures to prevent these outcomes may delay restoration of electric service to dropped customers. 1064: 883: 769: 342:
At the utility level, protective relays designed to isolate a portion of the grid can also switch in
323: 57: 1396: 1430:
Evaluation of Islanding Detection Methods for Utility-Interactive Inverters in Photovoltaic Systems
540: 425: 181: 147: 88: 42: 1388:
Risk analysis of islanding of photovoltaic power systems within low voltage distribution networks
1095: 1054: 738: 662: 454: 496:
Utilities generally argue that the distributed generators might effect the following problems:
1461:"Probability of Islanding in Utility Network due to Grid Connected Photovoltaic Power Systems" 849: 803: 785: 652: 523:
Reclosing distribution circuits onto an active island may damage equipment or be inhibited by
429: 418: 397: 362: 80: 1094:. 2020 IEEE Power & Energy Society Innovative Smart Grid Technologies Conference (ISGT). 322:
The active analogue of voltage and frequency shift detection attempts to measure the overall
1434: 1105: 1072: 1027: 996: 969: 935: 899: 891: 839: 793: 777: 730: 644: 354: 225: 189: 120: 84: 50: 27: 1301: 1282: 510: 473: 197: 193: 173:, such that fragmenting a network increases the probability of blackouts, but reduces the 76: 1510: 1448:
An Assessment of Distributed Generation Islanding Detection Methods and Issues for Canada
1068: 887: 773: 758:"Islanding the power grid on the transmission level: less connections for more security" 41:. If one island collapses, it will not take neighboring islands with it. For example, 798: 757: 532: 458: 374: 343: 335: 328: 174: 170: 128: 96: 445:
introduces a controlled amount of distortion to actively search for island formation.
1559: 1485:, IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems 607:"Centrale nuclĂ©aire de Fessenheim : Mise Ă  l'arrĂŞt de l'unitĂ© de production n°2" 561: 514: 233: 229: 100: 742: 666: 1452: 1109: 1004: 909: 548: 409: 185: 65: 1092:
Proactive islanding of the power grid to mitigate high-impact low-frequency events
311:
methods may be performed by local generators or "upstream" at the utility level.
119:
Intentional islanding divides an electrical network into fragments with adequate
1076: 895: 872:"Optimal intentional islanding to enhance the robustness of power grid networks" 433: 389: 382: 331:, especially if multiple inverters attempt to measure impedance simultaneously. 319:, and voltage and frequency shifts are generally used along with other signals. 973: 939: 844: 827: 543:
require explicit checks to ensure that a wire is dead before worker contact.
490: 469: 405: 1031: 1000: 853: 789: 734: 648: 636: 955:"Micro-grid autonomous operation during and subsequent to islanding process" 582:"Îlotage provoqué des deux réacteurs à la centrale nucléaire de Saint-Alban" 462: 393: 124: 61: 807: 635:
Saleh, M.; Esa, Y.; Mhandi, Y.; Brandauer, W.; Mohamed, A. (October 2016).
552:
end-user devices is largely inhibited by modern island-detection systems.
135:
during fault-induced island formation, and any inverters must switch from
556: 503:
If an island forms, repair crews may be faced with unexpected live wires.
346:
components, such that an islanded distributed generator will necessarily
92: 151: 904: 781: 1545: 1428: 1446: 870:
Pahwa, S.; Youssef, M.; Schumm, P.; Scoglio, C.; Schulz, N. (2013).
465:
then refused to connect the systems to the grid after construction.
1482: 1438: 1276:"Technical Interconnection Requirements for Distributed Generation" 1100: 1059: 683: 103:
the panels rather than continue to power the unintentional island.
16:
When distributed generation continues after electrical grid is down
424:
A very secure islanding detection method searches for distinctive
953:
Katiraei, F.; Iravani, M. R.; Lehn, P. W. (Jan 2005) .
688:
IEEE Standards Association Working Group Site & Liaison Index
555:
It is, generally, the last problem that most concerns utilities.
334:
Unlike the shifts, a random circuit is highly unlikely to have a
1504:"First-Ever Islanding Application of an Energy Storage System" 478: 357:. For example, utilities can send a shut-down signal through 247: 535:. For example, normal linework constantly risks exposure to 271: 1295:"California Electric Rule 21 Supplemental Review Guideline" 1090:
Biswas, Shuchismita; Bernabeu, Emanuel; Picarelli, David.
