2015 Turkey blackout

Source 📝

402: 396: 462: 206:
did not cope with running at reduced frequency, additional power was lost and resulted in a blackout of the Western part. The Eastern part suffered from hydropower oversupply (41%) that wasn't able to flow westward. The Eastern part was accelerated by ca. 1.6
235: 211:/s and culminated at 52.3 Hz. Power plants tripped due to overfrequency and the initially oversupplied Eastern part collapsed at underfrequency values less than 47.0 Hz. 344: 160:
with a surplus of power, which is then exported to the population centers in Western Turkey. At the time of the blackout, sufficiently many transmission lines and
499: 215: 446: 268: 317: 243: 152:
The Turkish electric authority regularly performs maintenance in the spring in preparation for high electricity demand during the summer. The
533: 370: 538: 492: 191:
also tripped. This was the reason that the disturbances only had effects in Turkey and did not cascade to neighbouring countries.
528: 203: 543: 523: 439: 548: 485: 180: 183:
split in half at CET 09:36:11 and separated from the Central European (CE) synchronous zone, i.e. connecting lines to
157: 282: 432: 214:
At 16:12 (CET) - ca. 6.5 hours after the blackout - the Western and Eastern part were resynchronised, while the
518: 194:
The two parts inside Turkey behaved differently. The Western part suffered from a lack generation (21%) and
41: 161: 299: 412: 195: 469: 416: 291: 290:. 53rd International Universities Power Engineering Conference. Glasgow. p. 8541901. 281:
Velay, Maxime; Vinyals, Meritxell; Besanger, Yvon; Retière, Nicolas (September 2018).
512: 218:
was already about 80% energized. At 18:30 almost 95% of the loads were served again.
199: 165: 142: 67: 318:"Explained: How 76 million people were hit by Turkey's worst blackout since 1999" 401: 303: 176: 153: 80: 295: 77: 395: 345:"Turkey's blackout caused by line maintenance, hydro production oversupply" 284:
An analysis of large-scale transmission power blackouts from 2005 to 2016
188: 461: 236:"Turkey's power outage linked to mismanagement, grid director resigns" 184: 146: 91:
Major losses in everyday life, mainly in electricity-dependent jobs
208: 164:
had been removed from service that the system was no longer in an
179:
line tripped, the remaining East-West connections failed. The
371:"Turkey's 10-Hour Blackout Shows Threat to World Power Grids" 473: 420: 127: 119: 111: 103: 95: 87: 73: 63: 55: 47: 36: 26: 369: 202:schemes did stabilize the frequency, but as some 493: 440: 269:Report on Blackout in Turkey on 31 March 2015 8: 21: 149:in the morning of Tuesday, 31 March 2015. 500: 486: 447: 433: 20: 263: 261: 468:This article about electric power is a 227: 145:that occurred in almost all parts of 7: 458: 456: 391: 389: 158:hydropower plants in Eastern Turkey 472:. You can help Knowledge (XXG) by 419:. You can help Knowledge (XXG) by 14: 16:Nationwide power outage in Turkey 460: 400: 394: 343:Sabadus, Aura (16 April 2015). 31:2015 Türkiye Elektrik Kesintisi 242:. 