1550: 232:
measure the island power frequency and perform automatic
637:"Design and implementation of CCNY DC microgrid testbed" 509:
Distributed generators may not be able to maintain grid
158:
exist, but finding the exactly optimal divisions can be
275: 1433:, DOE Office of Scientific and Technical Information, 641:
2016 IEEE Industry Applications Society Annual Meeting
485:
Unintentional islanding risk is primarily the case of
127:. Synchronous generators may not deliver sufficient 353:
Alternatively, anti-islanding circuitry can rely on
26:
into individual disconnected regions with their own
1445:Xu, Wilsun; Mauch, Konrad; Martel, Sylvain (2004). 22:is the intentional or unintentional division of an 678: 676: 83:, unintentional island can also present a risk of 404:. Between those events, the inverter produces a 373:Certain passive methods are uniquely viable with 453:Utilities have refused to allow installation of 832:IET Generation, Transmission & Distribution 56:Grid designs that lend themselves to islanding 33:Intentional islanding is often performed as a 1410: 1374: 1362: 1338: 1215: 1179: 531:The first two claims are disputed within the 315:the difference is not so large as to prevent 8: 388:For example, inverters typically generate a 1530:North American Electric Reliability Council 989:IEEE Transactions on Industrial Electronics 224:between the generator and large loads like 723:IEEE Transactions on Industry Applications 154:criterion exists to implement islanding. 1470:, vol. 23, no. 1, January 2008. 1395: 1350: 1314:"Ontario Hydro pulls plug on solar plans" 1263: 1251: 1239: 1227: 1203: 1191: 1167: 1146: 1134: 1122: 1099: 1058: 903: 843: 797: 708: 298:Learn how and when to remove this message 545:Supervisory Control and Data Acquisition 270:Relevant discussion may be found on the 79:alone. If not properly communicated to 1509:Mozina, Charles J. (Summer 2008). 613:(in French). 2018-07-14. Archived from 572: 396:generally match the grid signal with a 1511:"The Impact of Distributed Generation" 282:to additional sources at this section. 921: 919: 7: 865: 863: 821: 819: 817: 1451:. CANMET Energy Center – via 1427:Bower, Ward; Ropp, Michael (2002), 962:IEEE Transactions on Power Delivery 177:of unsatisfied electricity demand. 928:IEEE Transactions on Power Systems 449:Distributed generation controversy 263:relies largely or entirely upon a 14: 359:power line carrier communications 196:on electrical infrastructure, or 1468:IEEE Trans. on Power Electronics 1020:IEEE Transactions on Smart Grids 436:. There are generally no other 252: 1110:10.1109/ISGT45199.2020.9087788 580:AutoritĂ© de sĂ»retĂ© nuclĂ©aire. 547:(SCADA) systems can be set to 525:out-of-phase protection relays 210:2019 California power shutoffs 156:Polynomial-time approximations 1: 1517:. No. 5. pp. 20–25. 1551:Sandia National Laboratories 1546:Distributed Energy Resources 520:Controlled grid reconnection 369:Inverter-specific techniques 60:are commonly referred to as 1566:Electric power distribution 1411:Xu, Mauch & Martel 2004 1375:Xu, Mauch & Martel 2004 1363:Xu, Mauch & Martel 2004 1339:Xu, Mauch & Martel 2004 1320:(via QMI), 14 February 2011 1216:Xu, Mauch & Martel 2004 1180:Xu, Mauch & Martel 2004 1077:10.1016/j.physd.2015.10.010 896:10.1016/j.physa.2013.03.029 882:(17). Elsevier: 3741–3754. 1587: 482:] is virtually zero". 160:computationally infeasible 1528:(Report). Princeton, NJ: 1489:UL 1741 Table of Contents 974:10.1109/TPWRD.2004.835051 940:10.1109/TPWRS.2006.881126 845:10.1049/iet-gtd.2014.0228 438:total harmonic distortion 72:to power the local load. 24:interconnected power grid 1523:1996 System Disturbances 1032:10.1109/TSG.2010.2082577 1001:10.1109/TIE.2010.2049709 735:10.1109/TIA.2017.2694384 649:10.1109/IAS.2016.7731870 379:inverter-based resources 336:characteristic frequency 220:. Modules installed in 1532:. Aug 2002. p. 60. 442:Switched-mode inverters 58:near the customer level 53:if the grid collapses. 487:synchronous generators 430:nonlinear interactions 236:as the inverter nears 218:load-frequency control 214:distributed generation 180:Islanding reduces the 95:. For these reasons, 70:distributed generators 1351:Bower & Ropp 2002 1318:The London Free Press 1264:Bower & Ropp 2002 1252:Bower & Ropp 2002 1242:, pp. 28–29, 34. 1240:Bower & Ropp 2002 1228:Bower & Ropp 2002 1204:Bower & Ropp 2002 1192:Bower & Ropp 2002 1168:Bower & Ropp 2002 1147:Bower & Ropp 2002 1135:Bower & Ropp 2002 1123:Bower & Ropp 2002 709:Bower & Ropp 2002 426:2nd and 3rd harmonics 402:tracks zero-crossings 317:identification errors 115:Intentional islanding 684:"IEEE 1547.4 - 2011" 432:inside the inverter 276:improve this article 169:statistics follow a 43:nuclear power plants 1483:IEEE 1547 Standards 1069:2016PhyD..323...35S 1053:. Elsevier: 35–39. 976:. TPWRD-00103-2003. 888:2013PhyA..392.3741P 774:2016NatSR...634797M 541:standard procedures 355:out-of-band signals 182:economic efficiency 89:alternating current 1300:2010-10-19 at the 1281:2014-02-07 at the 762:Scientific Reports 131:to prevent severe 109:non-detection zone 91:they carry is not 81:power line workers 39:cascading blackout 1329:Verhoeven, pg. 46 1285:, Hydro One, 2010 1230:, pp. 20–21. 1218:, pp. 13–14. 1194:, pp. 37–38. 1182:, pp. 12–13. 1137:, pp. 17–19. 782:10.1038/srep34797 658:978-1-4799-8397-1 419:phase-locked loop 398:phase locked loop 392:when islanding. 308: 307: 300: 244:Detection methods 190:terrorist attacks 184:of the wholesale 51:diesel generators 1578: 1533: 1527: 1518: 1456: 1441: 1414: 1408: 1402: 1401: 1399: 1384: 1378: 1377:, pp. 9–10. 1372: 1366: 1360: 1354: 1348: 1342: 1336: 1330: 1327: 1321: 1310: 1304: 1292: 1286: 1273: 1267: 1261: 1255: 1249: 1243: 1237: 1231: 1225: 1219: 1213: 1207: 1201: 1195: 1189: 1183: 1177: 1171: 1165: 1159: 1156: 1150: 1144: 1138: 1132: 1126: 1120: 1114: 1113: 1103: 1087: 1081: 1080: 1062: 1042: 1036: 1035: 1015: 1009: 1008: 984: 978: 977: 959: 950: 944: 943: 934:(4): 1840–1847. 923: 914: 913: 907: 867: 858: 857: 847: 823: 812: 811: 801: 753: 747: 746: 729:(4): 3831–3839. 718: 712: 706: 700: 699: 697: 695: 680: 671: 670: 643:. pp. 1–7. 632: 626: 625: 623: 622: 603: 597: 596: 594: 593: 577: 303: 296: 292: 289: 283: 256: 255: 248: 226:air conditioners 194:military strikes 141:constant-voltage 137:constant-current 121:power generation 85:electrical shock 35:defence in depth 28:power generation 1586: 1585: 1581: 1580: 1579: 1577: 1576: 1575: 1556: 1555: 1542: 1537: 1525: 1521: 1508: 1499: 1497:Further reading 1494: 1478: 1473: 1459:Bas Verhoeven, 1444: 1426: 1422: 1417: 1409: 1405: 1397:10.1.1.114.2752 1386: 1385: 1381: 1373: 1369: 1361: 1357: 1349: 1345: 1337: 1333: 1328: 1324: 1312:Jonathan Sher, 1311: 1307: 1302:Wayback Machine 1293: 1289: 1283:Wayback Machine 1274: 1270: 1262: 1258: 1250: 1246: 1238: 1234: 1226: 1222: 1214: 1210: 1202: 1198: 1190: 1186: 1178: 1174: 1166: 1162: 1157: 1153: 1145: 1141: 1133: 