6 April 2015. Archived from 1: 534:March 2015 events in Turkey 175:. When the Osmanca – 565: 455: 388: 296:10.1109/UPEC.2018.8541901 181:electric system in Turkey 30: 539:2015 disasters in Turkey 22:2015 Turkey power outage 529:Power outages in Europe 83:due to line maintenance 40:31 March 2015 10:26:24 415:-related article is a 204:power plants in Turkey 59:81 provinces in Turkey 544:Turkish history stubs 524:Power outages in Asia 549:Electric power stubs 139:2015 Turkey blackout 322:Hürriyet Daily News 271:, 21 September 2015 23: 104:Non-fatal injuries 481: 480: 428: 427: 141:was a widespread 135: 134: 556: 502: 495: 488: 464: 457: 449: 442: 435: 406: 405: 404: 398: 390: 380: 379: 373: 366: 360: 359: 357: 355: 340: 334: 333: 331: 329: 314: 308: 307: 289: 278: 272: 265: 256: 255: 253: 251: 246:on 10 April 2015 232: 172: 128:Publication bans 32: 27:Native name 24: 564: 563: 559: 558: 557: 555: 554: 553: 509: 508: 507: 506: 454: 453: 413:Turkish history 399: 393: 386: 384: 383: 368: 367: 363: 353: 351: 342: 341: 337: 327: 325: 316: 315: 311: 287: 280: 279: 275: 266: 259: 249: 247: 234: 233: 229: 224: 166: 162:capacitor banks 120:Property damage 17: 12: 11: 5: 562: 560: 552: 551: 546: 541: 536: 531: 526: 521: 519:2015 in Turkey 511: 510: 505: 504: 497: 490: 482: 479: 478: 465: 452: 451: 444: 437: 429: 426: 425: 408: 382: 381: 361: 335: 324:. 2 April 2015 309: 273: 257: 226: 225: 223: 220: 133: 132: 129: 125: 124: 121: 117: 116: 113: 109: 108: 105: 101: 100: 97: 93: 92: 89: 85: 84: 75: 71: 70: 65: 61: 60: 57: 53: 52: 49: 45: 44: 38: 34: 33: 28: 15: 13: 10: 9: 6: 4: 3: 2: 561: 550: 547: 545: 542: 540: 537: 535: 532: 530: 527: 525: 522: 520: 517: 516: 514: 503: 498: 496: 491: 489: 484: 483: 477: 475: 471: 466: 463: 459: 450: 445: 443: 438: 436: 431: 430: 424: 422: 418: 414: 409: 403: 397: 392: 387: 377: 376:Bloomberg.com 372: 365: 362: 350: 346: 339: 336: 323: 319: 313: 310: 305: 301: 297: 293: 286: 285: 277: 274: 270: 264: 262: 258: 245: 241: 237: 231: 228: 221: 219: 217: 212: 210: 205: 201: 200:Load shedding 197: 192: 190: 186: 182: 178: 174: 173:-secure state 170: 163: 159: 155: 150: 148: 144: 140: 130: 126: 122: 118: 114: 110: 106: 102: 98: 94: 90: 86: 82: 79: 76: 72: 69: 66: 62: 58: 54: 50: 46: 43: 39: 35: 29: 25: 19: 474:expanding it 467: 421:expanding it 410: 407:   385: 375: 364: 352:. Retrieved 349:www.icis.com 348: 338: 326:. Retrieved 321: 312: 304:hal-02330748 283: 276: 248:. Retrieved 244:the original 239: 230: 216:Turkish grid 213: 193: 168: 154:spring rains 151: 143:power outage 138: 136: 68:Power outage 18: 354:2 September 250:2 September 198:went down. 513:Categories 240:DailySabah 222:References 156:also left 78:Power line 196:frequency 328:13 March 267:ENTSOE, 189:Bulgaria 177:Kurşunlu 81:overload 56:Location 48:Duration 123:unknown 115:unknown 112:Missing 107:unknown 99:unknown 88:Outcome 51:8 hours 302:  185:Greece 147:Turkey 96:Deaths 411:This 288:(PDF) 74:Cause 470:stub 417:stub 356:2017 330:2024 252:2017 187:and 137:The 131:none 64:Type 37:Time 300:HAL 292:doi 171:-1) 42:EET 515:: 374:. 347:. 320:. 298:. 260:^ 238:. 209:Hz 501:e 494:t 487:v 476:. 448:e 441:t 434:v 423:. 378:. 358:. 332:. 306:. 294:: 254:. 169:n 167:(

Index

EET
Power outage
Power line
overload
power outage
Turkey
spring rains
hydropower plants in Eastern Turkey
capacitor banks
(n-1)-secure state
Kurşunlu
electric system in Turkey
Greece
Bulgaria
frequency
Load shedding
power plants in Turkey
Hz
Turkish grid
"Turkey's power outage linked to mismanagement, grid director resigns"
the original


Report on Blackout in Turkey on 31 March 2015
An analysis of large-scale transmission power blackouts from 2005 to 2016
doi
10.1109/UPEC.2018.8541901
HAL
hal-02330748
"Explained: How 76 million people were hit by Turkey's worst blackout since 1999"

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.