1129: 1121: 1117: 1089: 1088: 1084: 1044: 1043: 1039: 1017: 1016: 1012: 986: 985: 981: 957: 952: 951: 947: 925: 924: 917: 869: 868: 861: 825: 824: 815: 755: 754: 750: 720: 719: 715: 707: 703: 693: 691: 682: 681: 674: 659: 634: 633: 629: 620: 618: 605: 604: 600: 591: 589: 579: 578: 574: 570: 506:End-user damage 500:Safety concerns 451: 371: 304: 293: 287: 284: 278:by introducing 269: 257: 253: 246: 206: 198:extreme weather 117: 97:solar inverters 77:electrical load 47:safety-critical 17: 12: 11: 5: 1584: 1582: 1574: 1573: 1571:Electric power 1568: 1558: 1557: 1554: 1553: 1548: 1541: 1540:External links 1538: 1536: 1535: 1519: 1506: 1500: 1498: 1495: 1493: 1492: 1486: 1479: 1477: 1474: 1472: 1471: 1464: 1457: 1442: 1439:10.2172/806700 1423: 1421: 1418: 1416: 1415: 1403: 1379: 1367: 1355: 1343: 1331: 1322: 1305: 1287: 1268: 1256: 1244: 1232: 1220: 1208: 1196: 1184: 1172: 1160: 1151: 1139: 1127: 1115: 1082: 1037: 1026:(3): 261–269. 1010: 995:(1): 147–157. 979: 968:(1): 248–257. 945: 915: 859: 813: 748: 713: 701: 672: 657: 627: 598: 571: 569: 566: 533:power industry 529: 528: 521: 518: 507: 504: 501: 459:feed-in tariff 450: 447: 375:direct current 370: 367: 344:high impedance 329:voltage source 306: 305: 274:. Please help 260: 258: 251: 245: 242: 230:electric ovens 208:Following the 205: 204:Home islanding 202: 129:reactive power 116: 113: 37:to mitigate a 15: 13: 10: 9: 6: 4: 3: 2: 1583: 1572: 1569: 1567: 1564: 1563: 1561: 1552: 1549: 1547: 1544: 1543: 1539: 1531: 1524: 1520: 1516: 1512: 1507: 1505: 1502: 1501: 1496: 1490: 1487: 1484: 1481: 1480: 1475: 1469: 1465: 1462: 1458: 1454: 1450: 1449: 1443: 1440: 1436: 1432: 1431: 1425: 1424: 1419: 1413:, p. 48. 1412: 1407: 1404: 1398: 1393: 1389: 1383: 1380: 1376: 1371: 1368: 1364: 1359: 1356: 1353:, p. 13. 1352: 1347: 1344: 1341:, p. 45. 1340: 1335: 1332: 1326: 1323: 1319: 1315: 1309: 1306: 1303: 1299: 1296: 1291: 1288: 1284: 1280: 1277: 1272: 1269: 1266:, p. 26. 1265: 1260: 1257: 1254:, p. 22. 1253: 1248: 1245: 1241: 1236: 1233: 1229: 1224: 1221: 1217: 1212: 1209: 1206:, p. 40. 1205: 1200: 1197: 1193: 1188: 1185: 1181: 1176: 1173: 1170:, p. 20. 1169: 1164: 1161: 1155: 1152: 1149:, p. 24. 1148: 1143: 1140: 1136: 1131: 1128: 1124: 1119: 1116: 1111: 1107: 1102: 1097: 1093: 1086: 1083: 1078: 1074: 1070: 1066: 1061: 1056: 1052: 1048: 1041: 1038: 1033: 1029: 1025: 1021: 1014: 1011: 1006: 1002: 998: 994: 990: 983: 980: 975: 971: 967: 963: 956: 949: 946: 941: 937: 933: 929: 922: 920: 916: 911: 906: 901: 897: 893: 889: 885: 881: 877: 873: 866: 864: 860: 855: 851: 846: 841: 837: 833: 829: 822: 820: 818: 814: 809: 805: 800: 795: 791: 787: 783: 779: 775: 771: 767: 763: 759: 752: 749: 744: 740: 736: 732: 728: 724: 717: 714: 711:, p. 10. 710: 705: 702: 689: 685: 679: 677: 673: 668: 664: 660: 654: 650: 646: 642: 638: 631: 628: 617:on 2019-02-26 616: 612: 608: 602: 599: 587: 583: 576: 573: 567: 565: 563: 558: 553: 550: 546: 542: 538: 534: 526: 522: 519: 516: 512: 508: 505: 502: 499: 498: 497: 494: 492: 488: 483: 481: 480: 475: 474:comparable to 471: 466: 464: 460: 456: 448: 446: 443: 439: 435: 431: 428:generated by 427: 422: 420: 414: 411: 407: 403: 399: 395: 391: 386: 384: 380: 376: 368: 366: 364: 360: 356: 351: 349: 345: 340: 337: 332: 330: 325: 320: 318: 312: 302: 299: 291: 281: 277: 273: 267: 266: 265:single source 261:This section 259: 250: 249: 243: 241: 239: 235: 234:load shedding 231: 227: 223: 219: 215: 211: 203: 201: 199: 195: 191: 187: 183: 178: 176: 172: 168: 163: 161: 157: 153: 149: 144: 142: 138: 134: 130: 126: 125:shedding load 122: 114: 112: 110: 104: 102: 98: 94: 90: 86: 82: 78: 73: 71: 67: 63: 59: 54: 52: 48: 44: 40: 36: 31: 29: 25: 21: 1514: 1467: 1463:, KEMA, 1999 1453:Academia.edu 1447: 1429: 1420:Bibliography 1406: 1387: 1382: 1370: 1365:, p. 3. 1358: 1346: 1334: 1325: 1317: 1308: 1290: 1271: 1259: 1247: 1235: 1223: 1211: 1199: 1187: 1175: 1163: 1154: 1142: 1130: 1118: 1091: 1085: 1050: 1046: 1040: 1023: 1019: 1013: 1005:Academia.edu 1003:– via 992: 988: 982: 965: 961: 948: 931: 927: 910:Kansas State 908:– via 879: 875: 838:(1): 31–42. 835: 831: 768:(1): 34797. 765: 761: 751: 726: 722: 716: 704: 692:. Retrieved 687: 640: 630: 619:. Retrieved 615:the original 610: 601: 590:. Retrieved 585: 575: 554: 530: 495: 484: 477: 467: 452: 434:transformers 423: 415: 410:power factor 387: 383:solar panels 377:generators ( 372: 352: 341: 333: 321: 313: 309: 294: 285: 262: 207: 186:power market 179: 175:total amount 164: 145: 118: 108: 105: 74: 66:power outage 55: 32: 19: 18: 912:repository. 588:(in French) 511:frequencies 400:(PLL) that 390:phase shift 381:), such as 1560:Categories 1101:1911.04440 1060:1512.03088 905:2097/16520 621:2019-02-25 611:EDF France 592:2019-02-25 568:References 537:live wires 491:microhydro 470:pretextual 455:home solar 406:sinusoidal 288:April 2024 150:, no good 133:transients 101:shorts out 62:microgrids 1515:PAC World 1476:Standards 1392:CiteSeerX 1047:Physica D 876:Physica A 854:1751-8695 790:2045-2322 557:Reclosers 463:Hydro One 413:circuit. 394:Inverters 363:telephony 324:impedance 280:citations 272:talk page 171:power law 146:Assuming 143:control. 20:Islanding 1390:. 2002. 1298:Archived 1279:Archived 808:27713509 743:40097383 667:16464909 515:voltages 489:, as in 365:hookup. 348:overload 238:overload 200:events. 167:blackout 93:in phase 64:. In a 1065:Bibcode 884:Bibcode 799:5054509 770:Bibcode 694:3 March 152:cut set 1394:  852:  806:  796:  788:  741:  690:. IEEE 665:  655:  562:phases 539:, and 222:series 1526:(PDF) 1096:arXiv 1055:arXiv 958:(PDF) 739:S2CID 663:S2CID 549:alarm 361:or a 45:have 850:ISSN 804:PMID 786:ISSN 696:2017 653:ISBN 228:and 148:P≠NP 1435:doi 1106:doi 1073:doi 1051:323 1028:doi 997:doi 970:doi 936:doi 900:hdl 892:doi 880:392 840:doi 794:PMC 778:doi 731:doi 645:doi 586:ASN 513:or 479:sic 139:to 1562:: 1513:. 1316:, 1104:. 1071:. 1063:. 1049:. 1022:. 993:58 991:. 966:20 964:. 960:. 932:21 930:. 918:^ 898:. 890:. 878:. 874:. 862:^ 848:. 834:. 830:. 816:^ 802:. 792:. 784:. 776:. 764:. 760:. 737:. 727:53 725:. 686:. 675:^ 661:. 651:. 639:. 609:. 584:. 564:. 385:. 240:. 192:, 162:. 30:. 1455:. 1437:: 1400:. 1125:. 1112:. 1108:: 1098:: 1079:. 1075:: 1067:: 1057:: 1034:. 1030:: 1024:1 1007:. 999:: 972:: 942:. 938:: 902:: 894:: 886:: 856:. 842:: 836:9 810:. 780:: 772:: 766:6 745:. 733:: 698:. 669:. 647:: 624:. 595:. 301:) 295:( 290:) 286:( 268:. 107:"

Index

interconnected power grid
power generation
defence in depth
cascading blackout
nuclear power plants
safety-critical
diesel generators
near the customer level
microgrids
power outage
distributed generators
electrical load
power line workers
electrical shock
alternating current
in phase
solar inverters
shorts out
power generation
shedding load
reactive power
transients
constant-current
constant-voltage
P≠NP
cut set
Polynomial-time approximations
computationally infeasible
blackout
power law

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.

↑